SPEC 45257

CU 600V PVC-Nylon Insulation PVC Jacket. THHN/THWN-2

Type TC-ER Power Cable 600Volt Four Conductor Copper, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone Free

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    SOUTHWIRE{R} MASTER-DESIGN {UL} 1 AWG (XX.X{mm2}) CU 4 CDRS TYPE TC-ER THHN OR THWN CDRS GW 1 X X AWG 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE {YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    557694870.141301 x 10600.701238382
    664736870.141301 x 10 GG600.709238386
    553438670.177301 x 8600.789378559
    601989470.225401 x 8800.933572876
    601997270.282401 x 6801.0829091230
    6020031190.322501 x 6801.21811251545
    5545681/0190.361501 x 6801.30413991851
    5567202/0190.405501 x 6801.41017422252
    6020293/0190.456501 x 4801.53122232801
    4447454/0190.512501 x 4801.63727693286
    580495250370.558601 x 21101.89533254181
    602045250370.558601 x 41101.89532484113
    602060350370.661601 x 31102.14445305482
    563180350370.661601 x 3/01102.25748895892
    552513500370.789601 x 21102.39764437485
    593375500370.789601 x 250302.48570168064
    604819600610.865701 x 21102.69176919011
    TBA600610.865801 x 4/01102.71274788538
    604827750610.968701 x 11402.998961611402
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition - Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F) and adjusted to 80% per Table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    55769482.85280.6530.7860.052324044
    66473682.85280.6530.7860.052324044
    55343863.18390.4110.4950.051445260
    60198943.713350.2580.3100.048566876
    60199725.421230.1620.1950.0457692104
    60200316.026780.1280.1540.04688104116
    5545681/06.533790.1020.1220.044100120136
    5567202/07.042590.0810.0970.043116140156
    6020293/07.653690.0640.0780.042132160180
    4447454/08.167710.0510.0620.041156184208
    5804952509.480000.0430.0530.041172204232
    6020452509.480000.0430.0530.041172204232
    60206035012.8112000.0310.0390.040208248280
    56318035013.5112000.0310.0390.040208248280
    55251350014.3160000.0220.0290.039256304344
    59337550014.9160000.0220.0290.039256304344
    60481960016.1192000.0180.0250.039280336380
    TBA60016.2192000.0180.0250.039280336380
    60482775017.9240000.0140.0220.038320380428
    † Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition - Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F) and adjusted to 80% per Table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors.

    Revision: 3.0.00C