SPEC 26131
HVTECK AL 1/C 90TRXLPE TS PVC AIA PVC 5kV 100% CSA
Single Conductor, 90 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:90 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 90 TRXLPE AIA 5kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | inch | mil | inch | lb/1000ft | |
TBA | 2 | 7 | 0.268 | 0.486 | 90 | 0.546 | 0.918 | 50 | 1.018 | 489 |
TBA | 1 | 19 | 0.298 | 0.516 | 90 | 0.576 | 0.948 | 50 | 1.048 | 526 |
TBA | 1/0 | 19 | 0.336 | 0.554 | 90 | 0.614 | 0.986 | 50 | 1.086 | 574 |
TBA | 2/0 | 19 | 0.376 | 0.594 | 90 | 0.654 | 1.026 | 50 | 1.126 | 628 |
TBA | 3/0 | 19 | 0.422 | 0.640 | 90 | 0.700 | 1.102 | 50 | 1.202 | 725 |
TBA | 4/0 | 19 | 0.474 | 0.692 | 90 | 0.752 | 1.154 | 50 | 1.254 | 804 |
TBA | 250 | 37 | 0.520 | 0.746 | 90 | 0.806 | 1.208 | 50 | 1.308 | 883 |
TBA | 350 | 37 | 0.615 | 0.841 | 90 | 0.901 | 1.413 | 50 | 1.513 | 1057 |
TBA | 500 | 37 | 0.735 | 0.961 | 90 | 1.021 | 1.533 | 60 | 1.653 | 1319 |
TBA | 750 | 61 | 0.908 | 1.144 | 90 | 1.204 | 1.740 | 60 | 1.860 | 1734 |
TBA | 1000 | 61 | 1.060 | 1.296 | 90 | 1.356 | 1.892 | 60 | 2.012 | 2181 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C† | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 7.1 | 398 | 0.267 | 0.336 | 0.040 | 0.052 | 0.681 + j0.546 | 0.337 + j0.052 | 1691 | 169 | 176 |
1 | 7.3 | 502 | 0.211 | 0.266 | 0.037 | 0.051 | 0.615 + j0.527 | 0.267 + j0.049 | 1784 | 194 | 198 |
1/0 | 7.6 | 633 | 0.168 | 0.211 | 0.034 | 0.049 | 0.565 + j0.506 | 0.212 + j0.047 | 1902 | 222 | 223 |
2/0 | 7.8 | 798 | 0.133 | 0.167 | 0.031 | 0.047 | 0.525 + j0.485 | 0.168 + j0.045 | 2026 | 255 | 250 |
3/0 | 8.4 | 1006 | 0.105 | 0.133 | 0.028 | 0.046 | 0.494 + j0.461 | 0.134 + j0.044 | 2168 | 290 | 278 |
4/0 | 8.7 | 1269 | 0.084 | 0.105 | 0.025 | 0.044 | 0.468 + j0.436 | 0.106 + j0.042 | 2329 | 329 | 309 |
250 | 9.1 | 1500 | 0.071 | 0.090 | 0.024 | 0.043 | 0.454 + j0.412 | 0.091 + j0.041 | 2497 | 370 | 347 |
350 | 10.5 | 2100 | 0.050 | 0.065 | 0.021 | 0.042 | 0.425 + j0.372 | 0.066 + j0.041 | 2791 | 446 | 402 |
500 | 11.5 | 3000 | 0.035 | 0.046 | 0.018 | 0.040 | 0.401 + j0.329 | 0.047 + j0.039 | 3163 | 533 | 451 |
750 | 13.0 | 4500 | 0.024 | 0.033 | 0.015 | 0.038 | 0.374 + j0.275 | 0.034 + j0.037 | 3730 | 631 | 500 |
1000 | 14.0 | 6000 | 0.018 | 0.026 | 0.013 | 0.036 | 0.354 + j0.239 | 0.027 + j0.035 | 4201 | 707 | 539 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
Table 3 – Weights and Measurements (Metric)
Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Dia. Over Armour | Jacket Thickness1 | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | mm | mm | mm | kg/km | |
TBA | 2 | 7 | 6.81 | 12.34 | 2.29 | 13.87 | 23.32 | 1.27 | 25.86 | 728 |
TBA | 1 | 19 | 7.57 | 13.11 | 2.29 | 14.63 | 24.08 | 1.27 | 26.62 | 783 |
TBA | 1/0 | 19 | 8.53 | 14.07 | 2.29 | 15.60 | 25.04 | 1.27 | 27.58 | 854 |
TBA | 2/0 | 19 | 9.55 | 15.09 | 2.29 | 16.61 | 26.06 | 1.27 | 28.60 | 935 |
TBA | 3/0 | 19 | 10.72 | 16.26 | 2.29 | 17.78 | 27.99 | 1.27 | 30.53 | 1079 |
TBA | 4/0 | 19 | 12.04 | 17.58 | 2.29 | 19.10 | 29.31 | 1.27 | 31.85 | 1196 |
TBA | 250 | 37 | 13.21 | 18.95 | 2.29 | 20.47 | 30.68 | 1.27 | 33.22 | 1314 |
TBA | 350 | 37 | 15.62 | 21.36 | 2.29 | 22.89 | 35.89 | 1.27 | 38.43 | 1573 |
TBA | 500 | 37 | 18.67 | 24.41 | 2.29 | 25.93 | 38.94 | 1.52 | 41.99 | 1963 |
TBA | 750 | 61 | 23.06 | 29.06 | 2.29 | 30.58 | 44.20 | 1.52 | 47.24 | 2580 |
TBA | 1000 | 61 | 26.92 | 32.92 | 2.29 | 34.44 | 48.06 | 1.52 | 51.10 | 3246 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C† | Allowable Ampacity Directly Buried 90°C‡ |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 180.34 | 1771 | 0.8760 | 1.10 | 0.0122 | 0.1706 | 0.681 + j0.546 | 0.337 + j0.052 | 1691 | 169 | 176 |
1 | 185.42 | 2234 | 0.6923 | 0.87 | 0.0113 | 0.1673 | 0.615 + j0.527 | 0.267 + j0.049 | 1784 | 194 | 198 |
1/0 | 193.04 | 2817 | 0.5512 | 0.69 | 0.0104 | 0.1608 | 0.565 + j0.506 | 0.212 + j0.047 | 1902 | 222 | 223 |
2/0 | 198.12 | 3551 | 0.4364 | 0.55 | 0.0094 | 0.1542 | 0.525 + j0.485 | 0.168 + j0.045 | 2026 | 255 | 250 |
3/0 | 213.36 | 4477 | 0.3445 | 0.44 | 0.0085 | 0.1509 | 0.494 + j0.461 | 0.134 + j0.044 | 2168 | 290 | 278 |
4/0 | 220.98 | 5647 | 0.2756 | 0.34 | 0.0076 | 0.1444 | 0.468 + j0.436 | 0.106 + j0.042 | 2329 | 329 | 309 |
250 | 231.14 | 6675 | 0.2329 | 0.30 | 0.0073 | 0.1411 | 0.454 + j0.412 | 0.091 + j0.041 | 2497 | 370 | 347 |
350 | 266.70 | 9345 | 0.1640 | 0.21 | 0.0064 | 0.1378 | 0.425 + j0.372 | 0.066 + j0.041 | 2791 | 446 | 402 |
500 | 292.10 | 13350 | 0.1148 | 0.15 | 0.0055 | 0.1312 | 0.401 + j0.329 | 0.047 + j0.039 | 3163 | 533 | 451 |
750 | 330.20 | 20025 | 0.0787 | 0.11 | 0.0046 | 0.1247 | 0.374 + j0.275 | 0.034 + j0.037 | 3730 | 631 | 500 |
1000 | 355.60 | 26700 | 0.0591 | 0.09 | 0.0040 | 0.1181 | 0.354 + j0.239 | 0.027 + j0.035 | 4201 | 707 | 539 |
* Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
† Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
Revision: 3.0.00C