SPEC 26372

HVTECK AL 3/C 220TRXLPE TS PVC AIA PVC 15kV 133% CSA

3 Conductor, 220 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:220 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    {SQMTR_DUAL} {CSA} SOUTHWIRE® POWER CABLE {NESC} 3/C XXX AWG COMPACT AL.--- {ALUMAFLEX}® AA8176 XXX mm (220 mils) TR-XLPE AIA GW X x X AWG CU 15KV 133% INS LEVEL 25%TS MV68.10 SUN. RES. 105°C FT4 HL (-40°C) LTGG RoHS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ftinch
    TBA270.2680.7462200.8061x81102.297752.44725519773
    TBA1190.2990.7772200.8371x61102.364752.51429221313
    6694391/0100.3360.8142200.8741x61102.502752.65231028213.5
    TBA2/0190.3760.8542200.9141x61102.53752.6831224643.5
    4562942/0120.3760.8542200.9141x61102.588752.73832429213.5
    TBA3/0190.4230.9012200.9611x61102.632752.78232326803.5
    TBA4/0190.4750.9532201.0131x61102.744752.89433629343.5
    6657184/0190.4750.9532201.0131x61102.81752.9634734714
    TBA250370.521.0062201.0661x41102.859753.00939632344
    664830350370.6161.1022201.1621x41253.174853.34443045474.5
    456295350370.6161.1022201.1621x41253.174853.34443045624.5
    665713350370.6161.1022201.1621x41253.174853.34443045624.5
    664692500340.7361.2442201.3041x31253.48853.6549453925
    456300750530.9081.4162201.4761x21253.861854.03158166605.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    ^Yellow jacket
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    217.111940.2660.3650.0610.0310.735+j0.4710.365+j0.0472528135157
    117.615060.2110.2890.0570.030.660+j0.4550.289+j0.0442624154178
    1/018.619000.1670.2290.0530.0280.600+j0.4390.229+j0.0432739176202
    2/018.823950.1330.1820.0490.0260.553+j0.4220.182+j0.0412863204229
    2/019.223950.1330.1820.0490.0260.553+j0.4220.182+j0.0412863204229
    3/019.530200.1050.1440.0460.0250.514+j0.4030.144+j0.0403009234260
    4/020.338080.0840.1150.0420.0230.483+j0.3830.115+j0.0383170268294
    4/020.738080.0840.1150.0420.0230.483+j0.3830.115+j0.0383170268294
    25021.145000.070.0960.0390.0220.462+j0.3650.096+j0.0373334296323
    35023.463000.0510.070.0350.0210.430+j0.3340.070+j0.0353631363386
    35023.463000.0510.070.0350.0210.430+j0.3340.070+j0.0353631363386
    35023.463000.0510.070.0350.0210.430+j0.3340.070+j0.0353631363386
    50025.690000.0360.050.0320.0190.400+j0.2950.050+j0.0344071447465
    75028.2135000.0230.0330.0260.0170.369+j0.2550.033+j0.0324604566563
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGroundInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/kminch
    TBA276.8118.955.5920.471x82.7958.341.9162.1537929423
    TBA1197.5919.745.5921.261x62.7960.051.9163.8643531713
    6694391/0108.5320.685.5922.201x62.7963.551.9167.3646141983.5
    TBA2/0199.5521.695.5923.221x62.7964.261.9168.0746436673.5
    4562942/0129.5521.695.5923.221x62.7965.741.9169.5548243473.5
    TBA3/01910.7422.895.5924.411x62.7966.851.9170.6648139883.5
    TBA4/01912.0724.215.5925.731x62.7969.701.9173.5150043663.5
    6657184/01912.0724.215.5925.731x62.7971.371.9175.1851651654
    TBA2503713.2125.555.5927.081x42.7972.621.9176.4358948134
    6648303503715.6527.995.5929.511x43.1880.622.1684.9464067674.5
    4562953503715.6527.995.5929.511x43.1880.622.1684.9464067894.5
    6657133503715.6527.995.5929.511x43.1880.622.1684.9464067894.5
    6646925003418.6931.605.5933.121x33.1888.392.1692.7173580245
    4563007505323.0635.975.5937.491x23.1898.072.16102.3986599115.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    ^Yellow jacket
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2434.3453130.87271.200.01860.10170.735+j0.4710.365+j0.0472528135157
    1447.0467020.69230.950.01740.09840.660+j0.4550.289+j0.0442624154178
    1/0472.4484550.54790.750.01620.09190.600+j0.4390.229+j0.0432739176202
    2/0477.52106580.43640.600.01490.08530.553+j0.4220.182+j0.0412863204229
    2/0487.68106580.43640.600.01490.08530.553+j0.4220.182+j0.0412863204229
    3/0495.30134390.34450.470.01400.08200.514+j0.4030.144+j0.0403009234260
    4/0515.62169460.27560.380.01280.07550.483+j0.3830.115+j0.0383170268294
    4/0525.78169460.27560.380.01280.07550.483+j0.3830.115+j0.0383170268294
    250535.94200250.22970.310.01190.07220.462+j0.3650.096+j0.0373334296323
    350594.36280350.16730.230.01070.06890.430+j0.3340.070+j0.0353631363386
    350594.36280350.16730.230.01070.06890.430+j0.3340.070+j0.0353631363386
    350594.36280350.16730.230.01070.06890.430+j0.3340.070+j0.0353631363386
    500650.24400500.11810.160.00980.06230.400+j0.2950.050+j0.0344071447465
    750716.28600750.07550.110.00790.05580.369+j0.2550.033+j0.0324604566563
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3/C in air copper and aluminum: D17N
    3/C direct buried copper and aluminum: D17E

    Revision: 1.000.002

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC