SPEC 26252
HVTECK CU 3/C 140TRXLPE TS PVC AIA PVC 8kV 133% CSA
3 Conductor, 140 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Conductor Shield:Semi-conducting cross-linked copolymer
- Insulation:140 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 140 TRXLPE AIA 8kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Ground Size | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | AWG | mil | inch | inch | mil | inch | lb/1000ft | lb/1000ft | inch | |
| TBA | 2 | 7 | 0.283 | 0.601 | 140 | 0.661 | 1x6 | 6 | 80 | 1.614 | 1.924 | 60 | 2.044 | 868 | 1905 | 2.5 |
| 668932 | 2 | 7 | 0.283 | 0.601 | 140 | 0.661 | 1x6 | 6 | 80 | 1.614 | 1.982 | 60 | 2.102 | 897 | 2364 | 2.5 |
| TBA | 1 | 19 | 0.322 | 0.64 | 140 | 0.7 | 1x6 | 6 | 110 | 1.758 | 2.068 | 60 | 2.188 | 1039 | 2159 | 3 |
| TBA | 1/0 | 19 | 0.362 | 0.68 | 140 | 0.74 | 1x6 | 6 | 110 | 1.844 | 2.154 | 60 | 2.274 | 1255 | 2443 | 3 |
| TBA | 2/0 | 19 | 0.405 | 0.723 | 140 | 0.783 | 1x6 | 6 | 110 | 1.937 | 2.247 | 60 | 2.367 | 1523 | 2785 | 3 |
| TBA | 3/0 | 19 | 0.456 | 0.774 | 140 | 0.834 | 1x4 | 4 | 110 | 2.047 | 2.357 | 75 | 2.507 | 1908 | 3323 | 3 |
| TBA | 4/0 | 19 | 0.512 | 0.83 | 140 | 0.89 | 1x4 | 4 | 110 | 2.168 | 2.478 | 75 | 2.628 | 2331 | 3845 | 3.5 |
| 666021 | 4/0 | 19 | 0.512 | 0.83 | 140 | 0.89 | 1x4 | 4 | 110 | 2.168 | 2.536 | 75 | 2.686 | 2347 | 4441 | 3.5 |
| TBA | 250 | 37 | 0.558 | 0.884 | 140 | 0.944 | 1x4 | 4 | 110 | 2.285 | 2.595 | 75 | 2.745 | 2705 | 4328 | 3.5 |
| 664670 | 350 | 37 | 0.661 | 0.987 | 140 | 1.047 | 1x3 | 3 | 110 | 2.508 | 2.875 | 75 | 3.025 | 3712 | 6199 | 4 |
| TBA | 500 | 37 | 0.789 | 1.115 | 140 | 1.175 | 1x3 | 3 | 125 | 2.814 | 3.124 | 85 | 3.294 | 5135 | 7240 | 4.5 |
| 672305 | 500 | 37 | 0.789 | 1.092 | 140 | 1.152 | 1x3 | 3 | 125 | 2.764 | 3.13 | 85 | 3.3 | 5139 | 7782 | 4.5 |
| 675794 | 500 | 37 | 0.789 | 1.092 | 140 | 1.152 | 1x3 | 3 | 125 | 2.764 | 3.13 | 85 | 3.3 | 5139 | 7771 | 4.5 |
| TBA | 750 | 61 | 0.968 | 1.304 | 140 | 1.364 | 1x2 | 2 | 125 | 3.222 | 3.532 | 85 | 3.702 | 7563 | 10042 | 5 |
| TBA | 1000 | 61 | 1.117 | 1.453 | 140 | 1.513 | 1x1 | 1 | 125 | 3.544 | 3.854 | 85 | 4.024 | 9993 | 12750 | 5.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 14.3 | 1592 | 0.162 | 0.221 | 0.043 | 0.026 | 0.583+j0.533 | 0.221+j0.043 | 2079 | 172 | 201 |
| 2 | 14.7 | 1592 | 0.162 | 0.221 | 0.043 | 0.026 | 0.583+j0.533 | 0.221+j0.043 | 2079 | 172 | 201 |
| 1 | 15.3 | 2008 | 0.128 | 0.175 | 0.039 | 0.024 | 0.540+j0.512 | 0.175+j0.040 | 2200 | 197 | 228 |
