SPEC 10111

Flat Parallel Pump 600 Volt Cable Type THW

600 Volts, Stranded Copper Conductors. Polyvinyl Chloride (PVC) Insulation. Water Well Cable, Moisture Resistant, Flat Parallel. Rated 75°C.

...

Construction:

  1. Conductor:Solid soft drawn or fully annealed bare copper per ASTM B3 or stranded class B compressed bare copper ASTM B3 and B8
  2. Insulation:Polyvinyl Chloride (PVC) Type THW

Applications and Features:

For use in residential, farm and industrial water well applications. Grounded and ungrounded water well cable systems. Conductors are twisted and colored black, red, and yellow when supplied with three conductors and green ground. Cable is supplied without an overall jacket.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® SUBMERSIBLE PUMP CABLE TYPE THW X AWG (X.XX{mm2}) W/GRD 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessGroundApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilNo. x AWGinchlb/1000ft
    563658◊14270.07301 x 140.166x0.55870
    563659◊14370.07301 x 140.166x0.74591
    563660◊122190.09301 x 120.185x0.61595
    563661◊123190.09301 x 120.185x0.830126
    563662◊102190.117301 x 100.210x0.690136
    563663◊103190.117301 x 100.210x0.930182
    563665◊83190.143451 x 100.270x1.109276
    563666◊63190.179601 x 80.304x1.272402
    563667◊43190.226601 x 80.365x1.490568
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Cond. Number does not include ground conductor.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMax Pull TensionMin Bending RadiusAllowable Ampacity In Raceway At 75°CAllowable Ampacity In Raceway At 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftlbinchAmpAmp
    142.6313.2650.058982.22025
    142.6313.2650.05810532025
    121.6622.0630.0541562.52530
    121.6622.0630.0541673.32530
    101.041.2910.052492.83540
    101.041.2910.052653.73540
    80.6530.810.0524225.55055
    60.4110.510.05167166575
    40.2580.320.04810687.58595