SPEC 26331

HVTECK AL 1/C 175TRXLPE TS PVC AIA PVC 15kV 100% CSA

Single Conductor, 175 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:175 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 175 TRXLPE AIA 15kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ft
    270.2680.6561750.716801.118501.218691
    1190.2980.6861750.746801.148501.248732
    1/0190.3360.7241750.784801.186501.286787
    2/0190.3760.7641750.824801.336501.436858
    3/0190.4220.8101750.870801.382501.482930
    4/0190.4740.8621750.922801.434501.5341016
    250370.5200.9161750.976801.488501.5881103
    350370.6151.0111751.071801.583601.7031312
    500370.7351.1311751.191801.727601.8471596
    750610.9081.3141751.374801.910602.0302099
    1000611.0601.4661751.5261102.122602.2422605
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    28.53980.2670.3360.0600.0570.697 + j0.4660.337 + j0.0562218169176
    18.75020.2110.2660.0560.0550.629 + j0.4490.267 + j0.0532311194198
    1/09.06330.1680.2110.0520.0530.574 + j0.4310.212 + j0.0512429222223
    2/010.07980.1330.1670.0480.0530.529 + j0.4120.168 + j0.0512552255250
    3/010.310060.1050.1330.0440.0510.494 + j0.3920.134 + j0.0492695290278
    4/010.712690.0840.1050.0400.0490.465 + j0.3710.106 + j0.0472856329309
    25011.115000.0710.0900.0380.0470.447 + j0.3510.091 + j0.0463024370347
    35011.921000.0500.0650.0330.0450.417 + j0.3190.066 + j0.0433318446402
    50012.930000.0350.0460.0290.0430.388 + j0.2830.047 + j0.0413689533451
    75014.245000.0240.0330.0250.0400.359 + j0.2390.034 + j0.0394257631500
    100015.660000.0180.0260.0220.0390.338 + j0.210.027 + j0.0384728707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/km
    276.8116.664.4418.192.0328.401.2730.941028
    1197.5717.424.4418.952.0329.161.2731.701089
    1/0198.5318.394.4419.912.0330.121.2732.661171
    2/0199.5519.414.4420.932.0333.931.2736.471277
    3/01910.7220.574.4422.102.0335.101.2737.641384
    4/01912.0421.894.4423.422.0336.421.2738.961512
    2503713.2123.274.4424.792.0337.801.2740.341641
    3503715.6225.684.4427.202.0340.211.5243.261952
    5003718.6728.734.4430.252.0343.871.5246.912375
    7506123.0633.384.4434.902.0348.511.5251.563124
    10006126.9237.244.4438.762.7953.901.5256.953877
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ/kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2215.9017710.87601.100.01830.18700.697 + j0.4660.337 + j0.0562218169176
    1220.9822340.69230.870.01710.18040.629 + j0.4490.267 + j0.0532311194198
    1/0228.6028170.55120.690.01580.17390.574 + j0.4310.212 + j0.0512429222223
    2/0254.0035510.43640.550.01460.17390.529 + j0.4120.168 + j0.0512552255250
    3/0261.6244770.34450.440.01340.16730.494 + j0.3920.134 + j0.0492695290278
    4/0271.7856470.27560.340.01220.16080.465 + j0.3710.106 + j0.0472856329309
    250281.9466750.23290.300.01160.15420.447 + j0.3510.091 + j0.0463024370347
    350302.2693450.16400.210.01010.14760.417 + j0.3190.066 + j0.0433318446402
    500327.66133500.11480.150.00880.14110.388 + j0.2830.047 + j0.0413689533451
    750360.68200250.07870.110.00760.13120.359 + j0.2390.034 + j0.0394257631500
    1000396.24267000.05910.090.00670.12800.338 + j0.210.027 + j0.0384728707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:39 p.m. UTC