SPEC 26541
HVTECK CU 3/C 280NLEPR TS PVC AIA PVC 28kV 100% CSA
3 Conductor, 280 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:280 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 280 NLEPR AIA 28kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | inch | mil | inch | lb/1000ft | |
TBA | 1 | 19 | 0.322 | 0.920 | 280 | 0.980 | 6 | 2.736 | 75 | 2.886 | 3812 |
TBA | 1/0 | 19 | 0.361 | 0.959 | 280 | 1.019 | 6 | 2.820 | 75 | 2.970 | 4159 |
TBA | 2/0 | 19 | 0.405 | 1.003 | 280 | 1.063 | 6 | 2.915 | 75 | 3.065 | 4579 |
TBA | 3/0 | 19 | 0.456 | 1.054 | 280 | 1.114 | 4 | 3.025 | 85 | 3.195 | 5157 |
TBA | 4/0 | 19 | 0.512 | 1.110 | 280 | 1.170 | 4 | 3.176 | 85 | 3.346 | 5870 |
TBA | 250 | 37 | 0.558 | 1.164 | 280 | 1.224 | 4 | 3.293 | 85 | 3.463 | 6449 |
TBA | 350 | 37 | 0.661 | 1.267 | 280 | 1.327 | 3 | 3.515 | 85 | 3.685 | 7789 |
TBA | 500 | 37 | 0.789 | 1.395 | 280 | 1.455 | 3 | 3.792 | 85 | 3.962 | 9703 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C† | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 20.2 | 2008 | 0.128 | 0.162 | 0.054 | 0.048 | 0.529 + j0.363 | 0.162 + j0.048 | 3036 | 202 | 226 |
1/0 | 20.7 | 2534 | 0.102 | 0.128 | 0.050 | 0.046 | 0.492 + j0.348 | 0.128 + j0.046 | 3157 | 231 | 256 |
2/0 | 21.4 | 3194 | 0.081 | 0.102 | 0.047 | 0.044 | 0.463 + j0.332 | 0.102 + j0.045 | 3293 | 265 | 290 |
3/0 | 22.3 | 4027 | 0.064 | 0.081 | 0.043 | 0.043 | 0.438 + j0.315 | 0.081 + j0.043 | 3451 | 303 | 327 |
4/0 | 23.4 | 5078 | 0.051 | 0.065 | 0.040 | 0.041 | 0.417 + j0.298 | 0.065 + j0.041 | 3625 | 348 | 369 |
250 | 24.2 | 6000 | 0.043 | 0.056 | 0.038 | 0.040 | 0.403 + j0.283 | 0.056 + j0.04 | 3792 | 384 | 408 |
350 | 25.7 | 8400 | 0.031 | 0.041 | 0.033 | 0.038 | 0.377 + j0.256 | 0.041 + j0.038 | 4111 | 468 | 485 |
500 | 27.7 | 12000 | 0.022 | 0.030 | 0.029 | 0.036 | 0.353 + j0.228 | 0.031 + j0.036 | 4508 | 565 | 571 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | kg/km | |
TBA | 1 | 19 | 8.18 | 23.37 | 7.11 | 24.89 | 6 | 69.49 | 1.91 | 73.30 | 5673 |
TBA | 1/0 | 19 | 9.17 | 24.36 | 7.11 | 25.88 | 6 | 71.63 | 1.91 | 75.44 | 6189 |
TBA | 2/0 | 19 | 10.29 | 25.48 | 7.11 | 27.00 | 6 | 74.04 | 1.91 | 77.85 | 6814 |
TBA | 3/0 | 19 | 11.58 | 26.77 | 7.11 | 28.30 | 4 | 76.84 | 2.16 | 81.15 | 7674 |
TBA | 4/0 | 19 | 13.00 | 28.19 | 7.11 | 29.72 | 4 | 80.67 | 2.16 | 84.99 | 8736 |
TBA | 250 | 37 | 14.17 | 29.57 | 7.11 | 31.09 | 4 | 83.64 | 2.16 | 87.96 | 9597 |
TBA | 350 | 37 | 16.79 | 32.18 | 7.11 | 33.71 | 3 | 89.28 | 2.16 | 93.60 | 11591 |
TBA | 500 | 37 | 20.04 | 35.43 | 7.11 | 36.96 | 3 | 96.32 | 2.16 | 100.63 | 14440 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C† | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 513.08 | 8936 | 0.4199 | 0.53 | 0.0165 | 0.1575 | 0.529 + j0.363 | 0.162 + j0.048 | 3036 | 202 | 226 |
1/0 | 525.78 | 11276 | 0.3346 | 0.42 | 0.0152 | 0.1509 | 0.492 + j0.348 | 0.128 + j0.046 | 3157 | 231 | 256 |
2/0 | 543.56 | 14213 | 0.2657 | 0.33 | 0.0143 | 0.1444 | 0.463 + j0.332 | 0.102 + j0.045 | 3293 | 265 | 290 |
3/0 | 566.42 | 17920 | 0.2100 | 0.27 | 0.0131 | 0.1411 | 0.438 + j0.315 | 0.081 + j0.043 | 3451 | 303 | 327 |
4/0 | 594.36 | 22597 | 0.1673 | 0.21 | 0.0122 | 0.1345 | 0.417 + j0.298 | 0.065 + j0.041 | 3625 | 348 | 369 |
250 | 614.68 | 26700 | 0.1411 | 0.18 | 0.0116 | 0.1312 | 0.403 + j0.283 | 0.056 + j0.04 | 3792 | 384 | 408 |
350 | 652.78 | 37380 | 0.1017 | 0.13 | 0.0101 | 0.1247 | 0.377 + j0.256 | 0.041 + j0.038 | 4111 | 468 | 485 |
500 | 703.58 | 53400 | 0.0722 | 0.10 | 0.0088 | 0.1181 | 0.353 + j0.228 | 0.031 + j0.036 | 4508 | 565 | 571 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C