SPEC 45360
CU 600/1000V XLPE Insulation PVC AIA PVC Jacket. XHHW-2 Teck
1000V Multi Conductor, Copper, FT4 - Flame Retardancy Rating, XLPE Insulation, Aluminum Interlocked Armour, Sunlight Resistant, Direct Buried, -40°C - 90°C, Rated HL, AG14

Construction:
- Conductor:Class B stranded copper, compressed, in accordance with ASTM B3 and B8. Sizes #1 to 4/0 are combination unilay-stranded copper conductors in accordance with ASTM B787.
- Insulation:Cross-Linked Polyethylene (XLPE)
- Grounding Conductors:Uninsulated Class B stranded grounding conductor
- Binder:Mylar tape
- Inner Jacket:Black Polyvinyl Chloride (PVC)
- Armor:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black PVC (optional colours available)
Applications and Features:
For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, hazardous locations or direct buried. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants.
- -40°C - CSA Cold Bend and Impact Temperature
- -40°C - Min. Installation Temperature
- 90°C - Max. Continuous Operating Temperature
Specifications:
Sample Print Legend:
{SQMTR_DUAL} SOUTHWIRE{R} MASTER-DESIGN {CSA} LL90458 3/C XXX AWG (XX{mm2}) CU TECK 90 XLPE -40{D}C FT4 AG14 SUN. RES. 90{D}C 1000V HL --- {UL} E96627 TYPE MC XLPE 600V SUN. RES. DIRECT BURIAL 90{D}C --- {NOM}-ANCE Tipo MC XHHW-2 CT FT4 600V o 1000V 90{D}C USA
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Inner Jacket Thickness | Diameter Over Armor | Jacket Thickness | Approx. OD | Copper Weight | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | mil | inch | mil | inch | lb/1000ft | lb/1000ft | |||
640853 | 8 | 3 | 7 | 0.141 | 45 | 50 | 0.846 | 50 | 0.956 | 186 | 95 | 493 |
640881 | 1 | 3 | 19 | 0.322 | 80 | 50 | 1.545 | 50 | 1.681 | 863 | 181 | 1643 |
640878 | 1/0 | 3 | 19 | 0.361 | 80 | 50 | 1.632 | 50 | 1.765 | 1067 | 194 | 1901 |
640889 | 3/0 | 3 | 19 | 0.456 | 80 | 50 | 1.814 | 60 | 1.946 | 1698 | 259 | 2649 |
640898 | 4/0 | 3 | 19 | 0.512 | 80 | 50 | 1.943 | 60 | 2.075 | 2106 | 281 | 3210 |
640905 | 350 | 3 | 37 | 0.661 | 90 | 60 | 2.36 | 60 | 2.526 | 3436 | 350 | 5028 |
TBA | 500 | 3 | 37 | 0.789 | 90 | 110 | 2.632 | 60 | 2.743 | 4673 | 416 | 6487 |
641155 | 1000 | 3 | 61 | 1.117 | 90 | 75 | 3.541 | 85 | 3.619 | 9607 | 533 | 12232 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | ||
640853 | 8 | 3 | 6.6 | 396 | 0.653 | 0.786 | 0.052 | 40 | 50 | 55 |
640881 | 1 | 3 | 11.7 | 2008 | 0.128 | 0.154 | 0.046 | 110 | 130 | 145 |
640878 | 1/0 | 3 | 12.3 | 2534 | 0.102 | 0.122 | 0.030 | 125 | 150 | 170 |
640889 | 3/0 | 3 | 13.6 | 4027 | 0.064 | 0.078 | 0.029 | 165 | 200 | 225 |
640898 | 4/0 | 3 | 14.5 | 5078 | 0.051 | 0.062 | 0.028 | 195 | 230 | 260 |
640905 | 350 | 3 | 17.6 | 8400 | 0.031 | 0.039 | 0.027 | 260 | 310 | 350 |
TBA | 500 | 3 | 19.2 | 10000 | 0.022 | 0.029 | 0.039 | 320 | 380 | 430 |
641155 | 1000 | 3 | 25.3 | 10000 | 0.011 | 0.018 | 0.025 | 455 | 545 | 615 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.