"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Cond. Strands","Cond. Number","Diameter Over Conductor","Insulation Thickness","Ground","Jacket Thickness","Approx. OD","Aluminum Weight","Approx. Weight" "","AWG/Kcmil","No.","","inches","mils","No. x AWG","mils","inches","lbs./MFT","lbs./MFT" "TBA","8","7","4","0.134","45","1 x 8","60","0.664","77","202" "TBA","6","7","4","0.169","45","1 x 8","60","0.749","114","259" "TBA","4","7","4","0.212","45","1 x 6","80","0.893","182","387" "TBA","2","7","4","0.268","45","1 x 6","80","1.028","276","518" "TBA","1","19","4","0.298","55","1 x 4","80","1.149","356","652" "TBA","1/0","19","4","0.336","55","1 x 4","80","1.241","439","764" "TBA","2/0","19","4","0.376","55","1 x 4","80","1.338","542","896" "672251","3/0","16","4","0.422","55","1 x 4","80","1.446","678","1177" "583727","4/0","19","4","0.474","55","1 x 2","80","1.572","868","1406" "582123","250","22","4","0.520","65","1 x 1","110","1.789","1031","1745" "672252","300","21","4","0.569","65","1 x 2","110","1.933","1204","1995" "582124","350","35","4","0.615","65","1 x 1/0","110","2.045","1432","2327" "578537","400","35","4","0.659","65","1 x 1","110","2.124","1601","2520" "582121","400","35","4","0.659","65","1 x 3/0","110","2.237","1681","2615" "578536","500","35","4","0.735","65","1 x 1","110","2.310","1982","2972" "582125","500","35","4","0.735","65","1 x 2/0","110","2.350","2029","3096" "596549","500","35","4","0.735","65","1 x 3/0","110","2.434","2062","3210" "582126","500","35","4","0.735","65","1 x 250","110","2.467","2140","3327" "582127","600","58","4","0.812","80","1 x 350","110","2.687","2616","3998" "582250","600","58","4","0.812","80","1 x 4/0","110","2.695","2484","3837" "578538","750","58","4","0.908","80","1 x 1/0","140","2.858","2954","4296" "TBA","900","61","4","0.999","80","1 x 1/0","140","3.087","3515","4896" "Table 2 - Electrical and Engineering Data" "" "Stock Number","Cond. Size","Cond. Number","Min Bending Radius","Max Pull Tension","DC Resistance @ 25C","AC Resistance @ 90C","Inductive Reactance @ 60Hz","Allowable Ampacity At 60C","Allowable Ampacity At 75C","Allowable Ampacity At 90C" "","AWG/Kcmil","","inches","lb","ohm/MFT","ohm/MFT","ohm/1000ft","Amps","Amps","Amps" "TBA","8","4","2.7","316","1.072","1.290","0.052","28","32","36" "TBA","6","4","3.0","503","0.674","0.812","0.051","32","40","44" "TBA","4","4","3.6","801","0.424","0.510","0.048","44","52","60" "TBA","2","4","5.1","1274","0.267","0.321","0.045","60","72","80" "TBA","1","4","5.7","1606","0.211","0.254","0.046","68","80","92" "TBA","1/0","4","6.2","2027","0.168","0.201","0.044","80","96","108" "TBA","2/0","4","6.7","2555","0.133","0.160","0.043","92","108","120" "672251","3/0","4","7.2","3221","0.105","0.126","0.042","104","124","140" "583727","4/0","4","7.9","4062","0.084","0.100","0.041","120","144","164" "582123","250","4","8.9","4800","0.071","0.086","0.041","136","164","184" "672252","300","4","9.7","5760","0.059","0.071","0.041","156","184","208" "582124","350","4","12.3","6720","0.050","0.062","0.040","168","200","224" "578537","400","4","12.7","7680","0.044","0.054","0.040","180","216","244" "582121","400","4","13.4","7680","0.044","0.054","0.040","180","216","244" "578536","500","4","13.9","9600","0.035","0.044","0.039","208","248","280" "582125","500","4","14.1","9600","0.035","0.044","0.039","208","248","280" "596549","500","4","14.6","9600","0.035","0.044","0.039","208","248","280" "582126","500","4","14.8","9600","0.035","0.044","0.039","208","248","280" "582127","600","4","16.1","11520","0.029","0.037","0.039","228","272","308" "582250","600","4","16.2","11520","0.029","0.037","0.039","228","272","308" "578538","750","4","17.1","14400","0.024","0.031","0.038","256","308","348" "TBA","900","4","18.5","17280","0.020","0.027","0.037","284","340","384" "All dimensions are nominal and subject to normal manufacturing tolerances"