SPEC 60230

MC-AP™ Type MC All Purpose THHN/THWN Circuit Size Copper Conductor 120/208V Colors

Copper THHN Insulated Conductors. Full-Sized Aluminum Equipment Grounding/Bonding Conductor. UL Listed 600 Volt. Rated VW1. Lightweight Aluminum Interlocked Armor is Part of Equipment Bonding/Grounding Path.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Binder:Mylar tape
  4. Ground:Full-sized bare 8000 series aluminum grounding/bonding conductor. Armor and bare aluminum conductor form the equipment ground path.
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire MC-AP All Purpose Type MC Cable is suitable for use as follows:
- Branch, feeder and service power distribution in commercial, industrial, institutional, and multi- residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Binder tape with print legend wrapped around assembly.
- Type THHN/THWN rated 90ºC Dry.

Southwire Armorlite® Type MC Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS -- ARMOR IS EQUIPMENT GROUNDING PATH COMPONENT
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessDiameter Over ArmorCopper WeightOverall Weight
    AWG/Kcmilinchmilsinchlbs/1000ftlbs/1000ft
    14 AWG | SOLID Strands
    555272142BK,WE0.064SOLID150.4512570
    555273143BK,RD,WE0.064SOLID150.4683887
    555274144BK,RD,BE,WE0.064SOLID150.49250104
    12 AWG | SOLID Strands
    558768122RD,WE0.081SOLID150.4874092
    558770122BE,WE0.081SOLID150.4874092
    559841122BK,RD0.081SOLID150.4754091
    555103122BK,WE0.081SOLID150.4874092
    555104123BK,RD,WE0.081SOLID150.50760118
    559686123RD,WE,BE0.081SOLID150.50760118
    559684123BK,WE,BE0.081SOLID150.50760118
    555105124BK,RD,BE,WE0.081SOLID150.53880144
    567193126BK,RD,BE,WE/BK,WE/RD,WE/BE0.081SOLID150.61120199
    567246126BK,BK/WE,RD/WE,RD,WE/BK,WE0.081SOLID150.61120199
    558832128BK,BK/WE,RD,RD/WE,BE,BE/WE,WE,WE/BK0.081SOLID150.648160251
    12 AWG | 19 Strands
    596058123RD,PE,WE0.08919150.52960123
    567208124BK,RD,WE/BK,WE/RD0.08919150.56280151
    10 AWG | SOLID Strands
    555275102BK,WE0.102SOLID200.55662131
    559972102BE,WE0.102SOLID200.55662131
    559969102RD,WE0.102SOLID200.55662131
    555277103BK,RD,WE0.102SOLID200.58193170
    555278104BK,RD,BE,WE0.102SOLID200.62124210
    562278104BK,RD,WE/BK,WE/RD0.102SOLID200.62124210
    567197106BK,RD,BE,WE/BK,WE/RD,WE/BE0.102SOLID200.71186293
    558837106BK,BK/WE,RD,RD/WE,WE,WE/BK0.102SOLID200.71186293
    10 AWG | 19 Strands
    555875104BK,WE,RD,BE0.11319200.656129226
    567218106BK,RD,BE,WE/BK,WE/RD,WE/BE0.11319200.805194345
    567267106BK,RD,BK/WE,RD/WE,WE/BK,WE0.11319200.756194310
    56703082BK,WE0.14219300.682103197
    56703383BK,RD,WE0.14219300.717154264
    12 AWG | 19 Strands
    558788122BE,WE0.0919150.5074096
    558786122RD,WE0.0919150.5074096
    556377122BK,WE0.0919150.5074096
    556457123BK,RD,WE0.0919150.52960123
    555874124BK,RD,BE,WE0.0919150.56280151
    10 AWG | 19 Strands
    557387102BK,WE0.11719200.58665139
    557390103BK,RD,WE0.11719200.61497181
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    14 AWG | SOLID Strands
    1423.22.6313.2650.0582025
    1433.32.6313.2650.0582025
    1443.42.6313.2650.0581620
    12 AWG | SOLID Strands
    1223.41.6622.0630.0542530
    1223.41.6622.0630.0542530
    1223.31.6622.0630.0542530
    1223.41.6622.0630.0542530
    1233.51.6622.0630.0542530
    1233.51.6622.0630.0542530
    1233.51.6622.0630.0542530
    1243.81.6622.0630.0542024
    1264.31.6622.0630.0542024
    1264.31.6622.0630.0542024
    1284.51.6622.0630.0541821
    12 AWG | 19 Strands
    1233.71.6622.0630.0542530
    1243.91.6622.0630.0542024
    10 AWG | SOLID Strands
    1023.91.041.2910.053540
    1023.91.041.2910.053540
    1023.91.041.2910.053540
    1034.11.041.2910.053540
    1044.31.041.2910.052832
    1044.31.041.2910.052832
    10651.041.2910.052832
    10651.041.2910.052832
    10 AWG | 19 Strands
    1044.61.041.2910.052832
    1065.61.041.2910.052832
    1065.31.041.2910.052832
    824.80.6530.810.0525055
    8350.6530.810.0525055
    12 AWG | 19 Strands
    1223.51.6622.0630.0542530
    1223.51.6622.0630.0542530
    1223.51.6622.0630.0542530
    1233.71.6622.0630.0542530
    1243.91.6622.0630.0542024
    10 AWG | 19 Strands
    1024.11.041.2910.053540
    1034.31.041.2910.053540
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.006

    Updated On: Dec. 31, 2024, 11:08 p.m. UTC