SPEC 45360
CU 600/1000V XLPE Insulation PVC AIA PVC Jacket XHHW-2. Teck - CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free
{SQMTR_DUAL} SOUTHWIRE{R} {CSA} LL90458 3/C XXX AWG (XX{mm2}) CU TECK 90 XLPE -40{D}C FT4 AG14 SUN. RES. 90{D}C 1000V HL --- {UL} E96627 TYPE MC XLPE 600V SUN. RES. DIRECT BURIAL 90{D}C --- {NOM}-ANCE Tipo MC XHHW-2 CT FT4 600V o 1000V 90{D}C USA

Construction:
- Conductor:Class B stranded copper, compressed, in accordance with ASTM B3 and B8. Sizes #1 to 4/0 are combination unilay-stranded copper conductors in accordance with ASTM B787.
- Insulation:Cross-Linked Polyethylene (XLPE)
- Grounding Conductors:Uninsulated Class B stranded grounding conductor
- Binder:Mylar tape
- Inner Jacket:Black Polyvinyl Chloride (PVC)
- Armor:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black PVC (optional colours available)
Applications and Features:
For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, hazardous locations or direct buried. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants.
- -40°C - CSA Cold Bend and Impact Temperature
- -40°C - Min. Installation Temperature
- 90°C - Max. Continuous Operating Temperature
Specifications:
Sample Print Legend:
{SQMTR_DUAL} SOUTHWIRE® {CSA} LL90458 3/C XXX AWG (XX{mm2}) CU TECK 90 XLPE -40°C FT4 AG14 SUN. RES. 90°C 1000V HL --- {UL} E96627 TYPE MC XLPE 600V SUN. RES. DIRECT BURIAL 90°C --- {NOM}-ANCE Tipo MC XHHW-2 CT FT4 600V o 1000V 90°C USA
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Ground | Inner Jacket Thickness | Diameter Over Armor | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft | lb/1000ft | |||
| 640853 | 8 | 3 | 7 | 0.142 | 45 | 0.232 | 1 x 10 | 50 | 0.846 | 55 | 0.956 | 187 | 491 | BK |
| 640881 | 1 | 3 | 19 | 0.322 | 80 | 0.432 | 1 x 6 | 50 | 1.549 | 65 | 1.681 | 865 | 1641 | BK |
| 640878 | 1/0 | 3 | 19 | 0.362 | 80 | 0.472 | 1 x 6 | 50 | 1.633 | 65 | 1.765 | 1070 | 1900 | BK |
| 640889 | 3/0 | 3 | 19 | 0.456 | 80 | 0.566 | 1 x 4 | 50 | 1.814 | 65 | 1.946 | 1700 | 2654 | BK |
| 640898 | 4/0 | 3 | 19 | 0.512 | 80 | 0.622 | 1 x 4 | 50 | 1.943 | 65 | 2.075 | 2110 | 3207 | BK |
| 640905 | 350 | 3 | 37 | 0.661 | 90 | 0.791 | 1 x 3 | 60 | 2.36 | 80 | 2.526 | 3439 | 5021 | BK |
| TBA | 500 | 3 | 37 | 0.789 | 65 | 0.919 | 1 x 3 | 110 | 2.298 | 60 | 2.418 | 4678 | 5920 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| 640853 | 8 | 3 | 6.7 | 396 | 0.653 | 0.81 | 0.052 | 50 | 55 |
| 640881 | 1 | 3 | 11.8 | 2008 | 0.128 | 0.159 | 0.046 | 130 | 145 |
| 640878 | 1/0 | 3 | 12.4 | 2534 | 0.102 | 0.127 | 0.044 | 150 | 170 |
| 640889 | 3/0 | 3 | 13.6 | 4027 | 0.064 | 0.079 | 0.042 | 200 | 225 |
| 640898 | 4/0 | 3 | 14.5 | 5078 | 0.051 | 0.063 | 0.041 | 230 | 260 |
| 640905 | 350 | 3 | 17.7 | 8400 | 0.031 | 0.039 | 0.04 | 310 | 350 |
| TBA | 500 | 3 | 16.9 | 12000 | 0.021 | 0.027 | 0.039 | 380 | 430 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.007
Updated On: Dec. 31, 2024, 11:07 p.m. UTC



