SPEC 85018

Multi-Conductor CU 600 V FR-XLPE Shielded PVC Jacket Control Cable Color Method 1 Table 1

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Shielding:5 mils tape shield
  6. Rip Cord:Rip cord for ease of jacket removal
  7. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated construction can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • CSA CSA marking is available upon request
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE CDRS 90C PVC JKT TYPE TC-ER SHIELDED 600V SUN. RES. DIRECT BURIAL YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS SHIELDED 90C PVC JACKET SUNLIGHT RESISTANT 600V {YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.ColorInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CMin Bending RadiusAllowable Ampacity At 60°CAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    18 AWG
    67309018770.045M1T225450.448561266.6698.0355.4--9
    672570181270.045M1T225600.608892106.6698.0357.3--7
    14 AWG
    TBA14270.070M1T230450.37248922.6313.1704.5152025
    TBA14370.070M1T230450.392621122.6313.1704.7152025
    619529^14470.070M1T230450.440711342.6313.1705.3121620
    TBA14570.070M1T230450.463931542.6313.1705.6121620
    TBA14670.070M1T230450.5021101792.6313.1706.0121620
    606759^14770.070M1T130450.5191152022.6313.1706.2101417
    TBA14870.070M1T230600.5721392382.6313.1706.9101417
    TBA14970.070M1T230600.6111562652.6313.1707.3101417
    TBA141070.070M1T230600.6621722922.6313.1707.971012
    TBA141270.070M1T230600.6822003312.6313.1708.271012
    TBA141570.070M1T230600.7542443992.6313.1709.071012
    TBA141970.070M1T230600.7922994782.6313.1709.571012
    625498142070.070M1T230800.9013005602.6313.17010.871012
    TBA142570.070M1T230800.9623866472.6313.17011.56911
    TBA143070.070M1T230801.0154557492.6313.17012.26911
    TBA143770.070M1T230801.0925528932.6313.17013.16810
    12 AWG
    TBA12270.088M1T230450.408661171.6622.0024.9202530
    TBA12370.088M1T230450.431891471.6622.0025.2202530
    TBA12470.088M1T230450.4701121721.6622.0025.6162024
    TBA12570.088M1T230450.5111362051.6622.0026.1162024
    TBA12670.088M1T230600.5861602561.6622.0027.0162024
    TBA12770.088M1T230600.5861802821.6622.0027.0141721
    TBA12870.088M1T230600.6312043171.6622.0027.6141721
    673213^12970.088M1T130600.6992173651.6622.0028.4141721
    TBA121070.088M1T230600.7342543901.6622.0028.8101215
    620308121270.088M1T130600.7792834571.6622.0029.3101215
    TBA121570.088M1T230800.8793655771.6622.00210.5101215
    TBA121970.088M1T230800.9224506931.6622.00211.1101215
    TBA122070.088M1T230800.9674747291.6622.00211.6101215
    TBA122570.088M1T230801.0705858851.6622.00212.891113
    TBA123070.088M1T230801.13069210311.6622.00213.691113
    TBA123770.088M1T230801.21884112351.6622.00214.681012
    10 AWG
    606758^10270.113M1T230450.472871531.0401.2535.7303540
    618931^10370.113M1T230450.4961211971.0401.2536.0303540
    628590^10470.113M1T230600.5771562591.0401.2536.9242832
    572043^10270.113M1T230600.5801032091.0401.2537.0303540
    619547^10570.113M1T230600.6281923081.0401.2537.5242832
    TBA10670.113M1T230600.6612393521.0401.2537.9242832
    628587^10770.113M1T230600.6812594001.0401.2538.2212428
    TBA10870.113M1T230600.7143074401.0401.2538.6212428
    606760^10970.113M1T230600.7893315021.0401.2539.5212428
    TBA101070.113M1T230800.8743835781.0401.25310.5151720
    628581^101270.113M1T230800.9284346821.0401.25311.1151720
    TBA101570.113M1T230800.9965558041.0401.25312.0151720
    TBA101970.113M1T230801.0476899751.0401.25312.6151720
    TBA102070.113M1T230801.1072510261.0401.25313.2151720
    TBA102570.113M1T230801.22089812531.0401.25314.6131518
    TBA103070.113M1T230801.290106614671.0401.25315.5131518
    TBA103770.113M1T230801.393130017661.0401.25316.7121416
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for part numbers containing more than Three Current-Carrying Conductors.

    Revision: 1.000.001

    Updated On: Aug. 18, 2023, 2:41 p.m. UTC