SPEC 26126
HVTECK AL 1/C 115NLEPR CB PVC AIA PVC 5kV 133% CSA
Single Conductor, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 115 NLEPR AIA 5kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | inch |
| 2 | 7 | 0.268 | 0.536 | 115 | 0.596 | 5x12 | 80 | 1.256 | 50 | 1.356 | 130 | 966 | 3.5 |
| 1 | 19 | 0.299 | 0.567 | 115 | 0.627 | 5x12 | 80 | 1.287 | 50 | 1.387 | 133 | 1014 | 3.5 |
| 1/0 | 19 | 0.336 | 0.604 | 115 | 0.664 | 5x12 | 80 | 1.324 | 50 | 1.424 | 136 | 1072 | 3.5 |
| 2/0 | 19 | 0.376 | 0.644 | 115 | 0.704 | 7x12 | 80 | 1.364 | 50 | 1.464 | 187 | 1188 | 4 |
| 3/0 | 19 | 0.423 | 0.691 | 115 | 0.751 | 7x12 | 80 | 1.411 | 50 | 1.511 | 191 | 1269 | 4 |
| 4/0 | 19 | 0.475 | 0.743 | 115 | 0.803 | 7x12 | 80 | 1.563 | 60 | 1.683 | 195 | 1536 | 4.5 |
| 250 | 37 | 0.52 | 0.796 | 115 | 0.856 | 9x12 | 80 | 1.616 | 60 | 1.736 | 238 | 1675 | 4.5 |
| 350 | 37 | 0.616 | 0.892 | 115 | 0.952 | 11x12 | 80 | 1.712 | 60 | 1.832 | 283 | 1918 | 5 |
| 500 | 37 | 0.736 | 1.012 | 115 | 1.072 | 13x12 | 80 | 1.832 | 60 | 1.952 | 347 | 2252 | 5 |
| 750 | 61 | 0.908 | 1.194 | 115 | 1.254 | 17x12 | 110 | 2.074 | 60 | 2.194 | 429 | 2887 | 6 |
| 1000 | 61 | 1.117 | 1.403 | 115 | 1.463 | 17x12 | 110 | 2.283 | 75 | 2.433 | 446 | 3440 | 6.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 9.5 | 398 | 0.266 | 0.365 | 0.029 | 0.059 | 0.666+j0.193 | 0.368+j0.064 | 2770 | 169 | 176 |
| 1 | 9.7 | 502 | 0.211 | 0.289 | 0.027 | 0.057 | 0.590+j0.190 | 0.292+j0.061 | 2770 | 194 | 198 |
| 1/0 | 10 | 633 | 0.167 | 0.229 | 0.025 | 0.055 | 0.529+j0.189 | 0.232+j0.059 | 2770 | 222 | 223 |
| 2/0 | 10.2 | 798 | 0.133 | 0.182 | 0.023 | 0.053 | 0.426+j0.119 | 0.186+j0.056 | 3879 | 255 | 250 |
| 3/0 | 10.6 | 1006 | 0.105 | 0.144 | 0.021 | 0.051 | 0.388+j0.118 | 0.148+j0.054 | 3879 | 290 | 278 |
| 4/0 | 11.8 | 1269 | 0.084 | 0.115 | 0.019 | 0.051 | 0.358+j0.118 | 0.119+j0.054 | 3879 | 329 | 309 |
| 250 | 12.2 | 1500 | 0.07 | 0.096 | 0.018 | 0.049 | 0.297+j0.082 | 0.101+j0.052 | 4987 | 370 | 347 |
| 350 | 12.8 | 2100 | 0.051 | 0.07 | 0.016 | 0.047 | 0.240+j0.061 | 0.076+j0.049 | 6095 | 446 | 402 |
| 500 | 13.7 | 3000 | 0.036 | 0.05 | 0.013 | 0.044 | 0.197+j0.048 | 0.057+j0.047 | 7203 | 533 | 451 |
| 750 | 15.4 | 4500 | 0.023 | 0.033 | 0.011 | 0.042 | 0.148+j0.033 | 0.041+j0.044 | 9420 | 631 | 500 |
| 1000 | 17 | 6000 | 0.017 | 0.025 | 0.009 | 0.04 | 0.140+j0.034 | 0.033+j0.043 | 9420 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Table 3 – Weights and Measurements (Metric)
| Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Conduit Size* |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km | kg/km | inch |