| 1/0 | 15.9 | 2534 | 0.102 | 0.139 | 0.036 | 0.023 | 0.507+j0.492 | 0.139+j0.039 | 2324 | 225 | 257 |
| 2/0 | 16.6 | 3194 | 0.082 | 0.112 | 0.033 | 0.021 | 0.481+j0.471 | 0.112+j0.038 | 2457 | 260 | 292 |
| 3/0 | 17.5 | 4027 | 0.064 | 0.087 | 0.031 | 0.02 | 0.458+j0.448 | 0.087+j0.036 | 2615 | 297 | 330 |
| 4/0 | 18.4 | 5078 | 0.051 | 0.07 | 0.028 | 0.019 | 0.441+j0.425 | 0.070+j0.035 | 2789 | 342 | 372 |
| 4/0 | 18.8 | 5078 | 0.051 | 0.07 | 0.028 | 0.019 | 0.441+j0.425 | 0.070+j0.035 | 2789 | 342 | 372 |
| 250 | 19.2 | 6000 | 0.043 | 0.059 | 0.026 | 0.018 | 0.429+j0.404 | 0.059+j0.034 | 2956 | 376 | 410 |
| 350 | 21.2 | 8400 | 0.031 | 0.043 | 0.023 | 0.017 | 0.409+j0.367 | 0.043+j0.033 | 3275 | 460 | 487 |
| 500 | 23.1 | 12000 | 0.021 | 0.03 | 0.02 | 0.015 | 0.389+j0.327 | 0.030+j0.031 | 3672 | 556 | 573 |
| 500 | 23.1 | 12000 | 0.021 | 0.03 | 0.018 | 0.015 | 0.391+j0.333 | 0.030+j0.031 | 3600 | 556 | 573 |
| 500 | 23.1 | 12000 | 0.021 | 0.03 | 0.018 | 0.015 | 0.391+j0.333 | 0.030+j0.031 | 3600 | 556 | 573 |
| 750 | 25.9 | 18000 | 0.014 | 0.021 | 0.016 | 0.014 | 0.366+j0.277 | 0.021+j0.030 | 4257 | 678 | 668 |
| 1000 | 28.2 | 24000 | 0.011 | 0.018 | 0.015 | 0.013 | 0.351+j0.246 | 0.018+j0.029 | 4719 | 798 | 772 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground | Ground Size | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | AWG | mm | mm | mm | mm | mm | kg/km | kg/km | inch | |
| TBA | 2 | 7 | 7.19 | 15.27 | 3.56 | 16.79 | 1x6 | 6 | 2.03 | 41.00 | 48.87 | 1.52 | 51.92 | 1292 | 2835 | 2.5 |
| 668932 | 2 | 7 | 7.19 | 15.27 | 3.56 | 16.79 | 1x6 | 6 | 2.03 | 41.00 | 50.34 | 1.52 | 53.39 | 1335 | 3518 | 2.5 |
| TBA | 1 | 19 | 8.18 | 16.26 | 3.56 | 17.78 | 1x6 | 6 | 2.79 | 44.65 | 52.53 | 1.52 | 55.58 | 1546 | 3213 | 3 |
| TBA | 1/0 | 19 | 9.19 | 17.27 | 3.56 | 18.80 | 1x6 | 6 | 2.79 | 46.84 | 54.71 | 1.52 | 57.76 | 1868 | 3636 | 3 |
| TBA | 2/0 | 19 | 10.29 | 18.36 | 3.56 | 19.89 | 1x6 | 6 | 2.79 | 49.20 | 57.07 | 1.52 | 60.12 | 2266 | 4145 | 3 |
| TBA | 3/0 | 19 | 11.58 | 19.66 | 3.56 | 21.18 | 1x4 | 4 | 2.79 | 51.99 | 59.87 | 1.91 | 63.68 | 2839 | 4945 | 3 |
| TBA | 4/0 | 19 | 13.00 | 21.08 | 3.56 | 22.61 | 1x4 | 4 | 2.79 | 55.07 | 62.94 | 1.91 | 66.75 | 3469 | 5722 | 3.5 |
| 666021 | 4/0 | 19 | 13.00 | 21.08 | 3.56 | 22.61 | 1x4 | 4 | 2.79 | 55.07 | 64.41 | 1.91 | 68.22 | 3493 | 6609 | 3.5 |
| TBA | 250 | 37 | 14.17 | 22.45 | 3.56 | 23.98 | 1x4 | 4 | 2.79 | 58.04 | 65.91 | 1.91 | 69.72 | 4025 | 6441 | 3.5 |
