SPEC 45255
TCU 600/1000V XLPE Insulation Thermoplastic CPE-TP. XHHW-2
Type TC-ER Power Cable 600Volt Three Conductor Copper, Ethylene Propylene Rubber (EPR) insulation XHHW-2 Thermoplastic Chlorinated Polyethylene (CPE) Jacket with 1 Tinned CU Ground. VW-1 Rated

Construction:
- Conductor:Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
- Insulation:Ethylene Propylene Rubber (EPR) Type XHHW-2. VW-1 Rated
- Grounding Conductor:Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
- Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 Rated.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} XX AWG (XX.X{mm2}) 3/C EPR/CPE TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG TINNED E75755 MASTER-DESIGN {UL} 600V 90{D}C DRY/90{D}C WET OIL RES I SUNLIGHT RESISTANT DIRECT BURIAL FT4/IEEE 1202 -- {NOM}-ANCE EPR/CPE Tipo XHHW-2 SR FT4 600V 90{D}C USA
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |
591981◊ | 8 | 7 | 0.141 | 45 | 1 x 10 | 45 | 0.647 | 186 | 307 |
591983◊ | 6 | 7 | 0.177 | 45 | 1 x 8 | 45 | 0.724 | 297 | 441 |
591985◊ | 4 | 7 | 0.225 | 45 | 1 x 8 | 60 | 0.853 | 441 | 634 |
591987◊ | 2 | 7 | 0.282 | 45 | 1 x 6 | 60 | 0.978 | 702 | 930 |
591989◊ | 1 | 19 | 0.322 | 55 | 1 x 6 | 60 | 1.162 | 864 | 1198 |
591991◊ | 1/0 | 19 | 0.361 | 55 | 1 x 6 | 80 | 1.216 | 1069 | 1406 |
591993◊ | 2/0 | 19 | 0.405 | 55 | 1 x 6 | 80 | 1.329 | 1326 | 1719 |
591995 | 3/0 | 19 | 0.456 | 55 | 1 x 4 | 80 | 1.437 | 1699 | 2127 |
591996◊ | 4/0 | 19 | 0.512 | 55 | 1 x 4 | 80 | 1.558 | 2109 | 2579 |
591998◊ | 250 | 37 | 0.558 | 65 | 1 x 4 | 80 | 1.755 | 2469 | 3091 |
592000◊ | 350 | 37 | 0.661 | 65 | 1 x 3 | 80 | 1.990 | 3438 | 4167 |
674038 | 500 | 37 | 0.789 | 65 | 1 x 3/0 | 110 | 2.224 | 5201 | 5976 |
592002 | 500 | 37 | 0.789 | 65 | 1 x 2 | 115 | 2.225 | 4884 | 5681 |
TBA | 750 | 61 | 0.968 | 80 | 1 x 1 | 110 | 2.668 | 7270 | 8572 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
591981◊ | 8 | 2.5 | 396 | 0.653 | 0.786 | 0.052 | 40 | 50 | 55 |
591983◊ | 6 | 2.8 | 629 | 0.411 | 0.495 | 0.051 | 55 | 65 | 75 |
591985◊ | 4 | 3.4 | 1001 | 0.258 | 0.310 | 0.048 | 70 | 85 | 95 |
591987◊ | 2 | 3.9 | 1592 | 0.162 | 0.195 | 0.045 | 95 | 115 | 130 |
591989◊ | 1 | 5.8 | 2008 | 0.128 | 0.154 | 0.046 | 110 | 130 | 145 |
591991◊ | 1/0 | 6.0 | 2534 | 0.102 | 0.122 | 0.044 | 125 | 150 | 170 |
591993◊ | 2/0 | 6.6 | 3194 | 0.081 | 0.097 | 0.043 | 145 | 175 | 195 |
591995 | 3/0 | 7.1 | 4027 | 0.064 | 0.078 | 0.042 | 165 | 200 | 225 |
591996◊ | 4/0 | 7.7 | 5078 | 0.051 | 0.062 | 0.041 | 195 | 230 | 260 |
591998◊ | 250 | 8.7 | 6000 | 0.043 | 0.053 | 0.041 | 215 | 255 | 290 |
592000◊ | 350 | 9.9 | 8400 | 0.031 | 0.039 | 0.040 | 260 | 310 | 350 |
674038 | 500 | 13.3 | 12000 | 0.022 | 0.029 | 0.039 | 320 | 380 | 430 |
592002 | 500 | 13.3 | 12000 | 0.022 | 0.029 | 0.039 | 320 | 380 | 430 |
TBA | 750 | 16.0 | 18000 | 0.014 | 0.022 | 0.038 | 400 | 475 | 535 |
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
Revision: 3.0.00C