SPEC 26331
HVTECK AL 1/C 175TRXLPE TS PVC AIA PVC 15kV 100% CSA
Single Conductor, 175 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:175 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 175 TRXLPE AIA 15kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 2 | 7 | 0.268 | 0.656 | 175 | 0.716 | 80 | 1.106 | 50 | 1.206 | 59 | 722 | 3 |
| 1 | 19 | 0.299 | 0.687 | 175 | 0.747 | 80 | 1.137 | 50 | 1.237 | 62 | 766 | 3 |
| 1/0 | 19 | 0.336 | 0.724 | 175 | 0.784 | 80 | 1.174 | 50 | 1.274 | 65 | 819 | 3 |
| 2/0 | 19 | 0.376 | 0.764 | 175 | 0.824 | 80 | 1.214 | 50 | 1.314 | 68 | 882 | 3.5 |
| 3/0 | 19 | 0.423 | 0.811 | 175 | 0.871 | 80 | 1.261 | 50 | 1.361 | 72 | 957 | 3.5 |
| 4/0 | 19 | 0.475 | 0.863 | 175 | 0.923 | 80 | 1.313 | 50 | 1.413 | 76 | 1045 | 3.5 |
| 250 | 37 | 0.52 | 0.916 | 175 | 0.976 | 80 | 1.366 | 50 | 1.466 | 80 | 1133 | 4 |
| 350 | 37 | 0.616 | 1.012 | 175 | 1.072 | 80 | 1.562 | 60 | 1.682 | 88 | 1487 | 4.5 |
| 500 | 37 | 0.736 | 1.132 | 175 | 1.192 | 80 | 1.682 | 60 | 1.802 | 98 | 1751 | 4.5 |
| 750 | 61 | 0.908 | 1.314 | 175 | 1.374 | 80 | 1.864 | 60 | 1.984 | 113 | 2180 | 5 |
| 1000 | 61 | 1.117 | 1.523 | 175 | 1.583 | 110 | 2.133 | 60 | 2.253 | 130 | 2748 | 6 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 8.4 | 398 | 0.266 | 0.365 | 0.052 | 0.056 | 0.712+j0.499 | 0.366+j0.061 | 2249 | 169 | 176 |
| 1 | 8.7 | 502 | 0.211 | 0.289 | 0.048 | 0.054 | 0.638+j0.483 | 0.290+j0.058 | 2345 | 194 | 198 |
| 1/0 | 8.9 | 633 | 0.167 | 0.229 | 0.045 | 0.052 | 0.580+j0.467 | 0.230+j0.056 | 2460 | 222 | 223 |
| 2/0 | 9.2 | 798 | 0.133 | 0.182 | 0.042 | 0.05 | 0.535+j0.449 | 0.183+j0.054 | 2584 | 255 | 250 |
| 3/0 | 9.5 | 1006 | 0.105 | 0.144 | 0.038 | 0.049 | 0.499+j0.430 | 0.145+j0.052 | 2730 | 290 | 278 |
| 4/0 | 9.9 | 1269 | 0.084 | 0.115 | 0.035 | 0.047 | 0.470+j0.410 | 0.116+j0.051 | 2891 | 329 | 309 |
| 250 | 10.3 | 1500 | 0.07 | 0.096 | 0.033 | 0.046 | 0.451+j0.390 | 0.097+j0.049 | 3055 | 370 | 347 |
| 350 | 11.8 | 2100 | 0.051 | 0.07 | 0.029 | 0.045 | 0.421+j0.358 | 0.071+j0.049 | 3352 | 446 | 402 |
| 500 | 12.6 | 3000 | 0.036 | 0.05 | 0.025 | 0.042 | 0.396+j0.322 | 0.051+j0.046 | 3724 | 533 | 451 |
| 750 | 13.9 | 4500 | 0.023 | 0.033 | 0.021 | 0.04 | 0.367+j0.276 | 0.035+j0.043 | 4288 | 631 | 500 |
| 1000 | 15.8 | 6000 | 0.017 | 0.025 | 0.018 | 0.038 | 0.344+j0.235 | 0.027+j0.043 | 4936 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | mm | mm | mm | mm | kg/km | kg/km | inch |
