SPEC 60365

Armorlite® Type MC THHN/THWN Aluminum Conductor Feeder Cable 277/480V Colors

Aluminum THHN/THWN-2 Insulated Singles with 8000 series Triple E™ Aluminum Alloy. Bare AlumaFlex™ Aluminum Alloy Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B801or ASTM B836
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Bare aluminum ground
  4. Filler:Fillers as needed
  5. Binder:Mylar tape
  6. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Feeder cable is suitable for use as follows:
- Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Suitable for power and lighting circuits.
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Environmental air-handling spaces per NEC 300.22 (C).
- Installation in cable tray and approved raceways, or as aerial cable on a messenger.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(E)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Type THHN/THWN rated 90ºC Dry/ 75ºC Wet
- Anti-short bushings are not required for use with MC cable per NEC and UL

Southwire Armorlite® Type MC Feeder Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Color Code - 3/C: Brown, Orange, Yellow
- 4/C: Brown, Orange, Yellow, Gray

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS Compliant Lead-Free, Silicone-Free, Halogen Free
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC AWG XX THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ft
    5654271/03BN,OE,YW0.33610601x41.240614
    5633702/03BN,OE,GY0.37612601x41.276705
    5654292/03BN,OE,YW,0.37612601x41.276705
    5628113/03BN,OE,YW0.42216601x41.377833
    5627084/03BN,OE,YW0.47419601x21.5901087
    5615872503BN,OE,YW0.52022701x2/01.7351336
    5628162503BN,OE,YW0.52022701x11.7311292
    5628183003BN,OE,YW0.56921701x11.8431474
    5630523503BN,OE,YW0.61535701x11.9421651
    5627044003BN,OE,YW0.65935701x3/02.0351911
    5733666003BN,OE,YW0.81241801x4002.6622916
    5630467503BN,OE,YW0.90858801x1/02.6203121
    5633651/04BN,OE,YW,GY0.33610601x41.304778
    5633742/04BN,OE,YW,GY0.37612601x41.400918
    5598943/04BN,OE,YW,GY0.42216601x41.6141168
    5598964/04BN,OE,YW,GY0.47419601x21.7391414
    5599042504BN,OE,YW,GY0.52022701x11.9011678
    5599073004BN,OE,YW,GY0.56921701x12.0221933
    5599093504BN,OE,YW,GY0.61535701x1/02.1062199
    5599114004BN,OE,YW,GY0.65935701x3/02.2372491
    5599155004BN,OE,YW,GY0.73534701x3/02.4232948
    1382975004BN,OE,YW,GY0.73534701x3502.6633186
    5599176004BN,OE,YW,GY0.81241801x3/02.6423508
    5598696004BN,OE,YW,GY0.81241801x4002.7813752
    5599197504BN,OE,YW,GY0.90853801x3/02.8914227
    5934507504BN,OE,YW,GY0.90853801x3503.1964452
    5598669004BN,OE,YW,GY0.99958801x2503.1485062
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusMax Pull TensionDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesLbsΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    1/038.719000.1680.2010.044120135
    2/038.923950.1330.1600.043135150
    2/038.923950.1330.1600.043135150
    3/039.630200.1050.1260.042155175
    4/0311.138080.0840.1000.041180205
    250312.145000.0710.0860.041205230
    250312.145000.0710.0860.041205230
    300312.954000.0590.0710.041230260
    350313.663000.0500.0620.040250280
    400314.272000.0440.0540.040270305
    600318.6108000.0290.0370.039340385
    750318.3135000.0240.0310.038385435
    1/049.120270.1680.2010.04496108
    2/049.825550.1330.1600.043108120
    3/0411.332210.1050.1260.042124140
    4/0412.240620.0840.1000.041144164
    250413.348000.0710.0860.041164184
    300414.257600.0590.0710.041184208
    350414.767200.0500.0620.040200224
    400415.776800.0440.0540.040216244
    500417.096000.0350.0440.039248280
    500418.696000.0350.0440.039248280
    600418.5115200.0290.0370.039272308
    600419.5115200.0290.0370.039272308
    750420.2144000.0240.0310.038308348
    750422.4144000.0240.0310.038308348
    900422.0172800.0200.0270.037340384
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.011

    Updated On: Dec. 31, 2024, 11:08 p.m. UTC