| 664670 | 350 | 37 | 16.79 | 25.07 | 3.56 | 26.59 | 1x3 | 3 | 2.79 | 63.70 | 73.02 | 1.91 | 76.84 | 5524 | 9225 | 4 |
| TBA | 500 | 37 | 20.04 | 28.32 | 3.56 | 29.85 | 1x3 | 3 | 3.18 | 71.48 | 79.35 | 2.16 | 83.67 | 7642 | 10774 | 4.5 |
| 672305 | 500 | 37 | 20.04 | 27.74 | 3.56 | 29.26 | 1x3 | 3 | 3.18 | 70.21 | 79.50 | 2.16 | 83.82 | 7648 | 11581 | 4.5 |
| 675794 | 500 | 37 | 20.04 | 27.74 | 3.56 | 29.26 | 1x3 | 3 | 3.18 | 70.21 | 79.50 | 2.16 | 83.82 | 7648 | 11565 | 4.5 |
| TBA | 750 | 61 | 24.59 | 33.12 | 3.56 | 34.65 | 1x2 | 2 | 3.18 | 81.84 | 89.71 | 2.16 | 94.03 | 11255 | 14944 | 5 |
| TBA | 1000 | 61 | 28.37 | 36.91 | 3.56 | 38.43 | 1x1 | 1 | 3.18 | 90.02 | 97.89 | 2.16 | 102.21 | 14871 | 18974 | 5.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 363.22 | 7084 | 0.5315 | 0.73 | 0.0131 | 0.0853 | 0.583+j0.533 | 0.221+j0.043 | 2079 | 172 | 201 |
| 2 | 373.38 | 7084 | 0.5315 | 0.73 | 0.0131 | 0.0853 | 0.583+j0.533 | 0.221+j0.043 | 2079 | 172 | 201 |
| 1 | 388.62 | 8936 | 0.4199 | 0.57 | 0.0119 | 0.0787 | 0.540+j0.512 | 0.175+j0.040 | 2200 | 197 | 228 |
| 1/0 | 403.86 | 11276 | 0.3346 | 0.46 | 0.0110 | 0.0755 | 0.507+j0.492 | 0.139+j0.039 | 2324 | 225 | 257 |
| 2/0 | 421.64 | 14213 | 0.2690 | 0.37 | 0.0101 | 0.0689 | 0.481+j0.471 | 0.112+j0.038 | 2457 | 260 | 292 |
| 3/0 | 444.50 | 17920 | 0.2100 | 0.29 | 0.0094 | 0.0656 | 0.458+j0.448 | 0.087+j0.036 | 2615 | 297 | 330 |
| 4/0 | 467.36 | 22597 | 0.1673 | 0.23 | 0.0085 | 0.0623 | 0.441+j0.425 | 0.070+j0.035 | 2789 | 342 | 372 |
| 4/0 | 477.52 | 22597 | 0.1673 | 0.23 | 0.0085 | 0.0623 | 0.441+j0.425 | 0.070+j0.035 | 2789 | 342 | 372 |
| 250 | 487.68 | 26700 | 0.1411 | 0.19 | 0.0079 | 0.0591 | 0.429+j0.404 | 0.059+j0.034 | 2956 | 376 | 410 |
| 350 | 538.48 | 37380 | 0.1017 | 0.14 | 0.0070 | 0.0558 | 0.409+j0.367 | 0.043+j0.033 | 3275 | 460 | 487 |
| 500 | 586.74 | 53400 | 0.0689 | 0.10 | 0.0061 | 0.0492 | 0.389+j0.327 | 0.030+j0.031 | 3672 | 556 | 573 |
| 500 | 586.74 | 53400 | 0.0689 | 0.10 | 0.0055 | 0.0492 | 0.391+j0.333 | 0.030+j0.031 | 3600 | 556 | 573 |
| 500 | 586.74 | 53400 | 0.0689 | 0.10 | 0.0055 | 0.0492 | 0.391+j0.333 | 0.030+j0.031 | 3600 | 556 | 573 |
| 750 | 657.86 | 80100 | 0.0459 | 0.07 | 0.0049 | 0.0459 | 0.366+j0.277 | 0.021+j0.030 | 4257 | 678 | 668 |
| 1000 | 716.28 | 106800 | 0.0361 | 0.06 | 0.0046 | 0.0427 | 0.351+j0.246 | 0.018+j0.029 | 4719 | 798 | 772 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E