SPEC 45227

CU 600V XLPE Insulation ARMOR-X® PVC Jacket XHHW-2 Control Cable. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type MC-HL Control Cable 600Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Continuous Corrugated Welded Armor ARMOR-X®, Polyvinyl Chloride (PVC) Jacket with 1 Insulated Green CU Ground

...

Construction:

  1. Conductor:7 strands class B compressed copper per ASTM B3 and B8
  2. Insulation:Cross Linked Polyethylene (XLPE) XHHW-2
  3. Grounding Conductor:Class B compressed stranded copper with green insulation
  4. Filler:Polypropylene filler as needed
  5. Binder:Polyester flat thread binder tape as needed
  6. Armor:ARMOR-X® Continuous Corrugated Aluminum Welded Armor
  7. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 600 Volt Type MC-HL ARMOR-X® control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -40°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • UL 2225 Cables and Cable-Fittings For Use In Hazardous (Classified) Locations
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • Sample Print Legend:

    {SQFTG_DUAL} SOUTHWIRE ARMOR-X {UL} TYPE MC-HL ARMOR-X® X/C XXAWG (X.XXmm2}) CU XHHW-2 GW 1 X X AWG 90°C JACKET -40°C SUN. RES. DIR. BUR. FOR CT USE 600V IEEE1202/FT4 -- {CSA} RA90-HL AGXX XLPE -40°C 600V FT4 SR 90°C -- CWCMC -- {NOM}-ANCE Tipo MC XHHW-2 CT FT4 -- USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsInsul. ThicknessGroundDiameter Over ArmorJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsmilNo. x AWGinchmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    14 AWG
    554894!1427301 x 140.480500.586381652.6313.1700.0584.12025Black
    568912^1427301 x 140.480500.586381592.6313.1700.0584.12025Black
    5892891447301 x 140.650500.676642142.6313.1700.0584.71620Black
    5506071467301 x 140.650500.756892672.6313.1700.0585.31620Black
    5864501477301 x 140.650500.756892482.6313.1700.0585.31620Black
    12 AWG
    8905921277301 x 120.700500.8061423371.6622.0020.0545.62024Black
    14 AWG
    5506091487301 x 140.700500.8061143182.6313.1700.0585.61417Black
    890611!1497301 x 140.790500.8961273522.6313.1700.0586.31417Black
    55061414117301 x 140.480500.8961533882.6313.1700.0586.21012Black
    890585!14127300 x -0.790500.8961533872.6313.1700.0586.31012Black
    55061514187301 x 140.920501.0262425402.6313.1700.0587.21012Black
    55061714367301 x 140.943501.0434727932.6313.1700.0584.1810Black
    12 AWG
    550810!1227301 x 120.530500.636611931.6622.0020.0544.52530Black
    568795^1237301 x 120.610500.716812361.6622.0020.0545.02530Black
    5687961247301 x 120.650500.7561022721.6622.0020.0545.32024Black
    5506101257301 x 120.700500.8061213131.6622.0020.0545.62024Black
    5506111267301 x 120.700500.8061413361.6622.0020.0545.62024Black
    5506181287301 x 120.790500.8961824091.6622.0020.0546.31721Black
    55061912117301 x 120.920501.0262435161.6622.0020.0547.21215Black
    58418912127301 x 120.920501.0262635431.6622.0020.0547.21215Black
    55062012187301 x 121.020501.1263857221.6622.0020.0547.91215Black
    10 AWG
    954321!1027301 x 100.650500.756972681.0401.2530.0505.33540Black
    5506121057301 x 100.790500.8961934111.0401.2530.0506.32832Black
    5506131067301 x 100.790500.8962254501.0401.2530.0506.32832Black
    5506221087301 x 100.920501.0262895641.0401.2530.0507.22428Black
    550623!10117301 x 101.020501.1263866991.0401.2530.0507.91720Black
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    ! No CSA product Type RA90-HL
    ^ Tested as per IEC 60332-3-22 & 60092-350
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.022

    Updated On: Dec. 31, 2024, 11:07 p.m. UTC