SPEC 26216

HVTECK CU 1/C 140TRXLPE CB PVC AIA PVC 8kV 133% CSA

Single Conductor, 140 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:140 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 140 TRXLPE AIA 8kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ft
    270.2820.6001400.6607 x 14801.176501.276859
    1190.3220.6401400.70011 x 14801.326501.4261007
    1/0190.3610.6791400.73911 x 14801.365501.4651102
    2/0190.4050.7231400.78311 x 14801.409501.5091219
    3/0190.4560.7741400.83413 x 14801.460501.5601391
    4/0190.5120.8301400.89013 x 14801.516601.6361600
    250370.5580.8841400.94417 x 14801.570601.6901816
    350370.6610.9871401.04721 x 14801.697601.8172291
    500370.7891.1151401.17526 x 14801.825601.9452921
    750610.9681.3041401.36421 x 121102.108602.2284171
    1000611.1171.4531401.51321 x 121102.257752.4075147
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    28.95300.1620.2040.0510.0560.186 + j0.0310.192 + j0.0395458215221
    19.96690.1280.1620.0460.0560.144 + j0.0280.149 + j0.0368577245247
    1/010.28440.1020.1280.0420.0540.11 + j0.0270.115 + j0.0358577278275
    2/010.510640.0810.1020.0390.0520.084 + j0.0250.089 + j0.0338577317306
    3/010.913420.0640.0810.0360.0500.063 + j0.0240.069 + j0.03210137357335
    4/011.416920.0510.0650.0320.0480.047 + j0.0220.053 + j0.0310137404369
    25011.820000.0430.0560.0310.0470.038 + j0.0210.044 + j0.02913256456412
    35012.728000.0310.0410.0270.0450.023 + j0.020.029 + j0.02816376537456
    50013.640000.0220.0300.0230.0420.012 + j0.0180.018 + j0.02620275616497
    75015.560000.0140.0230.0200.0410.005 + j0.0170.011 + j0.02526018706551
    100016.880000.0110.0190.0170.0390.001 + j0.0160.007 + j0.02426018813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    277.1615.243.5616.767 x 142.0329.871.2732.411278
    1198.1816.263.5617.7811 x 142.0333.681.2736.221499
    1/0199.1717.253.5618.7711 x 142.0334.671.2737.211640
    2/01910.2918.363.5619.8911 x 142.0335.791.2738.331814
    3/01911.5819.663.5621.1813 x 142.0337.081.2739.622070
    4/01913.0021.083.5622.6113 x 142.0338.511.5241.552381
    2503714.1722.453.5623.9817 x 142.0339.881.5242.932703
    3503716.7925.073.5626.5921 x 142.0343.101.5246.153409
    5003720.0428.323.5629.8526 x 142.0346.361.5249.404347
    7506124.5933.123.5634.6521 x 122.7953.541.5256.596207
    10006128.3736.913.5638.4321 x 122.7957.331.9161.147660
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ/kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2226.0623590.53150.670.01550.18370.186 + j0.0310.192 + j0.0395458215221
    1251.4629770.41990.530.01400.18370.144 + j0.0280.149 + j0.0368577245247
    1/0259.0837560.33460.420.01280.17720.11 + j0.0270.115 + j0.0358577278275
    2/0266.7047350.26570.330.01190.17060.084 + j0.0250.089 + j0.0338577317306
    3/0276.8659720.21000.270.01100.16400.063 + j0.0240.069 + j0.03210137357335
    4/0289.5675290.16730.210.00980.15750.047 + j0.0220.053 + j0.0310137404369
    250299.7289000.14110.180.00940.15420.038 + j0.0210.044 + j0.02913256456412
    350322.58124600.10170.130.00820.14760.023 + j0.020.029 + j0.02816376537456
    500345.44178000.07220.100.00700.13780.012 + j0.0180.018 + j0.02620275616497
    750393.70267000.04590.080.00610.13450.005 + j0.0170.011 + j0.02526018706551
    1000426.72356000.03610.060.00520.12800.001 + j0.0160.007 + j0.02426018813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:39 p.m. UTC