SPEC 45257
CU 600V PVC-Nylon Insulation PVC Jacket. THHN/THWN-2
Type TC-ER Power Cable 600Volt Four Conductor Copper, Polyvinyl Chloride (PVC) with nylon layer insulation THHN Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone Free
Specifications:
Sample Print Legend:
SOUTHWIRE{R} MASTER-DESIGN {UL} 1 AWG (XX.X{mm2}) CU 4 CDRS TYPE TC-ER THHN OR THWN CDRS GW 1 X X AWG 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE {YYYY}
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |
557694◊ | 8 | 7 | 0.141 | 30 | 1 x 10 | 60 | 0.701 | 238 | 382 |
664736◊ | 8 | 7 | 0.141 | 30 | 1 x 10 GG | 60 | 0.709 | 238 | 386 |
553438◊ | 6 | 7 | 0.177 | 30 | 1 x 8 | 60 | 0.789 | 378 | 559 |
601989◊ | 4 | 7 | 0.225 | 40 | 1 x 8 | 80 | 0.933 | 572 | 876 |
601997◊ | 2 | 7 | 0.282 | 40 | 1 x 6 | 80 | 1.082 | 909 | 1230 |
602003 | 1 | 19 | 0.322 | 50 | 1 x 6 | 80 | 1.218 | 1125 | 1545 |
554568◊ | 1/0 | 19 | 0.361 | 50 | 1 x 6 | 80 | 1.304 | 1399 | 1851 |
556720◊ | 2/0 | 19 | 0.405 | 50 | 1 x 6 | 80 | 1.410 | 1742 | 2252 |
602029◊ | 3/0 | 19 | 0.456 | 50 | 1 x 4 | 80 | 1.531 | 2223 | 2801 |
444745◊ | 4/0 | 19 | 0.512 | 50 | 1 x 4 | 80 | 1.637 | 2769 | 3286 |
580495 | 250 | 37 | 0.558 | 60 | 1 x 2 | 110 | 1.895 | 3325 | 4181 |
602045◊ | 250 | 37 | 0.558 | 60 | 1 x 4 | 110 | 1.895 | 3248 | 4113 |
602060◊ | 350 | 37 | 0.661 | 60 | 1 x 3 | 110 | 2.144 | 4530 | 5482 |
563180 | 350 | 37 | 0.661 | 60 | 1 x 3/0 | 110 | 2.257 | 4889 | 5892 |
552513◊ | 500 | 37 | 0.789 | 60 | 1 x 2 | 110 | 2.397 | 6443 | 7485 |
593375 | 500 | 37 | 0.789 | 60 | 1 x 250 | 30 | 2.485 | 7016 | 8064 |
604819 | 600 | 61 | 0.865 | 70 | 1 x 2 | 110 | 2.691 | 7691 | 9011 |
TBA | 600 | 61 | 0.865 | 80 | 1 x 4/0 | 110 | 2.712 | 7478 | 8538 |
604827 | 750 | 61 | 0.968 | 70 | 1 x 1 | 140 | 2.998 | 9616 | 11402 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition - Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F) and adjusted to 80% per Table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors.
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
557694◊ | 8 | 2.8 | 528 | 0.653 | 0.786 | 0.052 | 32 | 40 | 44 |
664736◊ | 8 | 2.8 | 528 | 0.653 | 0.786 | 0.052 | 32 | 40 | 44 |
553438◊ | 6 | 3.1 | 839 | 0.411 | 0.495 | 0.051 | 44 | 52 | 60 |
601989◊ | 4 | 3.7 | 1335 | 0.258 | 0.310 | 0.048 | 56 | 68 | 76 |
601997◊ | 2 | 5.4 | 2123 | 0.162 | 0.195 | 0.045 | 76 | 92 | 104 |
602003 | 1 | 6.0 | 2678 | 0.128 | 0.154 | 0.046 | 88 | 104 | 116 |
554568◊ | 1/0 | 6.5 | 3379 | 0.102 | 0.122 | 0.044 | 100 | 120 | 136 |
556720◊ | 2/0 | 7.0 | 4259 | 0.081 | 0.097 | 0.043 | 116 | 140 | 156 |
602029◊ | 3/0 | 7.6 | 5369 | 0.064 | 0.078 | 0.042 | 132 | 160 | 180 |
444745◊ | 4/0 | 8.1 | 6771 | 0.051 | 0.062 | 0.041 | 156 | 184 | 208 |
580495 | 250 | 9.4 | 8000 | 0.043 | 0.053 | 0.041 | 172 | 204 | 232 |
602045◊ | 250 | 9.4 | 8000 | 0.043 | 0.053 | 0.041 | 172 | 204 | 232 |
602060◊ | 350 | 12.8 | 11200 | 0.031 | 0.039 | 0.040 | 208 | 248 | 280 |
563180 | 350 | 13.5 | 11200 | 0.031 | 0.039 | 0.040 | 208 | 248 | 280 |
552513◊ | 500 | 14.3 | 16000 | 0.022 | 0.029 | 0.039 | 256 | 304 | 344 |
593375 | 500 | 14.9 | 16000 | 0.022 | 0.029 | 0.039 | 256 | 304 | 344 |
604819 | 600 | 16.1 | 19200 | 0.018 | 0.025 | 0.039 | 280 | 336 | 380 |
TBA | 600 | 16.2 | 19200 | 0.018 | 0.025 | 0.039 | 280 | 336 | 380 |
604827 | 750 | 17.9 | 24000 | 0.014 | 0.022 | 0.038 | 320 | 380 | 428 |
† Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition - Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F) and adjusted to 80% per Table 310.15(B)(3)(a) for More Than Three Current-Carrying Conductors.
Revision: 3.0.00C