SPEC 10010

RHH/RHW-2/USE-2 Copper Silicone-Free.

USE-2 600 Volts or RHH/RHW-2 1000 Volts. Underground Service Entrance Cable. Copper Conductors. Cross-Linked Polyethylene (XLP) Insulation. High Heat, Moisture and Abrasion Resistant.

...

Construction:

  1. Conductor:Soild bare copper per ASTM B3, Class B compressed stranded copper per ASTM B3 and B8, or 19-strand combination unilay copper per ASTM B3 and B787
  2. Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2 or USE-2. Silicone-Free, High Heat, Moisture and Abrasion Resistant

Applications and Features:

Southwire's USE-2 600 Volts or RHH/RHW-2 1000 Volts power cables are suited for use in wet and dry areas, conduits, ducts, troughs, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lb/ft maximum sidewall pressure.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • RoHS-2 (European Directive 2011/65/EU)
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE E32071 {UL} XXX AWG (XX.X{mm2}) CU TYPE USE-2 600V OR RHH OR RHW-2 1000V XX MILS XLP 90C
    Table 1 – Weights and Measurements
    Cond. SizeStrand CountDiameter Over ConductorInsul. ThicknessInsulation ColorApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    1470.07145BK0.1651221
    12SOLID0.08145BK0.1751928
    1270.08945BK0.1832029
    1070.11345BK0.2073243
    870.14260BK0.2689569
    670.17860GY0.30481103
    470.22560BK0.351128155
    370.25260BK0.378162191
    270.28360GY0.409204237
    1190.32280BK0.489258308
    1/0190.36280BK0.528325380
    2/0190.40580GN0.572410470
    3/0190.45680BK0.622518584
    4/0190.51280BE0.678655728
    250370.55895BK0.742771865
    300370.61195BK0.7949261026
    350370.66195BK0.86110811191
    400370.70695BK0.88512351349
    500370.78995WE0.96615431670
    600610.866110YW1.07218532012
    750610.968110GN1.17123152492
    1000611.117110BK1.34930883295
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    • TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    140.72.6313.2650.0582025
    120.71.6622.0630.0542530
    120.71.6622.0630.0542530
    100.81.041.2910.053540
    81.10.6530.810.0525055
    61.20.4110.510.0516575
    41.40.2580.320.0488595
    31.50.2050.2540.047100115
    21.60.1620.2010.045115130
    120.1280.1590.046130145
    1/02.10.1020.1270.044150170
    2/02.30.0820.1020.043175195
    3/02.50.0640.0790.042200225
    4/02.70.0510.0630.041230260
    25030.0430.0530.041255290
    3003.20.0360.0450.041285320
    3503.40.0310.0390.04310350
    4003.50.0270.0350.04335380
    5003.90.0210.0270.039380430
    6005.40.0180.0240.039420475
    7505.90.0140.0190.038475535
    10006.70.0110.0160.037545615
    •Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    • Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Table 3 - Stock Code Colors

    Size (Strand)BlackRedBlueWhiteBrownOrangeYellowGrayGreenPurple
    12 (Solid)113399
    12 (7)113431
    10 (7)113449645838
    8 (7)113456952689588683643957655993
    6 (7)113464620685959726640110646503646504646506646507640128
    4 (7)113472476549643577476565588746588747952663
    3 (7)113480587189
    2 (7)113498476531643544476523620746616347616346620747958009
    1 (19)113506647620647621647622
    1/0 (19)113514643973
    2/0 (19)113522666096591255
    3/0 (19)113530
    4/0 (19)113548647337647338564225
    250 (37)113555
    300 (37)113563
    350 (37)113571666097
    400 (37)113589
    500 (37)113597678973139530678974580165580166580168580169
    600 (61)113605139369139370139371
    750 (61)113613139351139352139353139354
    1000 (61)113647

    Revision: 1.000.043

    Updated On: Sept. 3, 2026, 5:48 p.m. UTC

    Award Winning Patent Pending Building Wire Selector
    QR Code