SPEC 45055

TCU 600/1000V EPR Insulation XHHW-2 Thermoplastic CPE-TP Jacket. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable, 600/1000 Volt, Tinned Copper Conductors, Ethylene Propylene Rubber (EPR) Insulation XHHW-2, Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2, VW-1 Rated 14 - 10 AWG, CT Rated, Sunlight Resistant, For Direct Burial, Silicone Free

...

Construction:

  1. Conductor:7-strand class B compressed tinned copper per ASTM B33 and B8
  2. Insulation:Ethylene Propylene Rubber (EPR) Type XHHW-2
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP)

Applications and Features:

Southwire’s 600/1000 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Constructions with 2 conductors are rated TC. VW-1 rated for sizes 14 - 10 AWG. Sunlight Resistant. For Direct Burial. Silicone Free.

Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 44 VW-1 Vertical flame test on individual conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® XX AWG (X.XX{MM2}) X/C EPR/CPE TYPE TC-ER XHHW-2 CDRS E75755 {UL} 600V/1000V 90°C DRY/90°C WET OIL RES I SUNLIGHT RESISTANT DIRECT BURIAL FT4/IEEE 1202 -- {NOM}-ANCE EPR/CPE Tipo XHHW-2 SR FT4 600V/1000V 90°C USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    16 AWG
    59193116270.05730450.33216524.1815.1890.0331.3-18BK
    59193216370.05730450.35124674.1815.1890.0331.4-18BK
    59193316470.05730450.38232834.1815.1890.0331.5-14BK
    59193416570.05730450.415401004.1815.1890.0331.7-14BK
    59193516770.05730600.451561294.1815.1890.0331.8-13BK
    59193616970.05730600.555721784.1815.1890.0332.2-13BK
    591937161270.05730600.618962254.1815.1890.0332.5-9BK
    591938161570.05730600.6841212734.1815.1890.0332.7-9BK
    14 AWG
    59194414270.07130450.36625662.6313.2650.0581.52025BK
    59194714370.07130450.38838862.6313.2650.0581.62025BK
    591948◊14470.07130450.423501082.6313.2650.0581.71620BK
    591949◊14570.07130450.461631302.6313.2650.0581.81620BK
    591950◊14770.07130450.502881732.6313.2650.05821418BK
    591951◊14970.07130600.6161132332.6313.2650.0582.51418BK
    591952◊141270.07130600.6921502992.6313.2650.0582.81012BK
    591953141570.07130600.7431883652.6313.2650.05831012BK
    591954141970.07130600.8052384472.6313.2650.0583.21012BK
    591955142570.07130800.9493136112.6313.2650.0583.8911BK
    TBA143070.07130801.0064066982.6313.2650.0585911BK
    12 AWG
    59195912270.08930450.40441881.6622.0630.0541.62530BK
    591960◊12370.08930450.466611171.6622.0630.0541.92530BK
    591966◊121270.08930600.4662444121.6622.0630.0541.91215BK
    591962◊12470.08930450.469811471.6622.0630.0541.92024BK
    59196312570.08930600.5431021971.6622.0630.0542.22024BK
    591964◊12770.08930600.5891432541.6622.0630.0542.41821BK
    591965◊12970.08930600.5891833121.6622.0630.0542.41821BK
    591967121570.08930800.8643055431.6622.0630.0543.51215BK
    591968121970.08930800.9343876601.6622.0630.0543.71215BK
    10 AWG
    591973◊10270.11330450.448651171.041.2910.051.83540BK
    591974◊10370.11330450.476971611.041.2910.051.93540BK
    591976◊10470.11330650.561292251.041.2910.052.22832BK
    591977◊10570.11330600.6021622681.041.2910.052.42832BK
    59197810770.11330600.6552273561.041.2910.052.62428BK
    59197910970.11330600.7652914611.041.2910.053.12428BK
    591980101270.11330800.8993886311.041.2910.053.61820BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.015

    Updated On: March 9, 2026, 7:31 p.m. UTC