SPEC 44141

3/C CU 2000V EPDM/CPE Type G-GC Industrial Grade Cable 90°C. MSHA Approved

Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

...

Construction:

  1. Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
  2. Separator Tape:Non-conducting tape applied between the conductor and insulation to facilitate stripping
  3. Insulation:Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, red
  4. Ground Conductors:Two insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172
  5. Ground Check:One insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172
  6. Fillers:Paper fillers applied as needed to round the cable core
  7. Reinforcement Binder:Reinforcing binder with twine applied over the core
  8. Jacket:Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)

Applications and Features:

Southwire Type G-GC cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications where equipment grounding is required. Suitable for continuous submersion in water – ideal for submersible pumps, marine application. Also suitable for use in light to medium-duty mining applications. Sunlight resistant. Highly flexible and easy to work with in cold conditions. Not for use as permanent building wiring. Meets FT-5 Flame Test.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • CSA C22.2 No. 96 Portable Power Cables
  • RoHS-2 (European Directive 2011/65/EU)
  • Sample Print Legend:

    {CSA} LL90458 XXX AWG 3/C TYPE G-GC PORTABLE POWER CABLE 90°C WET OR DRY 2000V SUN RES. FT1/FT5 (-40°C) --- 07-KA110009-MSHA
    Table 1 – Weights and Measurements
    Cond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessGroundGround Check Insulation ThicknessJacket ThicknessApprox. ODApprox. WeightJacket Color
    AWG/KcmilNo.No.inchmilNo. x AWGmilmilinchlb/1000ft
    1031040.125602 x 121 x 12750.682144BK
    83710.145602 x 101 x 101450.865206BK
    63650.186602 x 101 x 101450.954303BK
    431120.235602 x 81 x 101451.06474BK
    231680.291602 x 71 x 101451.181593BK
    132240.3802 x 61 x 81451.287754BK
    1/032590.379802 x 51 x 81601.4871131BK
    2/033240.4802 x 41 x 81601.5331429BK
    3/034180.48802 x 31 x 81601.7051737BK
    4/035320.53802 x 21 x 81751.8432113BK
    25036080.605952 x 11 x 81552.032564BK
    35038550.67952 x 1/01 x 82402.3413480BK
    500312210.858952 x 3/01 x 82702.8074912BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMin Bending RadiusAllowable Ampacity In Air 60°CAllowable Ampacity In Air 75°CAllowable Ampacity In Air 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    101.041.2910.052.7374349
    80.6540.8120.0523.5485765
    60.4190.520.0513.8637787
    40.2630.3260.0485.384101114
    20.1660.2060.0455.9112133152
    10.1320.1640.0466.4131156177
    1/00.1050.130.0447.4151181205
    2/00.0840.1040.0437.7174208237
    3/00.0660.0820.0428.5201241274
    4/00.0530.0660.0419.2232277316
    2500.0450.0560.04112.2259310352
    3500.0320.0410.0414318381433
    5000.0220.0290.03916.8392470536
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.