SPEC 26171
HVTECK AL 3/C 90TRXLPE TS PVC AIA PVC 5kV 100% CSA
3 Conductor, 90 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket.

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:90 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Filler:Interstices filled with non-hydroscoping/non-wicking fillers
- Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
- Binder:Polypropylene tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 3/C [#AWG or #kcmil] CPT AL 90 TRXLPE AIA 5kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | AWG | mil | inch | mil | inch | lb/1000ft |
2 | 7 | 0.268 | 0.486 | 90 | 0.546 | 8 | 80 | 1.739 | 60 | 1.859 | 1271 |
1 | 19 | 0.298 | 0.516 | 90 | 0.576 | 6 | 80 | 1.803 | 60 | 1.923 | 1389 |
1/0 | 19 | 0.336 | 0.554 | 90 | 0.614 | 6 | 80 | 1.885 | 60 | 2.005 | 1622 |
2/0 | 19 | 0.376 | 0.594 | 90 | 0.654 | 6 | 80 | 1.972 | 60 | 2.092 | 1788 |
3/0 | 19 | 0.422 | 0.640 | 90 | 0.700 | 6 | 110 | 2.131 | 60 | 2.251 | 2110 |
4/0 | 19 | 0.474 | 0.692 | 90 | 0.752 | 6 | 110 | 2.244 | 60 | 2.364 | 2358 |
250 | 37 | 0.520 | 0.746 | 90 | 0.806 | 4 | 110 | 2.360 | 75 | 2.510 | 2693 |
350 | 37 | 0.615 | 0.841 | 90 | 0.901 | 4 | 110 | 2.565 | 75 | 2.715 | 3213 |
500 | 37 | 0.735 | 0.961 | 90 | 1.021 | 3 | 110 | 2.825 | 75 | 2.975 | 3962 |
750 | 61 | 0.908 | 1.144 | 90 | 1.204 | 2 | 125 | 3.250 | 85 | 3.420 | 5352 |
1000 | 61 | 1.060 | 1.296 | 90 | 1.356 | 2 | 125 | 3.578 | 85 | 3.748 | 6493 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
2 | 13.0 | 1194 | 0.267 | 0.336 | 0.035 | 0.039 | 0.699 + j0.550 | 0.336 + j0.039 | 1722 | 135 | 157 |
1 | 13.5 | 1506 | 0.211 | 0.266 | 0.030 | 0.038 | 0.633 + j0.530 | 0.266 + j0.036 | 1815 | 154 | 178 |
1/0 | 14.0 | 1900 | 0.168 | 0.211 | 0.030 | 0.036 | 0.581 + j0.508 | 0.211 + j0.035 | 1933 | 176 | 202 |
2/0 | 14.6 | 2395 | 0.133 | 0.167 | 0.030 | 0.035 | 0.540 + j0.485 | 0.167 + j0.034 | 2057 | 204 | 229 |
3/0 | 15.8 | 3020 | 0.105 | 0.133 | 0.030 | 0.030 | 0.508 + j0.461 | 0.133 + j0.032 | 2199 | 234 | 260 |
4/0 | 16.5 | 3808 | 0.084 | 0.105 | 0.020 | 0.030 | 0.481 + j0.435 | 0.105 + j0.031 | 2360 | 268 | 294 |
250 | 17.6 | 4500 | 0.071 | 0.090 | 0.020 | 0.030 | 0.465 + j0.410 | 0.090 + j0.031 | 2528 | 296 | 323 |
350 | 19.0 | 6300 | 0.050 | 0.065 | 0.020 | 0.030 | 0.436 + j0.370 | 0.065 + j0.029 | 2822 | 363 | 386 |
500 | 20.8 | 9000 | 0.035 | 0.046 | 0.020 | 0.030 | 0.410 + j0.326 | 0.046 + j0.028 | 3194 | 447 | 465 |
750 | 23.9 | 13500 | 0.020 | 0.030 | 0.013 | 0.030 | 0.381 + j0.272 | 0.033 + j0.027 | 3761 | 566 | 563 |
