SPEC 10108

Flat Jacketed Heavy Duty 600 Volt Cable Type THW

600V, Water Well Cable, Moisture Resistant, PVC Insulation, Flat Parallel, Black PVC Jacket. Rated 75°C,

...

Construction:

  1. Conductor:Class B, stranded soft drawn bare copper per ASTM B8
  2. Insulation:Polyvinyl Chloride (PVC) Type THW
  3. Ground:Green Polyvinyl Chloride (PVC) Type THW
  4. Jacket:Black Polyvinyl Chloride (PVC)

Applications and Features:

For use in residential, farm and industrial water well applications. Used in both Grounded and ungrounded water well cable systems. Conductors are parallel and insulated with PVC colored black, red, and yellow. Insulated and jacketed with a Black Polyvinyl Chloride (PVC) material. Oil resistant. Used in both high temperature and low temperature wells

Specifications:

  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® SUBMERSIBLE PUMP CABLE TYPE THW XX AWG (XX.X{mm2}) 600 VOLTS {UL}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilNo. x AWGmilinchlb/1000ft
    563675◊14270.070451 x 14450.260x0.595115
    563678◊122190.090451 x 12450.280x0.660150
    563680◊102190.117451 x 10450.310x0.730202
    563682◊82190.143601 x 10450.370x0.850280
    563677◊14370.070451 x 14450.255x0.765150
    563679◊123190.090451 x 12450.280x0.814192
    563681◊103190.117451 x 10450.310x0.940266
    563683◊83190.143601 x 10450.370x1.120381
    563685◊63190.179601 x 8450.404x1.282530
    563686◊43190.226601 x 8450.460x1.447731
    563687◊23190.286601 x 6450.512x1.6561045
    563688◊1/03190.361801 x 6600.610x2.1701739
    563689◊2/03190.405801 x 6600.680x2.4252003
    644225◊3/03190.454801 x 4600.742x2.6802500
    583373◊4/03190.512801 x 4600.800x2.8142985
    583378◊3503370.661951 x 3800.955x3.5084582
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Conductor number does not include ground
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMax Pull TensionMin Bending RadiusAllowable Ampacity In Raceway At 75°CAllowable Ampacity In Raceway At 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftlbinchAmpAmp
    142.6313.1700.058652.42025
    121.6622.0020.0541042.62530
    101.0401.2530.0501662.93540
    80.6530.7860.0522643.45055
    142.6313.1700.058983.12025
    121.6622.0020.0541563.32530
    101.0401.2530.0502493.83540
    80.6530.7860.0523965.65055
    60.4110.4950.0516296.46575
    40.2580.3100.04810017.28595
    20.1620.1950.04515928.3115130
    1/00.1020.1220.044253410.9150170
    2/00.0810.0970.043319412.1175195
    3/00.0640.0780.042402713.4200225
    4/00.0510.0620.041507814.1230260
    3500.0310.0390.040840017.5310350
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.005

    Updated On: Dec. 31, 2024, 11:06 p.m. UTC