SPEC 10080

Bare Copper Solid or Compressed

...

Construction:

  1. Conductor: Solid bare copper per ASTM B3 or Class A, B, or C, compressed, stranded, bare copper per ASTM B3 and B8

Applications and Features:

Bare copper conductors are suitable for overhead transmission and distribution as well as grounding and general electrical constructions. Stranded conductors (Class A) are ideal for Overhead transmission and distribution lines. More flexible stranded designs (Class B and C) work well for uninsulated connections, jumpers, grounding, or insulated cables for general wiring and underground systems.

Features:

  • The conductor is manufactured from Electrolytic Tough Pitch (ETP) copper, designated as Unified Numbering System (UNS) C11000, which applies to all copper products regardless of temper or stranding classification.
  • Soft-drawn copper exhibits an electrical conductivity of 100% at 20°C in accordance with the International Annealed Copper Standard (IACS).
  • Copper purity is at least 99.9%, with total impurities, including oxygen and other trace elements, limited to a maximum of 0.1%.
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand ClassStrand CountCond. CmilDiameter Over ConductorApprox. ODApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CRated Strength
    AWG/kcmilNo. of Strandscmilinchinchlb/1000ftΩ/1000ftΩ/1000ftlb
    550247◊18B716200.0450.04546.6698.03522
    106088◊16SolidSolid25800.0500.05074.1815.03726
    106146◊14SolidSolid41100.0640.064122.6313.17032
    TBA14B741100.0700.070122.6313.17032
    TBA14C1941100.0730.073122.6313.17032
    106203◊12SolidSolid65300.0800.080201.6622.00252
    TBA12B765300.0880.088201.6622.00252
    TBA12C1965300.0900.090201.6622.00252
    106260◊10SolidSolid103800.1010.101321.0401.25383
    13641610B7103800.1130.113321.0401.25383
    TBA10C19103800.1170.117321.0401.25383
    106328◊8SolidSolid165100.1280.128500.6530.786132
    106567◊8B7165100.1410.141500.6530.786132
    TBA8C19165100.1430.143500.6530.786132
    106385◊6SolidSolid262400.1620.162810.4110.495209
    106658◊6B7262400.1770.177810.4110.495209
    TBA6C19262400.1790.179810.4110.495209
    106443◊4SolidSolid417400.2040.2041280.2580.310333
    106740◊4B7417400.2250.2251280.2580.310333
    TBA4C19417400.2260.2261280.2580.310333
    TBA3SolidSolid526200.2290.2291620.2050.246420
    TBA3B7526200.2520.2521620.2050.246420
    TBA3C19526200.2540.2541620.2050.246420
    106500◊2SolidSolid663600.2570.2572040.1620.195530
    106864◊2B7663600.2820.2822040.1620.195530
    TBA2C19663600.2860.2862040.1620.195530
    TBA1SolidSolid836900.2890.2892580.1280.154669
    TBA1B19836900.3220.3222580.1280.154669
    5791951C37836900.3330.3332580.1280.154669
    2312821/0SolidSolid1056000.3240.3243250.1020.122844
    207712◊1/0B191056000.3610.3613250.1020.122844
    TBA2/0SolidSolid1331000.3640.3644100.0810.0971064
    106955◊1/0A71056000.3670.3683260.1020.122844
    TBA1/0C371056000.3730.3733250.1020.122844
    207746◊2/0B191331000.4050.4054100.0810.0971064
    TBA3/0SolidSolid1678000.4090.4095180.0640.0781342
    106989◊2/0A71331000.4130.4134100.0810.0971064
    162669◊2/0C371331000.4200.4204100.0810.0971064
    427641◊3/0B191678000.4560.4565180.0640.0781342
    TBA4/0SolidSolid2116000.4600.4606530.0510.0621692
    TBA3/0C371678000.4710.4715180.0640.0781342
    427633◊4/0B192116000.5120.5126530.0510.0621692
    107045◊4/0A72116000.5220.5216530.0510.0621692
    140152◊4/0C372116000.5290.5296530.0510.0621692
    120337250B372500000.5580.5587710.0430.0532000
    107078◊250A192500000.5730.5737710.0430.0532000
    TBA250C612500000.5750.5757710.0430.0532000
    TBA300B373000000.6100.6109260.0360.0452400
    TBA300C613000000.6300.6309260.0360.0452400
    TBA350B373500000.6610.66110810.0310.0392800
    107136◊350A193500000.6790.67810800.0310.0392800
    207852◊350C613500000.6810.68110810.0310.0392800
    471020400B374000000.7050.70512350.0270.0353200
    TBA400C614000000.7280.72812350.0270.0353200
    TBA450B374500000.7490.74913890.0240.0313600
    TBA450C614500000.7730.77313890.0240.0313600
    107193500B375000000.7890.81315440.0220.0294000
    TBA500C615000000.8140.81415440.0220.0294000
    TBA550B615500000.8280.82816980.0200.0264400
    TBA550C915500000.8540.85416980.0200.0264400
    TBA600B616000000.8650.86518530.0180.0254800
    TBA600C916000000.8930.89318530.0180.0254800
    TBA650B616500000.9010.90120070.0170.0235200
    TBA650C916500000.9290.92920070.0170.0235200
    TBA700B617000000.9350.93521610.0150.0225600
    TBA700C917000000.9640.96421610.0150.0225600
    107250◊750B617500000.9680.96823160.0140.0226000
    TBA750C917500000.9980.99823160.0140.0226000
    TBA800B618000001.0001.00024700.0130.0216400
    TBA800C918000001.0311.03124700.0130.0216400
    TBA900B619000001.0601.06027790.0120.0207200
    TBA900C919000001.0931.09327790.0120.0207200
    107284◊1000B6110000001.1171.11730880.0110.0188000
    TBA1000C9110000001.1521.15230880.0110.0188000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.038