1000 | 26.2 | 18000 | 0.020 | 0.030 | 0.011 | 0.030 | 0.359 + j0.236 | 0.026 + j0.026 | 4232 | 661 | 638 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Table 3 – Weights and Measurements (Metric)
Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Ground Size | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | AWG | mm | mm | mm | mm | kg/km |
2 | 7 | 6.81 | 12.34 | 2.29 | 13.87 | 8 | 2.03 | 44.17 | 1.52 | 47.22 | 1891 |
1 | 19 | 7.57 | 13.11 | 2.29 | 14.63 | 6 | 2.03 | 45.80 | 1.52 | 48.84 | 2067 |
1/0 | 19 | 8.53 | 14.07 | 2.29 | 15.60 | 6 | 2.03 | 47.88 | 1.52 | 50.93 | 2414 |
2/0 | 19 | 9.55 | 15.09 | 2.29 | 16.61 | 6 | 2.03 | 50.09 | 1.52 | 53.14 | 2661 |
3/0 | 19 | 10.72 | 16.26 | 2.29 | 17.78 | 6 | 2.79 | 54.13 | 1.52 | 57.18 | 3140 |
4/0 | 19 | 12.04 | 17.58 | 2.29 | 19.10 | 6 | 2.79 | 57.00 | 1.52 | 60.05 | 3509 |
250 | 37 | 13.21 | 18.95 | 2.29 | 20.47 | 4 | 2.79 | 59.94 | 1.91 | 63.75 | 4008 |
350 | 37 | 15.62 | 21.36 | 2.29 | 22.89 | 4 | 2.79 | 65.15 | 1.91 | 68.96 | 4781 |
500 | 37 | 18.67 | 24.41 | 2.29 | 25.93 | 3 | 2.79 | 71.76 | 1.91 | 75.57 | 5896 |
750 | 61 | 23.06 | 29.06 | 2.29 | 30.58 | 2 | 3.18 | 82.55 | 2.16 | 86.87 | 7965 |
1000 | 61 | 26.92 | 32.92 | 2.29 | 34.44 | 2 | 3.18 | 90.88 | 2.16 | 95.20 | 9663 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
2 | 330.20 | 5313 | 0.8760 | 1.10 | 0.0107 | 0.1280 | 0.699 + j0.550 | 0.336 + j0.039 | 1722 | 135 | 157 |
1 | 342.90 | 6702 | 0.6923 | 0.87 | 0.0091 | 0.1247 | 0.633 + j0.530 | 0.266 + j0.036 | 1815 | 154 | 178 |
1/0 | 355.60 | 8455 | 0.5512 | 0.69 | 0.0091 | 0.1181 | 0.581 + j0.508 | 0.211 + j0.035 | 1933 | 176 | 202 |
2/0 | 370.84 | 10658 | 0.4364 | 0.55 | 0.0091 | 0.1148 | 0.540 + j0.485 | 0.167 + j0.034 | 2057 | 204 | 229 |
3/0 | 401.32 | 13439 | 0.3445 | 0.44 | 0.0091 | 0.0984 | 0.508 + j0.461 | 0.133 + j0.032 | 2199 | 234 | 260 |
4/0 | 419.10 | 16946 | 0.2756 | 0.34 | 0.0061 | 0.0984 | 0.481 + j0.435 | 0.105 + j0.031 | 2360 | 268 | 294 |
250 | 447.04 | 20025 | 0.2329 | 0.30 | 0.0061 | 0.0984 | 0.465 + j0.410 | 0.090 + j0.031 | 2528 | 296 | 323 |
350 | 482.60 | 28035 | 0.1640 | 0.21 | 0.0061 | 0.0984 | 0.436 + j0.370 | 0.065 + j0.029 | 2822 | 363 | 386 |
500 | 528.32 | 40050 | 0.1148 | 0.15 | 0.0061 | 0.0984 | 0.410 + j0.326 | 0.046 + j0.028 | 3194 | 447 | 465 |
750 | 607.06 | 60075 | 0.0656 | 0.10 | 0.0040 | 0.0984 | 0.381 + j0.272 | 0.033 + j0.027 | 3761 | 566 | 563 |
1000 | 665.48 | 80100 | 0.0656 | 0.10 | 0.0034 | 0.0984 | 0.359 + j0.236 | 0.026 + j0.026 | 4232 | 661 | 638 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
* CEC ampacities are based on:
3/C in air copper and aluminum: D17N
3/C direct buried copper and aluminum: D17E
Revision: 1.000.003
Updated On: May 1, 2025, 7:39 p.m. UTC