SPEC 26372

HVTECK AL 3/C 220TRXLPE TS PVC AIA PVC 15kV 133% CSA

3 Conductor, 220 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:220 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    {SQMTR_DUAL} {CSA} SOUTHWIRE{R} POWER CABLE {NESC} 3/C XXX AWG COMPACT AL.--- {ALUMAFLEX}{R} AA8176 XXX mm (220 mils) TR-XLPE AIA GW X x X AWG CU 15KV 133% INS LEVEL 25%TS MV68.10 SUN. RES. 105{D}C FT4 HL (-40{D}C) LTGG RoHS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchAWGmilinchmilinchlb/1000ft
    TBA270.2680.7462200.80681102.360752.5102529
    TBA1190.2980.7762200.83661102.424752.5742673
    6694391/0100.3360.8142200.87461102.501752.6512807
    TBA2/0190.3760.8542200.91461102.593752.7433073
    TBA3/0190.4220.9002200.96061102.692752.8423325
    TBA4/0190.4740.9522201.01261102.805752.9553627
    TBA250370.5201.0062201.06641102.921753.0713929
    664830350370.6151.1022201.16241253.173853.3434529
    TBA500370.7351.2212201.28131253.416853.5865561
    TBA750610.9081.4042201.46421253.811853.9816968
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    217.511940.2670.3360.0690.0480.711 + j0.4310.336 + j0.0472497135157
    118.015060.2110.2660.0640.0460.64 + j0.4150.266 + j0.0442590154178
    1/018.519000.1680.2110.0600.0440.584 + j0.3980.211 + j0.0432707176202
    2/019.223950.1330.1670.0550.0430.538 + j0.3810.167 + j0.0412831204229
    3/019.830200.1050.1330.0510.0410.501 + j0.3620.133 + j0.042974234260
    4/020.638080.0840.1050.0470.0400.47 + j0.3420.105 + j0.0383135268294
    25021.445000.0710.0900.0440.0390.451 + j0.3240.09 + j0.0373302296323
    35023.463000.0500.0650.0390.0370.417 + j0.2940.065 + j0.0353597363386
    50025.190000.0350.0460.0340.0350.387 + j0.2620.046 + j0.0333968447465
    75027.8135000.0240.0330.0290.0330.356 + j0.2220.034 + j0.0314536566563
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmAWGmmmmmmmmkg/km
    TBA276.8118.955.5920.4782.7959.941.9163.753764
    TBA1197.5719.715.5921.2362.7961.571.9165.383978
    6694391/0108.5320.685.5922.2062.7963.531.9167.344177
    TBA2/0199.5521.695.5923.2262.7965.861.9169.674573
    TBA3/01910.7222.865.5924.3862.7968.381.9172.194948
    TBA4/01912.0424.185.5925.7062.7971.251.9175.065398
    TBA2503713.2125.555.5927.0842.7974.191.9178.005847
    6648303503715.6227.995.5929.5143.1880.592.1684.916740
    TBA5003718.6731.015.5932.5433.1886.772.1691.088276
    TBA7506123.0635.665.5937.1923.1896.802.16101.1210370
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2444.5053130.87601.100.02100.15750.711 + j0.4310.336 + j0.0472497135157
    1457.2067020.69230.870.01950.15090.64 + j0.4150.266 + j0.0442590154178
    1/0469.9084550.55120.690.01830.14440.584 + j0.3980.211 + j0.0432707176202
    2/0487.68106580.43640.550.01680.14110.538 + j0.3810.167 + j0.0412831204229
    3/0502.92134390.34450.440.01550.13450.501 + j0.3620.133 + j0.042974234260
    4/0523.24169460.27560.340.01430.13120.47 + j0.3420.105 + j0.0383135268294
    250543.56200250.23290.300.01340.12800.451 + j0.3240.09 + j0.0373302296323
    350594.36280350.16400.210.01190.12140.417 + j0.2940.065 + j0.0353597363386
    500637.54400500.11480.150.01040.11480.387 + j0.2620.046 + j0.0333968447465
    750706.12600750.07870.110.00880.10830.356 + j0.2220.034 + j0.0314536566563
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000