SPEC 26471

HVTECK AL 3/C 260TRXLPE TS PVC AIA PVC 25kV 100% CSA

3 Conductor, 260 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:260 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 260 TRXLPE AIA 25kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGAWGmilinchinchmilinchlb/1000ftlb/1000ftinch
    TBA1190.2990.8572600.9171x661102.2272.537752.68731224113.5
    TBA1/0190.3360.8942600.9541x661102.3072.617752.76732225743.5
    TBA2/0190.3760.9342600.9941x661102.3932.703752.85333127613.5
    TBA3/0190.4230.9812601.0411x661102.4952.805752.95534329894
    TBA4/0190.4751.0332601.0931x661102.6072.917753.06735632554
    TBA250370.521.0862601.1461x441102.7213.031853.20141636244
    TBA350370.6161.1822601.2421x441252.9593.269853.43944041874.5
    TBA500370.7361.3022601.3621x331253.2183.528853.69850849895
    665880500340.7361.3262601.3861x331253.273.658853.82851357575
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    118.815060.2110.2890.0640.0320.660+j0.4260.289+j0.0462872158177
    1/019.419000.1670.2290.0590.030.599+j0.4110.229+j0.0452987181200
    2/02023950.1330.1820.0550.0280.551+j0.3950.182+j0.0433111208228
    3/020.730200.1050.1440.0510.0270.511+j0.3770.144+j0.0413256239258
    4/021.538080.0840.1150.0480.0250.479+j0.3590.115+j0.0403418273292
    25022.445000.070.0960.0440.0240.457+j0.3420.096+j0.0393582302321
    35024.163000.0510.070.0390.0220.425+j0.3140.070+j0.0373879368385
    50025.990000.0360.050.0350.020.395+j0.2830.050+j0.0354251454462
    50026.890000.0360.050.0360.020.394+j0.2780.050+j0.0354325454462
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundGround SizeInner Jacket ThicknessDia. Over Inner JacketDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGAWGmmmmmmmmmmkg/kmkg/kminch
    TBA1197.5921.776.6023.291x662.7956.5764.441.9168.2546435883.5
    TBA1/0198.5322.716.6024.231x662.7958.6066.471.9170.2847938313.5
    TBA2/0199.5523.726.6025.251x662.7960.7868.661.9172.4749341093.5
    TBA3/01910.7424.926.6026.441x662.7963.3771.251.9175.0651044484
    TBA4/01912.0726.246.6027.761x662.7966.2274.091.9177.9053048444
    TBA2503713.2127.586.6029.111x442.7969.1176.992.1681.3161953934
    TBA3503715.6530.026.6031.551x443.1875.1683.032.1687.3565562314.5
    TBA5003718.6933.076.6034.591x333.1881.7489.612.1693.9375674245
    6658805003418.6933.686.6035.201x333.1883.0692.912.1697.2376385675
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    1477.5267020.69230.950.01950.10500.660+j0.4260.289+j0.0462872158177
    1/0492.7684550.54790.750.01800.09840.599+j0.4110.229+j0.0452987181200
    2/0508.00106580.43640.600.01680.09190.551+j0.3950.182+j0.0433111208228
    3/0525.78134390.34450.470.01550.08860.511+j0.3770.144+j0.0413256239258
    4/0546.10169460.27560.380.01460.08200.479+j0.3590.115+j0.0403418273292
    250568.96200250.22970.310.01340.07870.457+j0.3420.096+j0.0393582302321
    350612.14280350.16730.230.01190.07220.425+j0.3140.070+j0.0373879368385
    500657.86400500.11810.160.01070.06560.395+j0.2830.050+j0.0354251454462
    500680.72400500.11810.160.01100.06560.394+j0.2780.050+j0.0354325454462
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E

    Revision: 1.000.000