SPEC 26252

HVTECK CU 3/C 140TRXLPE TS PVC AIA PVC 8kV 133% CSA

3 Conductor, 140 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:140 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CU 140 TRXLPE AIA 8kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchAWGmilinchmilinchlb/1000ft
    270.2820.6001400.6606801.984602.1042222
    1190.3220.6401400.70061102.131602.2512613
    1/0190.3610.6791400.73961102.215602.3352923
    2/0190.4050.7231400.78361102.310752.4603377
    3/0190.4560.7741400.83441102.420752.5703850
    4/0190.5120.8301400.89041102.541752.6914421
    250370.5580.8841400.94441102.658752.8084951
    350370.6610.9871401.04731102.880753.0306196
    500370.7891.1151401.17531253.187853.3578148
    750610.9681.3041401.36421253.595853.76511119
    1000611.1171.4531401.51311253.917854.08713954
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    214.715920.1620.2040.0510.0420.576 + j0.4960.204 + j0.0432044172201
    115.720080.1280.1620.0460.0400.536 + j0.4740.162 + j0.042168197228
    1/016.325340.1020.1280.0420.0390.503 + j0.4530.128 + j0.0392289225257
    2/017.231940.0810.1020.0390.0370.477 + j0.4310.102 + j0.0382425260292
    3/017.940270.0640.0810.0360.0360.455 + j0.4080.081 + j0.0362584297330
    4/018.850780.0510.0650.0320.0350.437 + j0.3840.065 + j0.0352757342372
    25019.660000.0430.0560.0310.0340.425 + j0.3630.056 + j0.0342924376410
    35021.284000.0310.0410.0270.0330.403 + j0.3260.041 + j0.0333243460487
    50023.4120000.0220.0300.0230.0310.381 + j0.2870.03 + j0.0313640556573
    75026.3180000.0140.0230.0200.0300.356 + j0.240.023 + j0.034226678668
    100028.6240000.0110.0190.0170.0290.337 + j0.210.02 + j0.0294687798772
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmAWGmmmmmmmmkg/km
    277.1615.243.5616.7662.0350.391.5253.443307
    1198.1816.263.5617.7862.7954.131.5257.183889
    1/0199.1717.253.5618.7762.7956.261.5259.314350
    2/01910.2918.363.5619.8962.7958.671.9162.485026
    3/01911.5819.663.5621.1842.7961.471.9165.285729
    4/01913.0021.083.5622.6142.7964.541.9168.356579
    2503714.1722.453.5623.9842.7967.511.9171.327368
    3503716.7925.073.5626.5932.7973.151.9176.969221
    5003720.0428.323.5629.8533.1880.952.1685.2712126
    7506124.5933.123.5634.6523.1891.312.1695.6316547
    10006128.3736.913.5638.4313.1899.492.16103.8120766
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ/kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2373.3870840.53150.670.01550.13780.576 + j0.4960.204 + j0.0432044172201
    1398.7889360.41990.530.01400.13120.536 + j0.4740.162 + j0.042168197228
    1/0414.02112760.33460.420.01280.12800.503 + j0.4530.128 + j0.0392289225257
    2/0436.88142130.26570.330.01190.12140.477 + j0.4310.102 + j0.0382425260292
    3/0454.66179200.21000.270.01100.11810.455 + j0.4080.081 + j0.0362584297330
    4/0477.52225970.16730.210.00980.11480.437 + j0.3840.065 + j0.0352757342372
    250497.84267000.14110.180.00940.11150.425 + j0.3630.056 + j0.0342924376410
    350538.48373800.10170.130.00820.10830.403 + j0.3260.041 + j0.0333243460487
    500594.36534000.07220.100.00700.10170.381 + j0.2870.03 + j0.0313640556573
    750668.02801000.04590.080.00610.09840.356 + j0.240.023 + j0.034226678668
    1000726.441068000.03610.060.00520.09510.337 + j0.210.02 + j0.0294687798772
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:39 p.m. UTC