SPEC 26171
HVTECK AL 3/C 90TRXLPE TS PVC AIA PVC 5kV 100% CSA
3 Conductor, 90 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:90 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 90 TRXLPE AIA 5kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | inch | mil | inch | lb/1000ft | |
TBA | 2 | 7 | 0.268 | 0.486 | 90 | 0.546 | 8 | 1.738 | 60 | 1.858 | 1357 |
TBA | 1 | 19 | 0.298 | 0.516 | 90 | 0.576 | 6 | 1.803 | 60 | 1.923 | 1473 |
TBA | 1/0 | 19 | 0.336 | 0.554 | 90 | 0.614 | 6 | 1.885 | 60 | 2.005 | 1711 |
TBA | 2/0 | 19 | 0.376 | 0.594 | 90 | 0.654 | 6 | 1.971 | 60 | 2.091 | 1884 |
TBA | 3/0 | 19 | 0.422 | 0.640 | 90 | 0.700 | 6 | 2.131 | 60 | 2.251 | 2217 |
TBA | 4/0 | 19 | 0.474 | 0.692 | 90 | 0.752 | 6 | 2.243 | 60 | 2.363 | 2472 |
TBA | 250 | 37 | 0.520 | 0.746 | 90 | 0.806 | 4 | 2.360 | 75 | 2.510 | 2804 |
TBA | 350 | 37 | 0.615 | 0.841 | 90 | 0.901 | 4 | 2.565 | 75 | 2.715 | 3342 |
TBA | 500 | 37 | 0.735 | 0.961 | 90 | 1.021 | 3 | 2.824 | 75 | 2.974 | 4100 |
TBA | 750 | 61 | 0.908 | 1.144 | 90 | 1.204 | 2 | 3.249 | 85 | 3.419 | 5510 |
TBA | 1000 | 61 | 1.060 | 1.296 | 90 | 1.356 | 2 | 3.578 | 85 | 3.748 | 6683 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C† | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 13.0 | 1194 | 0.267 | 0.336 | 0.040 | 0.039 | 0.697 + j0.556 | 0.336 + j0.039 | 1691 | 135 | 157 |
1 | 13.4 | 1506 | 0.211 | 0.266 | 0.037 | 0.038 | 0.631 + j0.536 | 0.266 + j0.036 | 1784 | 154 | 178 |
1/0 | 14.0 | 1900 | 0.168 | 0.211 | 0.034 | 0.036 | 0.58 + j0.513 | 0.211 + j0.035 | 1902 | 176 | 202 |
2/0 | 14.6 | 2395 | 0.133 | 0.167 | 0.031 | 0.035 | 0.539 + j0.49 | 0.167 + j0.034 | 2026 | 204 | 229 |
3/0 | 15.7 | 3020 | 0.105 | 0.133 | 0.028 | 0.034 | 0.507 + j0.466 | 0.133 + j0.032 | 2168 | 234 | 260 |
4/0 | 16.5 | 3808 | 0.084 | 0.105 | 0.025 | 0.033 | 0.48 + j0.439 | 0.105 + j0.031 | 2329 | 268 | 294 |
250 | 17.5 | 4500 | 0.071 | 0.090 | 0.024 | 0.032 | 0.465 + j0.414 | 0.09 + j0.031 | 2497 | 296 | 323 |
350 | 19.0 | 6300 | 0.050 | 0.065 | 0.021 | 0.031 | 0.437 + j0.374 | 0.065 + j0.029 | 2791 | 363 | 386 |
500 | 20.8 | 9000 | 0.035 | 0.046 | 0.018 | 0.030 | 0.41 + j0.33 | 0.046 + j0.028 | 3163 | 447 | 465 |
750 | 23.9 | 13500 | 0.024 | 0.033 | 0.015 | 0.029 | 0.381 + j0.275 | 0.033 + j0.027 | 3730 | 566 | 563 |
