SPEC 44103

4/C CU 2000V EPDM/CPE Type W Industrial Grade Cable 90°C. MSHA Approved

Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

...

Construction:

  1. Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
  2. Separator Tape:Non-conducting tape applied between the conductor and insulation to facilitate stripping
  3. Insulation:Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, red, green
  4. Fillers:Jute fillers applied as needed to round the cable core
  5. Reinforcement Binder:Reinforcing binder with twine applied over the core
  6. Jacket:Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)

Applications and Features:

Southwire Type W cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications per Article NEC 400. Suitable for continuous submersion in water – ideal for submersible pumps. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as perminant building wiring. Meets FT-5 Flame Test.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 1650 Standard for Portable Power Cable
  • CSA C22.2 No. 96 Portable Power Cables
  • MSHA Approved
  • RoHS-2 (European Directive 2011/65/EU)
  • Sample Print Legend:

    SOUTHWIRE® ROYAL® {5 CROWN LOGO} XX AWG (XX.XXmm2) 4/C TYPE W PORTABLE POWER CABLE E172226 (UL) 2000V 90C DRY 90C WET SUN RES -- 156205 CSA TYPE W 2000V -40C FT1 FT5 P-07-KA100010-MSHA
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightJacket Color
    AWG/KcmilNo.No.inchmilmilinchlb/1000ft
    55815284710.145601550.988577Black
    597803841330.145601551.011573Black
    55815464650.186601451.120748Black
    TBA444270.235601451.171952Black
    558156441120.235601251.2231054Black
    558157241680.290601451.4651766Black
    570102142240.300801451.6541985Black
    5581581/042590.379801651.7292249Black
    5581592/043240.400802251.8742764Black
    5600683/044180.480801551.8903226Black
    5600694/045320.530802352.1993979Black
    45621625046270.605952702.5385045Black
    57025035048930.670952842.9687114Black
    TBA500412210.858953103.1788464Black
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMin Bending RadiusAllowable Ampacity In Air 60°CAllowable Ampacity In Air 75°CAllowable Ampacity In Air 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    80.6790.8180.0523.9384652
    80.6790.8180.0525.0384652
    60.4350.5240.0515.6506270
    40.2740.3300.0485.8678191
    40.2740.3300.0486.1678191
    20.1720.2070.0457.390106122
    10.1370.1640.0468.2105125142
    1/00.1090.1310.0448.6121145164
    2/00.0870.1040.0439.3139166190
    3/00.0690.0830.0429.4201241274
    4/00.0550.0670.04113.1186222253
    2500.0470.0570.04114.9207248282
    3500.0330.0420.04017.8254305346
    5000.0230.0310.03919.0314376429
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Revision: 1.000.002

    Updated On: July 3, 2024, 10:13 p.m. UTC