SPEC 41045
TELCOFLEX® Telecom 2/C Power Tray Cable
600 Volt Flexible Copper Conductors, TelcoHyde® 5221 Limited Smoke, Non-Halogen Insulation with Thermoset Jacket, Type TC. Rated 90°C Dry and 60°C Wet, Sunlight Resistant with a Limiting Oxygen Index of 35%.
Construction:
- Conductor:Flexible, Rope-lay Stranded, Class K, Tinned Copper per ASTM B33 and B172
- Separator:Opaque Mylar for ease of stripping
- Insulation:Limited smoke, non-halogenated TelcoHyde® 5221, 90°C Dry and 60°C Wet. Color: Red, White.
- Core Wrap:Core wrap for ease of stripping
- Jacket:Limited smoke, non-halogenated, TelcoHyde® 5221
Applications and Features:
This specification covers the construction requirements for two conductor cabled round limited smoke, non-halogenated power cable insulated with TelcoHyde® 5221. UL listed Type TC, FT4 in accordance with the National Electrical Code. Product is for use in Central Office, CATV Head End, Data Center and Cell tower applications. Cable is suitable for UL “CT USE” (Cable Tray rated). These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in dry locations and 60°C in wet locations, 130°C for emergency overload, and 250°C for short circuit conditions.
Specifications:
Sample Print Legend:
SOUTHWIRE LSZH TELCOFLEX® (UL) XX AWG (XX.X mm2) XXX STRAND CLASS K 2/C TYPE TC-ST1 90°C DRY 60°C WET CDRS 90°C JACKET FT4/IEEE 1202 SUN RES OIL RES I 600V --- {CSA} AWM I A/B 105°C 600V FT1 FT4 ST1
Table 1 – Physical and Electrical Data
Cond. Size | Cond. Strands | Diameter Over Cond. | Insul. Thickness | Approx. OD | Approx. Weight | DC Resistance @ 25°C | Min Bending Radius | Allowable Ampacity 75°C | Allowable Ampacity 90°C |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | strands | inch | mil | inch | lb/1000ft | Ω/1000ft | inch | Amp | Amp |
6 | 65 | 0.186 | 45 | 0.566 | 222 | 0.435 | 2.3 | 65 | 75 |
4 | 105 | 0.235 | 45 | 0.664 | 345 | 0.274 | 2.7 | 85 | 95 |
2 | 133 | 0.290 | 45 | 0.774 | 435 | 0.172 | 3.1 | 115 | 130 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Stock Numbers and Colors
Size (AWG) | Blue | Red |
---|---|---|
6 | 673184 | 672848 |
4 | 672852 | 672853 |
2 | 672855 | 672856 |
Revision: 1.000.001
Updated On: July 3, 2024, 10:13 p.m. UTC