SPEC 10111

Flat Parallel Pump 600 Volt Cable Type THW

600 Volts, Stranded Copper Conductors. Polyvinyl Chloride (PVC) Insulation. Water Well Cable, Moisture Resistant, Flat Parallel. Rated 75°C.

...

Construction:

  1. Conductor:Solid soft drawn or fully annealed bare copper per ASTM B3 or stranded class B compressed bare copper ASTM B3 and B8
  2. Insulation:Polyvinyl Chloride (PVC) Type THW

Applications and Features:

For use in residential, farm and industrial water well applications. Grounded and ungrounded water well cable systems. Conductors are twisted and colored black, red, and yellow when supplied with three conductors and green ground. Cable is supplied without an overall jacket.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® SUBMERSIBLE PUMP CABLE TYPE THW X AWG (X.XX{mm2}) W/GRD 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessGroundApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilNo. x AWGinchlb/1000ft
    56365814270.070301 x 140.166 X 0.55870
    56365914370.070301 x 140.166 X 0.74591
    563660122190.090301 x 120.185 X 0.61595
    563661123190.090301 x 120.185 X 0.830126
    563662102190.117301 x 100.210 X 0.690136
    563663103190.117301 x 100.210 X 0.930182
    56366583190.143451 x 100.270 X 1.109276
    56366663190.179601 x 80.304 X 1.272402
    563667!43190.226601 x 80.365 X 1.490568
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Cond. Number does not include ground conductor.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMax Pull TensionMin Bending RadiusAllowable Ampacity In Raceway At 75°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftlbinchAmp
    142.6313.1700.058982.220
    142.6313.1700.0581053.016
    121.6622.0020.0541562.525
    121.6622.0020.0541673.320
    101.0401.2530.0502492.835
    101.0401.2530.0502653.728
    80.6530.7860.0524225.540
    60.4110.4950.0516716.452
    40.2580.3100.04810687.568

    Revision: 1.000.007