SPEC 26101

HVTECK CU 1/C 90NLEPR TS PVC AIA PVC 5kV 100% CSA

Single Conductor, 90 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:90 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 90 NLEPR AIA 5kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchinchmilinchlb/1000ft
    TBA270.2820.500900.5600.932501.032641
    TBA1190.3220.540900.6000.972501.072724
    TBA1/0190.3610.579900.6391.011501.111817
    TBA2/0190.4050.623900.6831.085501.185965
    TBA3/0190.4560.674900.7341.136501.2361110
    TBA4/0190.5120.730900.7901.192501.2921286
    TBA250370.5580.784900.8441.356501.4561458
    TBA350370.6610.887900.9471.459501.5591843
    TBA500370.7891.015901.0751.587601.7072433
    TBA750610.9681.204901.2641.800601.9203391
    TBA1000611.1171.353901.4131.949602.0694376
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    27.25300.1620.2040.0290.0510.551 + j0.5390.205 + j0.0521734215221
    17.56690.1280.1620.0260.0490.514 + j0.5150.163 + j0.051858245247
    1/07.78440.1020.1280.0240.0470.485 + j0.4940.129 + j0.0481979278275
    2/08.210640.0810.1020.0220.0460.462 + j0.4710.103 + j0.0472116317306
    3/08.613420.0640.0810.0200.0450.443 + j0.4460.082 + j0.0452274357335
    4/09.016920.0510.0650.0180.0430.429 + j0.420.066 + j0.0432447404369
    25010.120000.0430.0560.0170.0440.418 + j0.3970.057 + j0.0442614456412
    35010.928000.0310.0410.0150.0410.4 + j0.3570.042 + j0.0412934537456
    50011.940000.0220.0300.0130.0390.381 + j0.3140.031 + j0.043330616497
    75013.460000.0140.0230.0110.0370.359 + j0.2620.024 + j0.0373916706551
    100014.480000.0110.0190.0100.0360.342 + j0.2290.02 + j0.0364377813596
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldDia. Over ArmourJacket Thickness1Approx. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmmmmmmmkg/km
    TBA277.1612.702.2914.2223.671.2726.21954
    TBA1198.1813.722.2915.2424.691.2727.231077
    TBA1/0199.1714.712.2916.2325.681.2728.221216
    TBA2/01910.2915.822.2917.3527.561.2730.101436
    TBA3/01911.5817.122.2918.6428.851.2731.391652
    TBA4/01913.0018.542.2920.0730.281.2732.821914
    TBA2503714.1719.912.2921.4434.441.2736.982170
    TBA3503716.7922.532.2924.0537.061.2739.602743
    TBA5003720.0425.782.2927.3040.311.5243.363621
    TBA7506124.5930.582.2932.1145.721.5248.775046
    TBA10006128.3734.372.2935.8949.501.5252.556512
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2182.8823590.53150.670.00880.16730.551 + j0.5390.205 + j0.0521734215221
    1190.5029770.41990.530.00790.16080.514 + j0.5150.163 + j0.051858245247
    1/0195.5837560.33460.420.00730.15420.485 + j0.4940.129 + j0.0481979278275
    2/0208.2847350.26570.330.00670.15090.462 + j0.4710.103 + j0.0472116317306
    3/0218.4459720.21000.270.00610.14760.443 + j0.4460.082 + j0.0452274357335
    4/0228.6075290.16730.210.00550.14110.429 + j0.420.066 + j0.0432447404369
    250256.5489000.14110.180.00520.14440.418 + j0.3970.057 + j0.0442614456412
    350276.86124600.10170.130.00460.13450.4 + j0.3570.042 + j0.0412934537456
    500302.26178000.07220.100.00400.12800.381 + j0.3140.031 + j0.043330616497
    750340.36267000.04590.080.00340.12140.359 + j0.2620.024 + j0.0373916706551
    1000365.76356000.03610.060.00300.11810.342 + j0.2290.02 + j0.0364377813596
    * Calculations are based on three cables triplexed / 5 mil 25 % over lapping copper tape shield / Conductor temperature of 90°C / Shield temperature of 45°C / Earth resistivity of 100 ohms-meter
    † Ampacities are based on Table D17M of the 2015 Canadian Electrical Code Part I (40°C Ambient Air Temperature, indoor installation)
    ‡ Ampacities are based on Table D17A of the 2015 Canadian Electrical Code Part I

    Revision: 3.0.00C