SPEC 45302
CU 600/1000V XLPE Insulation ARMOR-X® Thermoplastic LSZH-TP Jacket XHHW-2. VFD Cable - CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free
Type MC-HL Power Cable 600 or 1000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Continuous Corrugated Welded Armor - ARMOR-X®, Thermoplastic Solonon® Low Smoke Zero Halogen (LSZH-TP) Jacket with Bare Copper Grounds

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and B8
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductors:Class B compressed stranded bare copper per ASTM B3 and B8
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polypropylene tape
- Armor:ARMOR-X® Continuous Corrugated Welded armor
- Overall Jacket:Thermoplastic Solonon® Low Smoke Zero Halogen (LSZH-TP)
Applications and Features:
Southwire’s 600 Volt Type MC-HL ARMOR-X® power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Cables with 3 ground wires suitable for VFD application.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE® {UL} ARMOR-X® TYPE MC-HL 3/C XX AWG or KCMIL (XX.X{MM2}) CU XHHW-2 GW 3 X XX AWG 90°C SOLONON® JACKET -40°C ST1 SUN.RES. DIR. BUR. FOR CT USE 600V/1kV IEEE1202/FT4 -- {NOM}-ANCE Tipo MC XHHW-2 CT FT4
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | inch | No. x AWG | inch | mil | inch | lb/1000ft | lb/1000ft | |||
| TBA | 8 | 3 | 7 | 0.142 | 45 | 0.232 | 3 x 14 | 0.75 | 50 | 0.85 | 154 | 385 | BK |
| TBA | 6 | 3 | 7 | 0.178 | 45 | 0.268 | 3 x 12 | 0.84 | 50 | 0.94 | 245 | 515 | BK |
| 647699 | 4 | 3 | 7 | 0.225 | 45 | 0.315 | 1 x 8 | 0.92 | 50 | 1.026 | 440 | 727 | BK |
| TBA | 2 | 3 | 7 | 0.283 | 45 | 0.373 | 1 x 6 | 1.06 | 50 | 1.16 | 621 | 975 | BK |
| TBA | 1/0 | 3 | 19 | 0.362 | 55 | 0.472 | 3 x 10 | 1.35 | 50 | 1.45 | 987 | 1530 | BK |
| 672673 | 2/0 | 3 | 19 | 0.405 | 55 | 0.515 | 3 x 10 | 1.47 | 50 | 1.576 | 1342 | 1955 | BK |
| 586674 | 3/0 | 3 | 19 | 0.456 | 55 | 0.566 | 3 x 8 | 1.54 | 60 | 1.666 | 1724 | 2409 | BK |
| TBA | 4/0 | 3 | 19 | 0.512 | 55 | 0.622 | 3 x 8 | 1.67 | 50 | 1.77 | 1978 | 2670 | BK |
| TBA | 250 | 3 | 37 | 0.558 | 65 | 0.688 | 3 x 8 | 1.845 | 50 | 1.945 | 2339 | 3179 | BK |
| TBA | 350 | 3 | 37 | 0.661 | 65 | 0.791 | 3 x 6 | 2.2 | 60 | 2.32 | 3275 | 4505 | BK |
| TBA | 500 | 3 | 37 | 0.789 | 65 | 0.919 | 3 x 6 | 2.43 | 60 | 2.55 | 4678 | 5993 | BK |
| TBA | 750 | 3 | 61 | 0.968 | 80 | 1.128 | 3 x 4 | 2.88 | 75 | 3.03 | 7017 | 8755 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| TBA | 8 | 3 | 6 | 396 | 0.653 | 0.81 | 0.052 | 50 | 55 |
| TBA | 6 | 3 | 6.6 | 629 | 0.411 | 0.51 | 0.051 | 65 | 75 |
| 647699 | 4 | 3 | 7.2 | 1001 | 0.258 | 0.32 | 0.048 | 85 | 95 |
| TBA | 2 | 3 | 8.1 | 1592 | 0.162 | 0.201 | 0.045 | 115 | 130 |
| TBA | 1/0 | 3 | 10.2 | 2534 | 0.102 | 0.127 | 0.044 | 150 | 170 |
| 672673 | 2/0 | 3 | 11 | 3194 | 0.082 | 0.102 | 0.043 | 175 | 195 |
| 586674 | 3/0 | 3 | 11.7 | 4027 | 0.064 | 0.079 | 0.042 | 200 | 225 |
| TBA | 4/0 | 3 | 12.4 | 5078 | 0.051 | 0.063 | 0.041 | 230 | 260 |
| TBA | 250 | 3 | 13.6 | 6000 | 0.043 | 0.053 | 0.041 | 255 | 290 |
| TBA | 350 | 3 | 16.2 | 8400 | 0.031 | 0.039 | 0.04 | 310 | 350 |
| TBA | 500 | 3 | 17.8 | 12000 | 0.021 | 0.027 | 0.039 | 380 | 430 |
| TBA | 750 | 3 | 21.2 | 18000 | 0.014 | 0.019 | 0.038 | 475 | 535 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.015
Updated On: Aug. 8, 2025, 5:53 p.m. UTC
VFD Sizing Calculator

