SPEC 45265

AL 600/1000V XLPE Insulation PVC Jacket. XHHW-2. Silicone Free

Type TC-ER Power Cable 600Volt Four Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free.

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XXX AWG (XX{mm2}) 3E AL 4/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG 3E AL 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {NOM}-ANCE
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    TBA870.134451 x 8600.67477201
    TBA670.169451 x 8600.758114259
    TBA470.212451 x 6800.902182387
    TBA270.268451 x 6801.038276519
    TBA1190.298551 x 4801.159356653
    TBA1/0190.336551 x 4801.251439764
    TBA2/0190.376551 x 4801.348542897
    6722513/0160.422551 x 4801.4466781177
    5837274/0190.474551 x 2801.5728681406
    582123250220.520651 x 11101.78910311745
    672252300350.569651 x 21101.90912041966
    582124350350.615651 x 1/0302.02014322283
    578537400350.659651 x 11102.12416012520
    582121400350.659651 x 3/01102.23716812615
    578536500350.735651 x 11102.31019822972
    582125500350.735651 x 2/0302.35020293084
    596549500350.735651 x 3/0302.43420623197
    582126500350.735651 x 2501102.46721403327
    582127600580.812801 x 3501102.68726163998
    582250600580.812801 x 4/01102.69524843837
    578538750580.908801 x 1/01402.85829544296
    TBA900610.999801 x 1/01403.09635154898
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    TBA82.63961.0721.2900.052283236
    TBA63.06290.6740.8120.051324044
    TBA43.610010.4240.5100.048445260
    TBA25.115920.2670.3210.045607280
    TBA15.720080.2110.2540.046688092
    TBA1/06.225340.1680.2010.0448096108
    TBA2/06.731940.1330.1600.04392108120
    6722513/07.240270.1050.1260.042104124140
    5837274/07.850780.0840.1000.041120144164
    5821232508.960000.0710.0860.041136164184
    6722523009.572000.0590.0710.041156184208
    58212435012.184000.0500.0620.040168200224
    57853740012.796000.0440.0540.040180216244
    58212140013.496000.0440.0540.040180216244
    57853650013.8120000.0350.0440.039208248280
    58212550014.1120000.0350.0440.039208248280
    59654950014.6120000.0350.0440.039208248280
    58212650014.8120000.0350.0440.039208248280
    58212760016.1144000.0290.0370.039228272308
    58225060016.1144000.0290.0370.039228272308
    57853875017.1180000.0240.0310.038256308348
    TBA90018.5216000.0200.0270.037284340384
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.

    Revision: 3.0.00C