SPEC 44100

1/C CU 2000V EPDM/CPE Type W RHH/RHW-2 Industrial Grade Cable 90°C. MSHA Approved

Flexible Copper Conductors, Ethylene Propylene Diene Monomer (EPDM) Insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket. Type RHH/RHW-2 90°C Wet and Dry

...

Construction:

  1. Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
  2. Separator Tape:Non-conducting tape applied between the conductor and insulation to facilitate stripping
  3. Insulation:Ethylene Propylene Diene Monomer (EPDM)
  4. Reinforcement Binder:Reinforcing twine.
  5. Jacket:Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)

Applications and Features:

Southwire Type W cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications per NEC Article 400. Suitable for continuous submersion in water ideal for submersible pumps. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Approved for use per the NEC® as Type RHH/RHW-2 90°C wet or dry. Meets FT-1 and FT-5 Flame Tests.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1650 Standard for Portable Power Cable
  • MSHA Approved
  • RoHS-2 (European Directive 2011/65/EU)
  • Sample Print Legend:

    SOUTHWIRE{R} ROYAL{R} XX AWG (53.5{mm2}) TYPE W PORTABLE POWER CABLE EXXXX {UL} RHH/RHW-2 2000V 90{D}C DRY 90{D}C WET SUN RES -- LL90458 {CSA} TYPE W 2000V -40{D}C FT1 FT5 P-07-KA100009-MSHA
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. StrandsDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightJacket Color
    AWG/KcmilNo.inchmilmilinchlb/1000ft
    59966481680.14560750.433132BK
    59971862730.18660950.522191BK
    64080744270.23560950.572255BK
    TBA26510.29060950.606299BK
    64081022590.29060950.666352BK
    64139212590.30080950.714432BK
    6413951/02590.37980950.759514BK
    6413982/03240.40080950.820614BK
    6413883/04180.480801000.854749BK
    6414024/05320.53080950.901894BK
    6414052506080.60595951.0111059BK
    6414093508930.67095951.1101411BK
    64141250012210.85895951.2541898BK
    56007250012210.85895951.2841935BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ class H stranding
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMin Bending RadiusAllowable Ampacity In Air 60°CAllowable Ampacity In Air 75°CAllowable Ampacity In Air 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    80.6790.8180.0521.7607080
    60.4350.5240.0512.08095105
    40.2740.3300.0482.2105125140
    20.1720.2070.0452.4140170190
    20.1720.2070.0452.6140170190
    10.1370.1640.0462.8165195220
    1/00.1090.1310.0443.0195230260
    2/00.0870.1040.0433.2225265300
    3/00.0690.0830.0423.4260310350
    4/00.0550.0670.0413.6300360405
    2500.0470.0570.0415.0340405455
    3500.0330.0420.0405.5420505570
    5000.0230.0310.0396.2515620700
    5000.0230.0310.0396.4515620700
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Revision: 1.000.002

    Updated On: Oct. 16, 2024, 8:19 p.m. UTC