SPEC 45503
1/C CU or TCU 2000V EPR RHH/RHW-2 Thermoset Solonon LSZH-TS Power Cable
Power Cable 2000 Volt Single Conductor Copper or Tinned Copper, Ethylene Propylene Rubber (EPR) insulation RHH/RHW-2 Thermoset SOLONON® (LSZH-TS) Jacket

Construction:
- Conductor:Class B compressed stranded bare or tinned copper per ASTM B3, ASTM B8, ASTM B33
- Binder Tape:Mylar Tape
- Insulation:Ethylene Propylene Rubber (EPR) Type RHH/RHW-2
- Overall Jacket:Cross-linked/Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket
Applications and Features:
Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} E30117 MASTER-DESIGN {UL} XXX AWG CU TYPE RHH OR RHW-2 XX MILS NL-EPR XX MILS SOLONON{R} SUN RES 2000V
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | mil | mil | inch | lb/1000ft | lb/1000ft | |
647083º | 1/0 | 19 | 45 | 45 | 0.598 | 326 | 427 |
TBA | 2/0 | 19 | 65 | 45 | 0.625 | 410 | 511 |
TBA | 3/0 | 19 | 65 | 45 | 0.676 | 518 | 629 |
TBA | 4/0 | 19 | 65 | 45 | 0.732 | 653 | 775 |
TBA | 250 | 37 | 75 | 65 | 0.838 | 771 | 947 |
TBA | 350 | 37 | 75 | 65 | 0.941 | 1081 | 1283 |
TBA | 500 | 37 | 75 | 65 | 1.069 | 1544 | 1779 |
TBA | 750 | 61 | 90 | 65 | 1.278 | 2316 | 2626 |
TBA | 1000 | 61 | 90 | 65 | 1.427 | 3088 | 3440 |
TBA | 2000 | 127 | 115 | 95 | 2.003 | 6175 | 6852 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
647083º | 1/0 | 2.3 | 844 | 0.102 | 0.122 | 0.044 | 125 | 150 | 170 |
TBA | 2/0 | 2.5 | 1064 | 0.081 | 0.097 | 0.043 | 145 | 175 | 195 |
TBA | 3/0 | 2.7 | 1342 | 0.064 | 0.078 | 0.042 | 165 | 200 | 225 |
TBA | 4/0 | 2.9 | 1692 | 0.051 | 0.062 | 0.041 | 195 | 230 | 260 |
TBA | 250 | 3.3 | 2000 | 0.043 | 0.053 | 0.041 | 215 | 255 | 290 |
TBA | 350 | 3.7 | 2800 | 0.031 | 0.039 | 0.04 | 260 | 310 | 350 |
TBA | 500 | 5.3 | 4000 | 0.022 | 0.029 | 0.039 | 320 | 380 | 430 |
TBA | 750 | 6.3 | 6000 | 0.014 | 0.022 | 0.038 | 400 | 475 | 535 |
TBA | 1000 | 7.1 | 8000 | 0.011 | 0.018 | 0.037 | 455 | 545 | 615 |
TBA | 2000 | 12 | 16000 | 0.005 | 0.016 | 0.034 | 555 | 665 | 750 |
Revision: 3.0.00C