SPEC 26152

HVTECK CU 3/C 115TRXLPE TS PVC AIA PVC 5kV 133% or 8kV 100% CSA

3 Conductor, 115 Mils Tree Retardant Cross Linked Polyethylene, 5kV 133% or 8kV 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:115 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Filler:Interstices filled with non-hydroscoping/non-wicking fillers
  7. Grounding Conductor:Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
  8. Binder:Polypropylene tape
  9. Inner Jacket:PVC inner jacket
  10. Armour:Aluminum Interlocked Armour (AIA)
  11. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 5kV / 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    {SQMTR} {CSA} SOUTHWIRE{R} POWER CABLE {NESC} MASTER-DESIGN 3/C XXX KCMIL CU X.XXmm (115 mils) TR-XLPE AIA GW 1 X X AWG CU 5KV 133%/8KV 100% INS LEVEL 25%TS SUN. RES. 105{D}C FT4 HL (-40{D}C) LTGG RoHS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchAWGinchmilinchlb/1000ft
    672897270.2820.5451150.60561.873601.9932232
    6719751190.3220.5901150.65061.957602.0772356
    6729051/0190.3610.6301150.69062.104602.2242896
    6729472/0190.4050.6741150.73462.199602.3193134
    TBA3/0190.4560.7241150.78442.312752.4623652
    5990014/0190.5120.7661150.82642.397752.5474219
    671984250370.5580.8181150.87842.510752.6604697
    640917350370.6610.9171150.97732.724752.8745967
    599006500370.7891.0421151.10232.994753.1447708
    674110^500370.7891.0421151.10232.994753.1447712
    671381750610.9681.2541151.31423.502853.67210935
    TBA1000611.1171.4031151.46313.809853.97913652
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ^ Stock Code: 674110. Yellow Jacket
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    213.915920.1620.2040.0450.0400.572 + j0.5220.204 + j0.0411889172201
    114.520080.1280.1620.0410.0390.534 + j0.4980.162 + j0.0392013197228
    1/015.525340.1020.1280.0370.0370.502 + j0.4760.128 + j0.0372134225257
    2/016.231940.0810.1020.0340.0360.477 + j0.4530.102 + j0.0362270260292
    3/017.240270.0640.0810.0310.0350.456 + j0.4280.081 + j0.0352429297330
    4/017.850780.0510.0650.0280.0340.439 + j0.4030.065 + j0.0342602342372
    25018.660000.0430.0560.0270.0330.428 + j0.380.056 + j0.0332769376410
    35020.184000.0310.0410.0230.0320.407 + j0.3410.041 + j0.0323088460487
    50022.0120000.0220.0300.0200.0300.386 + j0.30.03 + j0.033485556573
    50022.0120000.0220.0300.0200.0300.386 + j0.30.03 + j0.033485556573
    75025.7180000.0140.0230.0170.0290.361 + j0.250.023 + j0.0294071678668
    100027.8240000.0110.0190.0150.0280.342 + j0.2190.02 + j0.0284532798772
    * Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldGround SizeDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmAWGmmmmmmkg/km
    672897277.1613.842.9215.37647.571.5250.623322
    6719751198.1814.992.9216.51649.711.5252.763506
    6729051/0199.1716.002.9217.53653.441.5256.494310
    6729472/01910.2917.122.9218.64655.851.5258.904664
    TBA3/01911.5818.392.9219.91458.721.9162.535435
    5990014/01913.0019.462.9220.98460.881.9164.696279
    6719842503714.1720.782.9222.30463.751.9167.566990
    6409173503716.7923.292.9224.82369.191.9173.008880
    5990065003720.0426.472.9227.99376.051.9179.8611471
    674110^5003720.0426.472.9227.99376.051.9179.8611477
    6713817506124.5931.852.9233.38288.952.1693.2716273
    TBA10006128.3735.642.9237.16196.752.16101.0720316
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ^ Stock Code: 674110. Yellow Jacket
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2353.0670840.53150.670.01370.13120.572 + j0.5220.204 + j0.0411889172201
    1368.3089360.41990.530.01250.12800.534 + j0.4980.162 + j0.0392013197228
    1/0393.70112760.33460.420.01130.12140.502 + j0.4760.128 + j0.0372134225257
    2/0411.48142130.26570.330.01040.11810.477 + j0.4530.102 + j0.0362270260292
    3/0436.88179200.21000.270.00940.11480.456 + j0.4280.081 + j0.0352429297330
    4/0452.12225970.16730.210.00850.11150.439 + j0.4030.065 + j0.0342602342372
    250472.44267000.14110.180.00820.10830.428 + j0.380.056 + j0.0332769376410
    350510.54373800.10170.130.00700.10500.407 + j0.3410.041 + j0.0323088460487
    500558.80534000.07220.100.00610.09840.386 + j0.30.03 + j0.033485556573
    500558.80534000.07220.100.00610.09840.386 + j0.30.03 + j0.033485556573
    750652.78801000.04590.080.00520.09510.361 + j0.250.023 + j0.0294071678668
    1000706.121068000.03610.060.00460.09190.342 + j0.2190.02 + j0.0284532798772
    * Calculations are based on 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17N of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17E of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C