SPEC 45052

CU 600/1000V XLPE Insulation PVC Jacket XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable, 600 or 1000 Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2, Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2, CT Rated, Sunlight Resistant, For Direct Burial, VW-1 Rated, Silicone Free

...

Construction:

  1. Conductor:7-strand class B compressed bare copper per ASTM B3 and B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2 VW-1 Rated
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket:Polyvinyl Chloride (PVC)

Applications and Features:

Southwire’s 600 or 1000 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. The jacket acts as gas/vapor-tight polymeric sheath that is extruded over the core per Sections 501.15(D) and 501.15(E) of the NEC, however when these cables are used in a hazardous location, they may need to be sealed further as described in more detail in the NEC. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 Rated - Sunlight Resistant - For Direct Burial - Silicone Free.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 44 VW-1 Vertical flame test on individual conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Control, Thermocouple Extension, and Instrumentation Cables (applicable to sizes 20-9 AWG conductors)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE® {UL} XX AWG (X.XX{MM2}) CU X/C TYPE TC-ER XHHW-2 CDRS 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL FT4/IEEE1202 600V or 1000V {NOM}-ANCE XHHW-2 CT SR 600V 90°C
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessDiameter Over InsulationJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilinchmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    14 AWG
    952459◊14270.071300.131450.36426682.6313.2650.0581.52025BK
    952465◊14370.071300.131450.38638932.6313.2650.0581.52025BK
    952473◊14470.071300.131450.42511132.6313.2650.0581.71620BK
    952481◊14570.071300.131450.458641332.6313.2650.0581.81620BK
    952440◊14770.071300.131450.495901732.6313.2650.05821418BK
    95249914670.071300.131450.499771562.6313.2650.05821620BK
    95250714870.071300.131600.5731022132.6313.2650.0582.31418BK
    952572◊14970.071300.131600.6131152372.6313.2650.0582.51418BK
    952598◊141270.071300.131600.6881533032.6313.2650.0582.81012BK
    952606◊141570.071300.131600.7621913682.6313.2650.05831012BK
    952614◊141970.071300.131600.8012434512.6313.2650.0583.21012BK
    952622142070.071300.131600.8772555022.6313.2650.0583.51012BK
    952630◊142570.071300.131800.9783196182.6313.2650.0583.9911BK
    952648143070.071300.131801.0333867262.6313.2650.0585.2911BK
    952655◊143770.071300.131801.1134758622.6313.2650.0585.6810BK
    12 AWG
    953042◊12270.089300.149450.441911.6622.0630.0541.62530BK
    953059◊12370.089300.149450.42611211.6622.0630.0541.72530BK
    953067◊12470.089300.149450.463811561.6622.0630.0541.92024BK
    953075◊12570.089300.149450.5031021791.6622.0630.05422024BK
    953091◊12770.089300.149600.5791432551.6622.0630.0542.31821BK
    95310912870.089300.149600.6071622801.6622.0630.0542.41821BK
    953117◊12970.089300.149600.6781823241.6622.0630.0542.71821BK
    953125121070.089300.149600.7382033581.6622.0630.05431215BK
    953133◊121270.089300.149600.7622434161.6622.0630.05431215BK
    953141121570.089300.149800.8813045371.6622.0630.0543.51215BK
    953158◊121970.089300.149800.9333866641.6622.0630.0543.71215BK
    953174◊122570.089300.149801.0755118431.6622.0630.0545.41114BK
    953190123770.089300.149851.20975411761.6622.0630.05461012BK
    10 AWG
    952861◊10270.113300.173450.448651221.041.2910.051.83540BK
    952879◊10370.113300.173450.472971661.041.2910.051.93540BK
    952895◊10470.113300.173600.5471292301.041.2910.052.22832BK
    952887◊10570.113300.173600.6041622731.041.2910.052.42832BK
    TBA10770.113300.173600.6452583731.041.2910.052.62428BK
    952911◊10770.113300.173600.6572273621.041.2910.052.62428BK
    95292910870.113300.173600.7122584081.041.2910.052.82428BK
    952937◊10970.113300.173600.7652904561.041.2910.053.12428BK
    952952◊101270.113300.173800.9043876261.041.2910.053.61820BK
    952960101570.113300.173801.0024837631.041.2910.0551820BK
    952978101970.113300.173801.0456139311.041.2910.055.21820BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.