| 2 | 7 | 6.81 | 13.61 | 2.92 | 15.14 | 5x12 | 2.03 | 31.90 | 1.27 | 34.44 | 193 | 1438 | 3.5 |
| 1 | 19 | 7.59 | 14.40 | 2.92 | 15.93 | 5x12 | 2.03 | 32.69 | 1.27 | 35.23 | 198 | 1509 | 3.5 |
| 1/0 | 19 | 8.53 | 15.34 | 2.92 | 16.87 | 5x12 | 2.03 | 33.63 | 1.27 | 36.17 | 202 | 1595 | 3.5 |
| 2/0 | 19 | 9.55 | 16.36 | 2.92 | 17.88 | 7x12 | 2.03 | 34.65 | 1.27 | 37.19 | 278 | 1768 | 4 |
| 3/0 | 19 | 10.74 | 17.55 | 2.92 | 19.08 | 7x12 | 2.03 | 35.84 | 1.27 | 38.38 | 284 | 1888 | 4 |
| 4/0 | 19 | 12.07 | 18.87 | 2.92 | 20.40 | 7x12 | 2.03 | 39.70 | 1.52 | 42.75 | 290 | 2286 | 4.5 |
| 250 | 37 | 13.21 | 20.22 | 2.92 | 21.74 | 9x12 | 2.03 | 41.05 | 1.52 | 44.09 | 354 | 2493 | 4.5 |
| 350 | 37 | 15.65 | 22.66 | 2.92 | 24.18 | 11x12 | 2.03 | 43.48 | 1.52 | 46.53 | 421 | 2854 | 5 |
| 500 | 37 | 18.69 | 25.70 | 2.92 | 27.23 | 13x12 | 2.03 | 46.53 | 1.52 | 49.58 | 516 | 3351 | 5 |
| 750 | 61 | 23.06 | 30.33 | 2.92 | 31.85 | 17x12 | 2.79 | 52.68 | 1.52 | 55.73 | 638 | 4296 | 6 |
| 1000 | 61 | 28.37 | 35.64 | 2.92 | 37.16 | 17x12 | 2.79 | 57.99 | 1.91 | 61.80 | 664 | 5119 | 6.5 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance | Positive Sequence Impedance | Phase Short Circuit Current @ 6 Cycles | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp |
| 2 | 241.30 | 1771 | 0.8727 | 1.20 | 0.0088 | 0.1936 | 0.666+j0.193 | 0.368+j0.064 | 2770 | 169 | 176 |
| 1 | 246.38 | 2234 | 0.6923 | 0.95 | 0.0082 | 0.1870 | 0.590+j0.190 | 0.292+j0.061 | 2770 | 194 | 198 |
| 1/0 | 254.00 | 2817 | 0.5479 | 0.75 | 0.0076 | 0.1804 | 0.529+j0.189 | 0.232+j0.059 | 2770 | 222 | 223 |
| 2/0 | 259.08 | 3551 | 0.4364 | 0.60 | 0.0070 | 0.1739 | 0.426+j0.119 | 0.186+j0.056 | 3879 | 255 | 250 |
| 3/0 | 269.24 | 4477 | 0.3445 | 0.47 | 0.0064 | 0.1673 | 0.388+j0.118 | 0.148+j0.054 | 3879 | 290 | 278 |
| 4/0 | 299.72 | 5647 | 0.2756 | 0.38 | 0.0058 | 0.1673 | 0.358+j0.118 | 0.119+j0.054 | 3879 | 329 | 309 |
| 250 | 309.88 | 6675 | 0.2297 | 0.31 | 0.0055 | 0.1608 | 0.297+j0.082 | 0.101+j0.052 | 4987 | 370 | 347 |
| 350 | 325.12 | 9345 | 0.1673 | 0.23 | 0.0049 | 0.1542 | 0.240+j0.061 | 0.076+j0.049 | 6095 | 446 | 402 |
| 500 | 347.98 | 13350 | 0.1181 | 0.16 | 0.0040 | 0.1444 | 0.197+j0.048 | 0.057+j0.047 | 7203 | 533 | 451 |
| 750 | 391.16 | 20025 | 0.0755 | 0.11 | 0.0034 | 0.1378 | 0.148+j0.033 | 0.041+j0.044 | 9420 | 631 | 500 |
| 1000 | 431.80 | 26700 | 0.0558 | 0.08 | 0.0027 | 0.1312 | 0.140+j0.034 | 0.033+j0.043 | 9420 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
* CEC ampacities are based on:
3-1/C in air copper and aluminum: D17M
3-1/C direct buried copper and aluminum: D17A
Revision: 1.000.000
Updated On: Dec. 31, 2024, 11:07 p.m. UTC

