SPEC 85018
Multi-Conductor CU 600 V FR-XLPE Shielded PVC Jacket Control Cable Color Method 1 Table 1
Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

Construction:
- Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
- Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Shielding:5 mils tape shield
- Rip Cord:Rip cord for ease of jacket removal
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated construction can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
UL Listed
SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE CDRS 90C PVC JKT TYPE TC-ER SHIELDED 600V SUN. RES. DIRECT BURIAL YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Non UL Listed
SOUTHWIRE XX AWG X/C FR-XLPE CDRS SHIELDED 90C PVC JACKET SUNLIGHT RESISTANT 600V {YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | |||||
18 AWG | |||||||||||||||||||
673090 | 18 | 7 | 7 | 0.045 | 25 | 45 | 0.435 | 59 | 126 | 6.669 | 8.035 | 5.2 | 0 | 0 | 9 | ||||
672570 | 18 | 12 | 7 | 0.045 | 25 | 60 | 0.589 | 93 | 210 | 6.669 | 8.035 | 7 | 0 | 0 | 7 | ||||
14 AWG | |||||||||||||||||||
6195290 | 14 | 4 | 7 | 0.07 | 30 | 45 | 0.43 | 75 | 135 | 2.631 | 3.17 | 5.1 | 12 | 16 | 20 | ||||
625498 | 14 | 20 | 7 | 0.07 | 30 | 80 | 0.88 | 308 | 555 | 2.631 | 3.17 | 10.5 | 7 | 10 | 12 | ||||
12 AWG | |||||||||||||||||||
6732130 | 12 | 9 | 7 | 0.088 | 30 | 60 | 0.693 | 221 | 365 | 1.662 | 2.002 | 8.3 | 14 | 17 | 21 | ||||
620308 | 12 | 12 | 7 | 0.088 | 30 | 60 | 0.762 | 290 | 459 | 1.662 | 2.002 | 9.1 | 10 | 12 | 15 | ||||
10 AWG | |||||||||||||||||||
6067580 | 10 | 2 | 7 | 0.113 | 30 | 45 | 0.464 | 91 | 155 | 1.04 | 1.253 | 5.5 | 30 | 35 | 40 | ||||
6189310 | 10 | 3 | 7 | 0.113 | 30 | 45 | 0.483 | 124 | 197 | 1.04 | 1.253 | 5.7 | 30 | 35 | 40 | ||||
6285900 | 10 | 4 | 7 | 0.113 | 30 | 60 | 0.566 | 159 | 258 | 1.04 | 1.253 | 6.7 | 24 | 28 | 32 | ||||
5720430 | 10 | 2 | 7 | 0.113 | 30 | 60 | 0.58 | 103 | 207 | 1.04 | 1.253 | 6.9 | 30 | 35 | 40 | ||||
6195470 | 10 | 5 | 7 | 0.113 | 30 | 60 | 0.615 | 194 | 307 | 1.04 | 1.253 | 7.3 | 24 | 28 | 32 | ||||
6285870 | 10 | 7 | 7 | 0.113 | 30 | 60 | 0.663 | 262 | 395 | 1.04 | 1.253 | 7.9 | 21 | 24 | 28 | ||||
6067600 | 10 | 9 | 7 | 0.113 | 30 | 60 | 0.771 | 335 | 502 | 1.04 | 1.253 | 9.2 | 21 | 24 | 28 | ||||
6285810 | 10 | 12 | 7 | 0.113 | 30 | 80 | 0.903 | 438 | 673 | 1.04 | 1.253 | 10.8 | 15 | 17 | 20 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
^ UL Listed part number
^ UL Listed part number