1000 | 26.2 | 18000 | 0.018 | 0.026 | 0.013 | 0.028 | 0.359 + j0.238 | 0.026 + j0.026 | 4201 | 661 | 638 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | kg/km | |
TBA | 2 | 7 | 6.81 | 12.34 | 2.29 | 13.87 | 8 | 44.15 | 1.52 | 47.19 | 2019 |
TBA | 1 | 19 | 7.57 | 13.11 | 2.29 | 14.63 | 6 | 45.80 | 1.52 | 48.84 | 2192 |
TBA | 1/0 | 19 | 8.53 | 14.07 | 2.29 | 15.60 | 6 | 47.88 | 1.52 | 50.93 | 2546 |
TBA | 2/0 | 19 | 9.55 | 15.09 | 2.29 | 16.61 | 6 | 50.06 | 1.52 | 53.11 | 2804 |
TBA | 3/0 | 19 | 10.72 | 16.26 | 2.29 | 17.78 | 6 | 54.13 | 1.52 | 57.18 | 3299 |
TBA | 4/0 | 19 | 12.04 | 17.58 | 2.29 | 19.10 | 6 | 56.97 | 1.52 | 60.02 | 3679 |
TBA | 250 | 37 | 13.21 | 18.95 | 2.29 | 20.47 | 4 | 59.94 | 1.91 | 63.75 | 4173 |
TBA | 350 | 37 | 15.62 | 21.36 | 2.29 | 22.89 | 4 | 65.15 | 1.91 | 68.96 | 4973 |
TBA | 500 | 37 | 18.67 | 24.41 | 2.29 | 25.93 | 3 | 71.73 | 1.91 | 75.54 | 6101 |
TBA | 750 | 61 | 23.06 | 29.06 | 2.29 | 30.58 | 2 | 82.52 | 2.16 | 86.84 | 8200 |
TBA | 1000 | 61 | 26.92 | 32.92 | 2.29 | 34.44 | 2 | 90.88 | 2.16 | 95.20 | 9945 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C† | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 330.20 | 5313 | 0.8760 | 1.10 | 0.0122 | 0.1280 | 0.697 + j0.556 | 0.336 + j0.039 | 1691 | 135 | 157 |
1 | 340.36 | 6702 | 0.6923 | 0.87 | 0.0113 | 0.1247 | 0.631 + j0.536 | 0.266 + j0.036 | 1784 | 154 | 178 |
1/0 | 355.60 | 8455 | 0.5512 | 0.69 | 0.0104 | 0.1181 | 0.58 + j0.513 | 0.211 + j0.035 | 1902 | 176 | 202 |
2/0 | 370.84 | 10658 | 0.4364 | 0.55 | 0.0094 | 0.1148 | 0.539 + j0.49 | 0.167 + j0.034 | 2026 | 204 | 229 |
3/0 | 398.78 | 13439 | 0.3445 | 0.44 | 0.0085 | 0.1115 | 0.507 + j0.466 | 0.133 + j0.032 | 2168 | 234 | 260 |
4/0 | 419.10 | 16946 | 0.2756 | 0.34 | 0.0076 | 0.1083 | 0.48 + j0.439 | 0.105 + j0.031 | 2329 | 268 | 294 |
250 | 444.50 | 20025 | 0.2329 | 0.30 | 0.0073 | 0.1050 | 0.465 + j0.414 | 0.09 + j0.031 | 2497 | 296 | 323 |
350 | 482.60 | 28035 | 0.1640 | 0.21 | 0.0064 | 0.1017 | 0.437 + j0.374 | 0.065 + j0.029 | 2791 | 363 | 386 |
500 | 528.32 | 40050 | 0.1148 | 0.15 | 0.0055 | 0.0984 | 0.41 + j0.33 | 0.046 + j0.028 | 3163 | 447 | 465 |
750 | 607.06 | 60075 | 0.0787 | 0.11 | 0.0046 | 0.0951 | 0.381 + j0.275 | 0.033 + j0.027 | 3730 | 566 | 563 |
1000 | 665.48 | 80100 | 0.0591 | 0.09 | 0.0040 | 0.0919 | 0.359 + j0.238 | 0.026 + j0.026 | 4201 | 661 | 638 |
* Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C