SPEC 26111

HVTECK CU 1/C 90TRXLPE TS PVC AIA PVC 5kV 100% CSA

Single Conductor, 90 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:90 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 90 TRXLPE AIA 5kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ftlb/1000ftinch
    TBA270.2830.501900.561650.921501.0212516672.5
    TBA1190.3220.54900.6650.96501.063087492.5
    TBA1/0190.3620.58900.64651501.13798453
    TBA2/0190.4050.623900.683801.073501.1734679923
    TBA3/0190.4560.674900.734801.124501.22457911373
    TBA4/0190.5120.73900.79801.18501.2871813143.5
    TBA250370.5580.784900.844801.234501.33484214773.5
    TBA350370.6610.887900.947801.337501.437115918633.5
    TBA500370.7891.015901.075801.565601.685163225954.5
    TBA750610.9681.204901.264801.754601.874242035385
    5996601000611.1171.353901.413801.937602.057320643195.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    27.15300.1620.2210.030.0510.548+j0.5650.222+j0.0581769215221
    17.46690.1280.1750.0280.0490.509+j0.5440.176+j0.0551890245247
    1/07.78440.1020.1390.0250.0470.478+j0.5250.140+j0.0532014278275
    2/08.210640.0820.1120.0230.0460.456+j0.5040.113+j0.0522147317306
    3/08.613420.0640.0870.0210.0440.435+j0.4810.088+j0.0502305357335
    4/0916920.0510.070.0190.0430.422+j0.4560.071+j0.0482479404369
    2509.320000.0430.0590.0180.0420.413+j0.4350.060+j0.0472646456412
    35010.128000.0310.0430.0150.040.398+j0.3960.044+j0.0452965537456
    50011.840000.0210.030.0130.0390.381+j0.3530.031+j0.0453362616497
    75013.160000.0140.0210.0110.0370.363+j0.3000.022+j0.0423947706551
    100014.480000.0110.0180.010.0360.349+j0.2650.020+j0.0414409813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. WeightConduit Size*
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/kmkg/kminch
    TBA277.1912.732.2914.251.6523.391.2725.933749932.5
    TBA1198.1813.722.2915.241.6524.381.2726.9245811152.5
    TBA1/0199.1914.732.2916.261.6525.401.2727.9456412573
    TBA2/01910.2915.822.2917.352.0327.251.2729.7969514763
    TBA3/01911.5817.122.2918.642.0328.551.2731.0986216923
    TBA4/01913.0018.542.2920.072.0329.971.2732.51106919553.5
    TBA2503714.1719.912.2921.442.0331.341.2733.88125321983.5
    TBA3503716.7922.532.2924.052.0333.961.2736.50172527723.5
    TBA5003720.0425.782.2927.302.0339.751.5242.80242938624.5
    TBA7506124.5930.582.2932.112.0344.551.5247.60360152655
    59966010006128.3734.372.2935.892.0349.201.5252.25477164275.5
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2180.3423590.53150.730.00910.16730.548+j0.5650.222+j0.0581769215221
    1187.9629770.41990.570.00850.16080.509+j0.5440.176+j0.0551890245247
    1/0195.5837560.33460.460.00760.15420.478+j0.5250.140+j0.0532014278275
    2/0208.2847350.26900.370.00700.15090.456+j0.5040.113+j0.0522147317306
    3/0218.4459720.21000.290.00640.14440.435+j0.4810.088+j0.0502305357335
    4/0228.6075290.16730.230.00580.14110.422+j0.4560.071+j0.0482479404369
    250236.2289000.14110.190.00550.13780.413+j0.4350.060+j0.0472646456412
    350256.54124600.10170.140.00460.13120.398+j0.3960.044+j0.0452965537456
    500299.72178000.06890.100.00400.12800.381+j0.3530.031+j0.0453362616497
    750332.74267000.04590.070.00340.12140.363+j0.3000.022+j0.0423947706551
    1000365.76356000.03610.060.00300.11810.349+j0.2650.020+j0.0414409813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
    * CEC ampacities are based on:
    3-1/C in air copper and aluminum: D17M
    3-1/C direct buried copper and aluminum: D17A

    Revision: 1.000.000

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC