SPEC 45053
Multi-Conductor CU 600V XLPE XHHW-2 CPE-TP Control Cable
Type TC-ER Control Cable 600Volt Copper Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2

Construction:
- Conductor:7 strands class B compressed copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) XHHW-2, 30 Mils thick for all cable sizes
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket
Applications and Features:
Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XX AWG XX/C TYPE TC-ER XHHW-2 CDRS 90{D}C CPE JACKET SUN RES OIL RES II FT4/IEEE1202 600 VOLTS
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | |||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | ||||||
14 AWG | |||||||||||||||||||
890674 | 14 | 2 | 7 | 30 | 45 | 0.355 | 25 | 67 | 2.631 | 3.170 | 1.4 | 15 | 20 | 25 | |||||
890675 | 14 | 3 | 7 | 30 | 45 | 0.376 | 38 | 91 | 2.631 | 3.170 | 1.5 | 15 | 20 | 25 | |||||
890676 | 14 | 4 | 7 | 30 | 45 | 0.409 | 51 | 111 | 2.631 | 3.170 | 1.6 | 12 | 16 | 20 | |||||
890677 | 14 | 5 | 7 | 30 | 45 | 0.447 | 64 | 129 | 2.631 | 3.170 | 1.7 | 12 | 16 | 20 | |||||
890678 | 14 | 7 | 7 | 30 | 45 | 0.486 | 89 | 172 | 2.631 | 3.170 | 1.9 | 10 | 14 | 17 | |||||
890679 | 14 | 9 | 7 | 30 | 60 | 0.592 | 114 | 232 | 2.631 | 3.170 | 2.3 | 10 | 14 | 17 | |||||
550407 | 14 | 12 | 7 | 30 | 60 | 0.670 | 153 | 299 | 2.631 | 3.170 | 2.6 | 7 | 10 | 12 | |||||
TBA | 14 | 15 | 7 | 30 | 60 | 0.744 | 203 | 357 | 2.631 | 3.170 | 2.9 | 7 | 10 | 12 | |||||
890680 | 14 | 19 | 7 | 30 | 60 | 0.774 | 243 | 440 | 2.631 | 3.170 | 3.0 | 7 | 10 | 12 | |||||
TBA | 14 | 25 | 7 | 30 | 80 | 0.952 | 331 | 590 | 2.631 | 3.170 | 3.8 | 6 | 9 | 11 | |||||
TBA | 14 | 30 | 7 | 30 | 80 | 1.005 | 395 | 688 | 2.631 | 3.170 | 5.0 | 6 | 9 | 11 | |||||
TBA | 14 | 37 | 7 | 30 | 80 | 1.082 | 485 | 824 | 2.631 | 3.170 | 5.4 | 6 | 8 | 10 | |||||
12 AWG | |||||||||||||||||||
550411 | 12 | 2 | 7 | 30 | 45 | 0.388 | 40 | 89 | 1.662 | 2.002 | 1.5 | 20 | 25 | 30 | |||||
890681 | 12 | 3 | 7 | 30 | 45 | 0.412 | 61 | 120 | 1.662 | 2.002 | 1.6 | 20 | 25 | 30 | |||||
890682 | 12 | 4 | 7 | 30 | 45 | 0.449 | 81 | 154 | 1.662 | 2.002 | 1.7 | 16 | 20 | 24 | |||||
890683 | 12 | 5 | 7 | 30 | 45 | 0.491 | 101 | 178 | 1.662 | 2.002 | 1.9 | 16 | 20 | 24 | |||||
550412 | 12 | 7 | 7 | 30 | 60 | 0.576 | 142 | 243 | 1.662 | 2.002 | 2.3 | 14 | 17 | 21 | |||||
550413 | 12 | 9 | 7 | 30 | 60 | 0.666 | 183 | 306 | 1.662 | 2.002 | 2.6 | 14 | 17 | 21 | |||||
890684 | 12 | 12 | 7 | 30 | 60 | 0.738 | 244 | 408 | 1.662 | 2.002 | 2.9 | 10 | 12 | 15 | |||||
TBA | 12 | 15 | 7 | 30 | 80 | 0.869 | 325 | 535 | 1.662 | 2.002 | 3.4 | 10 | 12 | 15 | |||||
TBA | 12 | 19 | 7 | 30 | 80 | 0.912 | 406 | 647 | 1.662 | 2.002 | 3.6 | 10 | 12 | 15 | |||||
TBA | 12 | 25 | 7 | 30 | 80 | 1.060 | 508 | 807 | 1.662 | 2.002 | 5.3 | 9 | 11 | 13 | |||||
TBA | 12 | 30 | 7 | 30 | 80 | 1.120 | 630 | 967 | 1.662 | 2.002 | 5.6 | 9 | 11 | 13 | |||||
TBA | 12 | 37 | 7 | 30 | 80 | 1.208 | 772 | 1164 | 1.662 | 2.002 | 6.0 | 8 | 10 | 12 | |||||
10 AWG | |||||||||||||||||||
550419 | 10 | 2 | 7 | 30 | 45 | 0.432 | 64 | 119 | 1.040 | 1.253 | 1.7 | 30 | 35 | 40 | |||||
890685 | 10 | 3 | 7 | 30 | 45 | 0.463 | 97 | 167 | 1.040 | 1.253 | 1.8 | 30 | 35 | 40 | |||||
890686 | 10 | 4 | 7 | 30 | 45 | 0.502 | 129 | 209 | 1.040 | 1.253 | 2.0 | 24 | 28 | 32 | |||||
550420 | 10 | 5 | 7 | 30 | 60 | 0.587 | 161 | 269 | 1.040 | 1.253 | 2.3 | 24 | 28 | 32 | |||||
550421 | 10 | 7 | 7 | 30 | 60 | 0.639 | 226 | 357 | 1.040 | 1.253 | 2.5 | 21 | 24 | 28 | |||||
890687 | 10 | 9 | 7 | 30 | 60 | 0.756 | 291 | 436 | 1.040 | 1.253 | 3.0 | 21 | 24 | 28 | |||||
890688 | 10 | 12 | 7 | 30 | 80 | 0.871 | 386 | 613 | 1.040 | 1.253 | 3.4 | 15 | 17 | 20 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.