SPEC 45307
CU 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free
Type MC Power Cable 600Volt Four Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polypropylene tape
- Armor:Aluminum Interlocked Armor (AIA)
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE {UL} 4/C (XX AWG) XX.Xmm2 CU XX MILS XLP 600 VOLTS GW 1 X X AWG CU TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90°C USA -- {NOM}-ANCE Tipo MC XHHW-2 CT
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | inch | No. x AWG | inch | mil | inch | lb/1000ft | lb/1000ft | |||
| TBA | 8 | 4 | 7 | 0.142 | 45 | 0.232 | 1 x 10 | 0.774 | 50 | 0.874 | 206 | 485 | BK |
| 574460 | 6 | 4 | 7 | 0.178 | 45 | 0.268 | 1 x 8 | 0.875 | 50 | 0.98 | 379 | 659 | BK |
| TBA | 4 | 4 | 7 | 0.225 | 45 | 0.315 | 1 x 8 | 0.975 | 50 | 1.075 | 521 | 888 | BK |
| 580730 | 2 | 4 | 7 | 0.283 | 45 | 0.373 | 1 x 6 | 1.128 | 50 | 1.233 | 910 | 1280 | BK |
| TBA | 1 | 4 | 19 | 0.322 | 55 | 0.432 | 1 x 6 | 1.258 | 50 | 1.358 | 1042 | 1558 | BK |
| 890229 | 1/0 | 4 | 19 | 0.362 | 55 | 0.472 | 1 x 6 | 1.382 | 50 | 1.487 | 1399 | 1909 | BK |
| TBA | 2/0 | 4 | 19 | 0.405 | 55 | 0.515 | 1 x 6 | 1.459 | 50 | 1.559 | 1660 | 2271 | BK |
| TBA | 3/0 | 4 | 19 | 0.456 | 55 | 0.566 | 1 x 4 | 1.683 | 50 | 1.783 | 2092 | 2941 | BK |
| 562605 | 4/0 | 4 | 19 | 0.512 | 55 | 0.622 | 1 x 4 | 1.815 | 60 | 1.941 | 2770 | 3535 | BK |
| 557959 | 250 | 4 | 37 | 0.558 | 65 | 0.688 | 1 x 4 | 1.964 | 60 | 2.09 | 3249 | 4159 | BK |
| 551452 | 350 | 4 | 37 | 0.661 | 65 | 0.791 | 1 x 3 | 2.203 | 60 | 2.329 | 4530 | 5626 | BK |
| 668519 | 350 | 4 | 37 | 0.661 | 65 | 0.791 | 1 x 2/0 | 2.253 | 75 | 2.41 | 4781 | 5937 | BK |
| 605410 | 500 | 4 | 37 | 0.789 | 65 | 0.919 | 1 x 2 | 2.509 | 75 | 2.667 | 6444 | 7773 | BK |
| 563407 | 600 | 4 | 61 | 0.866 | 80 | 1.026 | 1 x 2 | 2.765 | 75 | 2.922 | 7691 | 9152 | BK |
| 672989 | 600 | 4 | 61 | 0.866 | 80 | 1.026 | 1 x 4/0 | 2.765 | 75 | 2.922 | 8146 | 9587 | BK |
| TBA | 750 | 4 | 61 | 0.968 | 80 | 1.128 | 1 x 1 | 3.043 | 75 | 3.193 | 9356 | 11304 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| TBA | 8 | 4 | 6.1 | 528 | 0.653 | 0.81 | 0.052 | 40 | 44 |
| 574460 | 6 | 4 | 6.9 | 839 | 0.411 | 0.51 | 0.051 | 52 | 60 |
| TBA | 4 | 4 | 7.5 | 1335 | 0.258 | 0.32 | 0.048 | 68 | 76 |
| 580730 | 2 | 4 | 8.6 | 2123 | 0.162 | 0.201 | 0.045 | 92 | 104 |
| TBA | 1 | 4 | 9.5 | 2678 | 0.128 | 0.159 | 0.046 | 104 | 116 |
| 890229 | 1/0 | 4 | 10.4 | 3379 | 0.102 | 0.127 | 0.044 | 120 | 136 |
| TBA | 2/0 | 4 | 10.9 | 4259 | 0.082 | 0.102 | 0.043 | 140 | 156 |
| TBA | 3/0 | 4 | 12.5 | 5369 | 0.064 | 0.079 | 0.042 | 160 | 180 |
| 562605 | 4/0 | 4 | 13.6 | 6771 | 0.051 | 0.063 | 0.041 | 184 | 208 |
| 557959 | 250 | 4 | 14.6 | 8000 | 0.043 | 0.053 | 0.041 | 204 | 232 |
| 551452 | 350 | 4 | 16.3 | 11200 | 0.031 | 0.039 | 0.04 | 248 | 280 |
| 668519 | 350 | 4 | 16.9 | 11200 | 0.031 | 0.039 | 0.04 | 248 | 280 |
| 605410 | 500 | 4 | 18.7 | 16000 | 0.021 | 0.027 | 0.039 | 304 | 344 |
| 563407 | 600 | 4 | 20.5 | 19200 | 0.018 | 0.024 | 0.039 | 336 | 380 |
| 672989 | 600 | 4 | 20.5 | 19200 | 0.018 | 0.024 | 0.039 | 336 | 380 |
| TBA | 750 | 4 | 22.4 | 24000 | 0.014 | 0.019 | 0.038 | 380 | 428 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
Revision: 1.000.007
Updated On: Dec. 31, 2024, 11:07 p.m. UTC


