SPEC 26406

HVTECK CU 1/C 320NLEPR CB PVC AIA PVC 25kV 133% CSA

Single Conductor, 320 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:320 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 320 NLEPR AIA 25kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGinchmilinchlb/1000ft
    TBA1190.3221.0003201.06011 x 141.710601.8301487
    TBA1/0190.3611.0393201.09911 x 141.749601.8691595
    TBA2/0190.4051.0833201.14311 x 141.793601.9131726
    TBA3/0190.4561.1343201.19413 x 141.844601.9641917
    TBA4/0190.5121.1903201.25013 x 141.900602.0202204
    TBA250370.5581.2443201.30417 x 141.954602.0742440
    TBA350370.6611.3473201.40721 x 142.117602.2373042
    TBA500370.7891.4753201.53526 x 142.245602.3653725
    TBA750610.9681.6643201.72421 x 122.468752.6184911
    TBA1000611.1171.8133201.87321 x 122.617752.7675865
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    112.86690.1280.1620.0590.0620.144 + j0.0370.15 + j0.0458577245244
    1/013.08440.1020.1280.0550.0590.11 + j0.0350.116 + j0.0438577278272
    2/013.310640.0810.1020.0510.0570.084 + j0.0330.09 + j0.0418577316303
    3/013.713420.0640.0810.0470.0550.063 + j0.0310.069 + j0.03910137356333
    4/014.116920.0510.0650.0440.0530.047 + j0.0290.053 + j0.03810137403367
    25014.520000.0430.0560.0410.0520.038 + j0.0280.044 + j0.03613256455411
    35015.628000.0310.0410.0370.0500.023 + j0.0260.029 + j0.03416376537459
    50016.540000.0220.0300.0320.0470.012 + j0.0240.018 + j0.03220275616499
    75018.360000.0140.0230.0280.0450.005 + j0.0220.012 + j0.0326018716557
    100019.380000.0110.0190.0250.0430.001 + j0.020.008 + j0.02826018825608
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmkg/km
    TBA1198.1825.408.1326.9211 x 1443.431.5246.482213
    TBA1/0199.1726.398.1327.9111 x 1444.421.5247.472374
    TBA2/01910.2927.518.1329.0311 x 1445.541.5248.592569
    TBA3/01911.5828.808.1330.3313 x 1446.841.5249.892853
    TBA4/01913.0030.238.1331.7513 x 1448.261.5251.313280
    TBA2503714.1731.608.1333.1217 x 1449.631.5252.683631
    TBA3503716.7934.218.1335.7421 x 1453.771.5256.824527
    TBA5003720.0437.478.1338.9926 x 1457.021.5260.075543
    TBA7506124.5942.278.1343.7921 x 1262.691.9166.507308
    TBA10006128.3746.058.1347.5721 x 1266.471.9170.288728
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    1325.1229770.41990.530.01800.20340.144 + j0.0370.15 + j0.0458577245244
    1/0330.2037560.33460.420.01680.19360.11 + j0.0350.116 + j0.0438577278272
    2/0337.8247350.26570.330.01550.18700.084 + j0.0330.09 + j0.0418577316303
    3/0347.9859720.21000.270.01430.18040.063 + j0.0310.069 + j0.03910137356333
    4/0358.1475290.16730.210.01340.17390.047 + j0.0290.053 + j0.03810137403367
    250368.3089000.14110.180.01250.17060.038 + j0.0280.044 + j0.03613256455411
    350396.24124600.10170.130.01130.16400.023 + j0.0260.029 + j0.03416376537459
    500419.10178000.07220.100.00980.15420.012 + j0.0240.018 + j0.03220275616499
    750464.82267000.04590.080.00850.14760.005 + j0.0220.012 + j0.0326018716557
    1000490.22356000.03610.060.00760.14110.001 + j0.020.008 + j0.02826018825608
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C