CU 600V XLPE Insulation Thermoplastic CPE-TP Jacket. XHHW-2

Type TC-ER Control Cable 600Volt Copper Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket, Control Cable Conductor Identification Method 1 Table 2

...

Construction:

  1. Conductor:7 strands class B compressed copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) XHHW-2, 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket:Thermoplastic Chlorinated Polyethylene (CPE-TP) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XX AWG XX/C TYPE TC-ER XHHW-2 CDRS 90{D}C CPE JACKET SUN RES OIL RES II FT4/IEEE1202 600 VOLTS
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 90°CMin Bending RadiusAllowable Ampacity At 60°C *Allowable Ampacity 75°C *Allowable Ampacity 90°C *
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    14 AWG
    89067414270.07030450.35525672.6313.1701.4152025
    89067514370.07030450.37638912.6313.1701.5152025
    89067614470.07030450.409511112.6313.1701.6121620
    89067714570.07030450.447641292.6313.1701.7121620
    89067814770.07030450.486891722.6313.1701.9101417
    89067914970.07030600.5921142322.6313.1702.3101417
    550407141270.07030600.6701532992.6313.1702.671012
    TBA141570.07030600.7442033572.6313.1702.971012
    890680141970.07030600.7742434402.6313.1703.071012
    TBA142570.07030800.9523315902.6313.1703.86911
    TBA143070.07030801.0053956882.6313.1705.06911
    TBA143770.07030801.0824858242.6313.1705.46810
    12 AWG
    55041112270.08830450.38840891.6622.0021.5202530
    89068112370.08830450.412611201.6622.0021.6202530
    89068212470.08830450.449811541.6622.0021.7162024
    89068312570.08830450.4911011781.6622.0021.9162024
    55041212770.08830600.5761422431.6622.0022.3141721
    55041312970.08830600.6661833061.6622.0022.6141721
    890684121270.08830600.7382444081.6622.0022.9101215
    TBA121570.08830800.8693255351.6622.0023.4101215
    TBA121970.08830800.9124066471.6622.0023.6101215
    TBA122570.08830801.0605088071.6622.0025.391113
    TBA123070.08830801.1206309671.6622.0025.691113
    TBA123770.08830801.20877211641.6622.0026.081012
    10 AWG
    55041910270.11330450.432641191.0401.2531.7303540
    89068510370.11330450.463971671.0401.2531.8303540
    89068610470.11330450.5021292091.0401.2532.0242832
    55042010570.11330600.5871612691.0401.2532.3242832
    55042110770.11330600.6392263571.0401.2532.5212428
    89068710970.11330600.7562914361.0401.2533.0212428
    890688101270.11330800.8713866131.0401.2533.4151720
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.

    Revision: 3.0.00C