| 2 | 7 | 6.81 | 16.66 | 4.44 | 18.19 | 2.03 | 28.09 | 1.27 | 30.63 | 88 | 1074 | 3 |
| 1 | 19 | 7.59 | 17.45 | 4.44 | 18.97 | 2.03 | 28.88 | 1.27 | 31.42 | 92 | 1140 | 3 |
| 1/0 | 19 | 8.53 | 18.39 | 4.44 | 19.91 | 2.03 | 29.82 | 1.27 | 32.36 | 97 | 1219 | 3 |
| 2/0 | 19 | 9.55 | 19.41 | 4.44 | 20.93 | 2.03 | 30.84 | 1.27 | 33.38 | 101 | 1313 | 3.5 |
| 3/0 | 19 | 10.74 | 20.60 | 4.44 | 22.12 | 2.03 | 32.03 | 1.27 | 34.57 | 107 | 1424 | 3.5 |
| 4/0 | 19 | 12.07 | 21.92 | 4.44 | 23.44 | 2.03 | 33.35 | 1.27 | 35.89 | 113 | 1555 | 3.5 |
| 250 | 37 | 13.21 | 23.27 | 4.44 | 24.79 | 2.03 | 34.70 | 1.27 | 37.24 | 119 | 1686 | 4 |
| 350 | 37 | 15.65 | 25.70 | 4.44 | 27.23 | 2.03 | 39.67 | 1.52 | 42.72 | 131 | 2213 | 4.5 |
| 500 | 37 | 18.69 | 28.75 | 4.44 | 30.28 | 2.03 | 42.72 | 1.52 | 45.77 | 146 | 2606 | 4.5 |
| 750 | 61 | 23.06 | 33.38 | 4.44 | 34.90 | 2.03 | 47.35 | 1.52 | 50.39 | 168 | 3244 | 5 |
| 1000 | 61 | 28.37 | 38.68 | 4.44 | 40.21 | 2.79 | 54.18 | 1.52 | 57.23 | 193 | 4089 | 6 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 213.36 | 1771 | 0.8727 | 1.20 | 0.0158 | 0.1837 | 0.712+j0.499 | 0.366+j0.061 | 2249 | 169 | 176 |
| 1 | 220.98 | 2234 | 0.6923 | 0.95 | 0.0146 | 0.1772 | 0.638+j0.483 | 0.290+j0.058 | 2345 | 194 | 198 |
| 1/0 | 226.06 | 2817 | 0.5479 | 0.75 | 0.0137 | 0.1706 | 0.580+j0.467 | 0.230+j0.056 | 2460 | 222 | 223 |
| 2/0 | 233.68 | 3551 | 0.4364 | 0.60 | 0.0128 | 0.1640 | 0.535+j0.449 | 0.183+j0.054 | 2584 | 255 | 250 |
| 3/0 | 241.30 | 4477 | 0.3445 | 0.47 | 0.0116 | 0.1608 | 0.499+j0.430 | 0.145+j0.052 | 2730 | 290 | 278 |
| 4/0 | 251.46 | 5647 | 0.2756 | 0.38 | 0.0107 | 0.1542 | 0.470+j0.410 | 0.116+j0.051 | 2891 | 329 | 309 |
| 250 | 261.62 | 6675 | 0.2297 | 0.31 | 0.0101 | 0.1509 | 0.451+j0.390 | 0.097+j0.049 | 3055 | 370 | 347 |
| 350 | 299.72 | 9345 | 0.1673 | 0.23 | 0.0088 | 0.1476 | 0.421+j0.358 | 0.071+j0.049 | 3352 | 446 | 402 |
| 500 | 320.04 | 13350 | 0.1181 | 0.16 | 0.0076 | 0.1378 | 0.396+j0.322 | 0.051+j0.046 | 3724 | 533 | 451 |
| 750 | 353.06 | 20025 | 0.0755 | 0.11 | 0.0064 | 0.1312 | 0.367+j0.276 | 0.035+j0.043 | 4288 | 631 | 500 |
| 1000 | 401.32 | 26700 | 0.0558 | 0.08 | 0.0055 | 0.1247 | 0.344+j0.235 | 0.027+j0.043 | 4936 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC

