SPEC 45360

CU 600/1000V XLPE Insulation PVC AIA PVC Jacket. XHHW-2 Teck

1000V Multi Conductor, Copper, FT4 - Flame Retardancy Rating, XLPE Insulation, Aluminum Interlocked Armour, Sunlight Resistant, Direct Buried, -40°C - 90°C, Rated HL, AG14

...

Construction:

  1. Conductor:Class B stranded copper, compressed, in accordance with ASTM B3 and B8. Sizes #1 to 4/0 are combination unilay-stranded copper conductors in accordance with ASTM B787.
  2. Insulation:Cross-Linked Polyethylene (XLPE)
  3. Grounding Conductors:Uninsulated Class B stranded grounding conductor
  4. Binder:Mylar tape
  5. Inner Jacket:Black Polyvinyl Chloride (PVC)
  6. Armor:Aluminum Interlocked Armour (AIA)
  7. Overall Jacket:Black PVC (optional colours available)

Applications and Features:

For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, hazardous locations or direct buried. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants.
  • -40°C - CSA Cold Bend and Impact Temperature
  • -40°C - Min. Installation Temperature
  • 90°C - Max. Continuous Operating Temperature

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • UL 1569 Metal-Clad Cables
  • CSA C22.2 No. 131 Type TECK 90 Cable
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA AG14 - Acid Gas Compliance
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQMTR_DUAL} SOUTHWIRE{R} MASTER-DESIGN {CSA} LL90458 3/C XXX AWG (XX{mm2}) CU TECK 90 XLPE -40{D}C FT4 AG14 SUN. RES. 90{D}C 1000V HL --- {UL} E96627 TYPE MC XLPE 600V SUN. RES. DIRECT BURIAL 90{D}C --- {NOM}-ANCE Tipo MC XHHW-2 CT FT4 600V o 1000V 90{D}C USA
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorInsul. ThicknessGroundDia. Over ArmourJacket Thickness1Approx. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C†
    AWG/KcmilNo.inchmilNo. x AWGinchmilinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    640853870.141451 x 100.846500.9564936.63960.6530.7860.05255
    6408811190.322801 x 61.545501.681164311.720080.1280.1540.046145
    6408781/0190.361801 x 61.632501.765190112.325340.1020.1220.030170
    6408893/0190.456801 x 41.814601.946264913.640270.0640.0780.029225
    6408984/0190.512801 x 41.943602.075321014.550780.0510.0620.028260
    640905350370.661901 x 32.36602.526502817.684000.0310.0390.027350
    TBA500370.789901 x 32.632602.743648719.2120000.0220.0290.039430
    6411551000611.117901 x 13.541853.6191223225.3240000.0110.0180.025615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorInsul. ThicknessGroundDia. Over ArmourJacket Thickness1Approx. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C†
    AWG/KcmilNo.mmmmNo. x AWGmmmmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    640853873.581.141 x 1021.491.2724.28734167.6417622.14242.580.170655
    6408811198.182.031 x 639.241.2742.702445297.1889360.41990.510.1509145
    6408781/0199.172.031 x 641.451.2744.832829312.42112760.33460.400.0984170
    6408893/01911.582.031 x 446.081.5249.433942345.44179200.21000.260.0951225
    6408984/01913.002.031 x 449.351.5252.714777368.30225970.16730.200.0919260
    6409053503716.792.291 x 359.941.5264.167482447.04373800.10170.130.0886350
    TBA5003720.042.291 x 366.851.5269.679654487.68534000.07220.100.1280430
    64115510006128.372.291 x 189.942.1691.9218203642.621068000.03610.060.0820615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item

    Revision: 3.0.00C