SPEC 45055

TCU 600V EPR Insulation Thermoplastic CPE-TP Jacket XHHW-2. Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable 600 Volt Tinned Copper Conductors, Ethylene Propylene Rubber (EPR) Insulation XHHW-2 Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2. VW-1 Rated #14 - #10 AWG. Sunlight Resistant - For Direct Burial - Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed tinned copper per ASTM B33 and ASTM B8
  2. Insulation:Ethylene Propylene Rubber (EPR) XHHW-2, 30 Mils thick for all cable sizes. VW-1 Rated #14 - #10 AWG
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 Rated #14 - #10 AWG. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 44 VW-1 Vertical flame test on individual conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    SOUTHWIRE{R} 14 AWG (2.08mm2) 3/C EPR/CPE TYPE TC-ER XHHW-2 CDRS E75755 MASTER-DESIGN (UL) 600V 90{D}C DRY/90{D}C WET OIL RES I SUNLIGHT RESISTANT DIRECT BURIAL FT4/IEEE 1202 -- NOM-ANCE EPR/CPE Tipo XHHW-2 SR FT4 600V 90{D}C USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CMin Bending RadiusAllowable Ampacity At 60°CAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    16 AWG
    59193116270.05630450.33216524.1815.0371.3--18
    59193216370.05630450.35124664.1815.0371.4--18
    59193316470.05630450.38232824.1815.0371.5--14
    59193416570.05630450.415401004.1815.0371.6--14
    59193516770.05630450.451561284.1815.0371.8--12
    59193616970.05630600.555721784.1815.0372.2--12
    591937161270.05630600.618962254.1815.0372.4--9
    591938161570.05630600.6841202734.1815.0372.7--9
    14 AWG
    59194414270.07030450.36625652.6313.1701.4152025
    59194714370.07030450.38837862.6313.1701.5152025
    59194814470.07030450.423501072.6313.1701.6121620
    59194914570.07030450.461621292.6313.1701.8121620
    59195014770.07030450.502871702.6313.1702.0101417
    591953141570.07030600.5601874132.6313.1702.271012
    591954141970.07030600.5602374132.6313.1702.271012
    59195114970.07030600.6161122322.6313.1702.4101417
    591952141270.07030600.6921502992.6313.1702.771012
    TBA142570.07030800.9493135972.6313.1703.76911
    TBA143070.07030800.9963756652.6313.1703.96911
    12 AWG
    59195912270.08830450.40440861.6622.0021.6202530
    59196012370.08830450.466611161.6622.0021.8202530
    591966121270.08830600.4662444111.6622.0021.8101215
    59196212470.08830450.469811471.6622.0021.8162024
    59196312570.08830450.5431011981.6622.0022.1162024
    59196412770.08830600.5891422531.6622.0022.3141721
    59196512970.08830600.5891833071.6622.0022.3141721
    591967121570.08830800.8643055381.6622.0023.4101215
    591968121970.08830800.9343866591.6622.0023.7101215
    10 AWG
    59197310270.11330450.448641161.0401.2531.7303540
    59197410370.11330450.476971601.0401.2531.9303540
    59197610470.11330450.5601292251.0401.2532.2242832
    59197710570.11330600.6021612671.0401.2532.4242832
    59197810770.11330600.6552263551.0401.2532.6212428
    59197910970.11330600.7652914501.0401.2533.0212428
    591980101270.11330800.8993886191.0401.2533.5151720
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.