SPEC 26272

HVTECK AL 3/C 140TRXLPE TS PVC AIA PVC 8kV 133% CSA

3 Conductor, 140 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:140 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 140 TRXLPE AIA 8kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchAWGinchmilinchlb/1000ft
    673689280.2680.5861400.64681.949602.0691726
    6527781190.2980.6171400.67762.076602.1961985
    6720791/0100.3360.6541400.71462.156602.2762171
    6742492/0120.3760.6941400.75462.118602.2382291
    TBA3/0190.4220.7401400.80062.347752.4972661
    6720704/0190.4740.7931400.85362.456752.6062896
    TBA250370.5200.8461400.90642.576752.7263214
    652787350370.6150.9421401.00242.778752.9283750
    674257500340.7351.0841401.14433.134853.3044747
    TBA750610.9081.2441401.30423.465853.6356046
    TBA1000611.0601.3961401.45623.794853.9647265
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    214.411940.2670.3360.0530.0430.707 + j0.5030.336 + j0.0422001135157
    115.315060.2110.2660.0490.0410.639 + j0.4850.266 + j0.042094154178
    1/015.919000.1680.2110.0450.0400.585 + j0.4640.211 + j0.0382212176202
    2/015.615970.1330.1670.0410.0380.542 + j0.4440.167 + j0.0372336
    3/017.430200.1050.1330.0380.0370.508 + j0.4220.133 + j0.0352478234260
    4/018.238080.0840.1050.0340.0360.479 + j0.3980.105 + j0.0342639268294
    25019.045000.0710.0900.0330.0350.461 + j0.3760.09 + j0.0332806296323
    35020.463000.0500.0650.0280.0330.431 + j0.340.065 + j0.0323101363386
    50023.190000.0350.0460.0240.0320.402 + j0.3010.046 + j0.033473447465
    75025.4135000.0240.0330.0210.0300.372 + j0.2520.033 + j0.0294040566563
    100027.7180000.0180.0260.0180.0290.349 + j0.220.027 + j0.0284511661638
    * Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17E or D17G of the 2021 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmAWGmmmmmmkg/km
    673689286.8114.883.5616.41849.501.5252.552569
    6527781197.5715.673.5617.20652.731.5255.782954
    6720791/0108.5316.613.5618.14654.761.5257.813231
    6742492/0129.5517.633.5619.15653.801.5256.853409
    TBA3/01910.7218.803.5620.32659.611.9163.423960
    6720704/01912.0420.143.5621.67662.381.9166.194310
    TBA2503713.2121.493.5623.01465.431.9169.244783
    6527873503715.6223.933.5625.45470.561.9174.375581
    6742575003418.6727.533.5629.06379.602.1683.927064
    TBA7506123.0631.603.5633.12288.012.1692.338997
    TBA10006126.9235.463.5636.98296.372.16100.6910812
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2365.7653130.87601.100.01620.14110.707 + j0.5030.336 + j0.0422001135157
    1388.6267020.69230.870.01490.13450.639 + j0.4850.266 + j0.042094154178
    1/0403.8684550.55120.690.01370.13120.585 + j0.4640.211 + j0.0382212176202
    2/0396.2471070.43640.550.01250.12470.542 + j0.4440.167 + j0.0372336
    3/0441.96134390.34450.440.01160.12140.508 + j0.4220.133 + j0.0352478234260
    4/0462.28169460.27560.340.01040.11810.479 + j0.3980.105 + j0.0342639268294
    250482.60200250.23290.300.01010.11480.461 + j0.3760.09 + j0.0332806296323
    350518.16280350.16400.210.00850.10830.431 + j0.340.065 + j0.0323101363386
    500586.74400500.11480.150.00730.10500.402 + j0.3010.046 + j0.033473447465
    750645.16600750.07870.110.00640.09840.372 + j0.2520.033 + j0.0294040566563
    1000703.58801000.05910.090.00550.09510.349 + j0.220.027 + j0.0284511661638
    * Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17E or D17G of the 2021 Canadian Electrical Code Part I

    Revision: 3.0.00C