SPEC 26442
HVTECK CU 3/C 320NLEPR TS PVC AIA PVC 25kV 133% CSA
3 Conductor, 320 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:320 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 320 NLEPR AIA 25kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | inch | mil | inch | lb/1000ft | |
581881^ | 1 | 19 | 0.322 | 1.000 | 320 | 1.060 | 4 | 2.903 | 75 | 3.053 | 4124 |
675390 | 1/0 | 19 | 0.361 | 1.040 | 320 | 1.100 | 6 | 2.989 | 75 | 3.139 | 4528 |
TBA | 2/0 | 19 | 0.405 | 1.083 | 320 | 1.143 | 6 | 3.118 | 85 | 3.288 | 5121 |
TBA | 3/0 | 19 | 0.456 | 1.134 | 320 | 1.194 | 4 | 3.228 | 85 | 3.398 | 5652 |
678708^^ | 4/0 | 19 | 0.512 | 1.176 | 320 | 1.236 | 4 | 3.333 | 85 | 3.503 | 5959 |
TBA | 250 | 37 | 0.558 | 1.244 | 320 | 1.304 | 4 | 3.465 | 85 | 3.635 | 6878 |
TBA | 350 | 37 | 0.661 | 1.347 | 320 | 1.407 | 3 | 3.688 | 85 | 3.858 | 8246 |
TBA | 500 | 37 | 0.789 | 1.475 | 320 | 1.535 | 3 | 3.964 | 85 | 4.134 | 10185 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
^ Red outer jacket
^^ Yellow outer jacket
^ Red outer jacket
^^ Yellow outer jacket
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C† | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 21.3 | 2008 | 0.128 | 0.162 | 0.059 | 0.050 | 0.523 + j0.339 | 0.162 + j0.05 | 3284 | 202 | 226 |
1/0 | 21.9 | 2534 | 0.102 | 0.128 | 0.055 | 0.048 | 0.486 + j0.325 | 0.128 + j0.048 | 3405 | 231 | 256 |
2/0 | 23.0 | 3194 | 0.081 | 0.102 | 0.051 | 0.046 | 0.456 + j0.31 | 0.102 + j0.046 | 3541 | 265 | 290 |
3/0 | 23.7 | 4027 | 0.064 | 0.081 | 0.047 | 0.044 | 0.43 + j0.295 | 0.081 + j0.044 | 3699 | 303 | 327 |
4/0 | 24.5 | 5078 | 0.051 | 0.065 | 0.044 | 0.043 | 0.409 + j0.279 | 0.065 + j0.043 | 3872 | 348 | 369 |
250 | 25.4 | 6000 | 0.043 | 0.056 | 0.041 | 0.042 | 0.395 + j0.265 | 0.056 + j0.042 | 4040 | 384 | 408 |
350 | 27.0 | 8400 | 0.031 | 0.041 | 0.037 | 0.039 | 0.369 + j0.241 | 0.042 + j0.039 | 4359 | 468 | 485 |
500 | 28.9 | 12000 | 0.022 | 0.030 | 0.032 | 0.037 | 0.345 + j0.215 | 0.031 + j0.037 | 4755 | 565 | 571 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | kg/km | |
581881^ | 1 | 19 | 8.18 | 25.40 | 8.13 | 26.92 | 4 | 73.74 | 1.91 | 77.55 | 6137 |
675390 | 1/0 | 19 | 9.17 | 26.42 | 8.13 | 27.94 | 6 | 75.92 | 1.91 | 79.73 | 6738 |
TBA | 2/0 | 19 | 10.29 | 27.51 | 8.13 | 29.03 | 6 | 79.20 | 2.16 | 83.52 | 7621 |
TBA | 3/0 | 19 | 11.58 | 28.80 | 8.13 | 30.33 | 4 | 81.99 | 2.16 | 86.31 | 8411 |
678708^^ | 4/0 | 19 | 13.00 | 29.87 | 8.13 | 31.39 | 4 | 84.66 | 2.16 | 88.98 | 8868 |
TBA | 250 | 37 | 14.17 | 31.60 | 8.13 | 33.12 | 4 | 88.01 | 2.16 | 92.33 | 10236 |
TBA | 350 | 37 | 16.79 | 34.21 | 8.13 | 35.74 | 3 | 93.68 | 2.16 | 97.99 | 12271 |
TBA | 500 | 37 | 20.04 | 37.47 | 8.13 | 38.99 | 3 | 100.69 | 2.16 | 105.00 | 15157 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
^ Red outer jacket
^^ Yellow outer jacket
^ Red outer jacket
^^ Yellow outer jacket
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C† | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1 | 541.02 | 8936 | 0.4199 | 0.53 | 0.0180 | 0.1640 | 0.523 + j0.339 | 0.162 + j0.05 | 3284 | 202 | 226 |
1/0 | 556.26 | 11276 | 0.3346 | 0.42 | 0.0168 | 0.1575 | 0.486 + j0.325 | 0.128 + j0.048 | 3405 | 231 | 256 |
2/0 | 584.20 | 14213 | 0.2657 | 0.33 | 0.0155 | 0.1509 | 0.456 + j0.31 | 0.102 + j0.046 | 3541 | 265 | 290 |
3/0 | 601.98 | 17920 | 0.2100 | 0.27 | 0.0143 | 0.1444 | 0.43 + j0.295 | 0.081 + j0.044 | 3699 | 303 | 327 |
4/0 | 622.30 | 22597 | 0.1673 | 0.21 | 0.0134 | 0.1411 | 0.409 + j0.279 | 0.065 + j0.043 | 3872 | 348 | 369 |
250 | 645.16 | 26700 | 0.1411 | 0.18 | 0.0125 | 0.1378 | 0.395 + j0.265 | 0.056 + j0.042 | 4040 | 384 | 408 |
350 | 685.80 | 37380 | 0.1017 | 0.13 | 0.0113 | 0.1280 | 0.369 + j0.241 | 0.042 + j0.039 | 4359 | 468 | 485 |
500 | 734.06 | 53400 | 0.0722 | 0.10 | 0.0098 | 0.1214 | 0.345 + j0.215 | 0.031 + j0.037 | 4755 | 565 | 571 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C