SPEC 25054
CSA TECK 90 1000V LSZH POWER CABLE
1000V Multi Conductor, 8AWG -1000 Kcmil Copper, FT4 - Flame Retardancy Rating, XLPE Insulation, Aluminum Interlocked Armour, Sunlight Resistant, -40°C - 90°C, Rated HL, AG14

Construction:
- Conductor:Class B stranded copper, compressed or compact, in accordance with ASTM B3 and B8.
- Insulation:Cross-Linked Polyethylene (XLPE), Colour Code: 2/C black, white; 3/C red, black, blue; 4/C red, black, blue, white; For cables larger than No. 2 AWG or more than 4/C, the insulation is black and numbered
- Grounding Conductors:Uninsulated Class B stranded grounding conductor
- Inner Jacket:Black Polyvinyl Chloride (PVC)
- Armor:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Low Smoke Zero Halogen (LSZH)
Applications and Features:
For exposed or concealed wiring in wet or dry locations. For use in ventilated, non-ventilated and ladder type cable troughs and ventilated flexible cableway in wet, dry, or hazardous locations. Sunlight Resistant. Typical applications are for control. lighting and power circuits in: pulp and paper mills, steel mills, food processing plants, commercial centers, mines, generating stations, refineries, industrial plants and chemical plants. Rated for 1000 lbs./FT maximum sidewall pressure.
- -40°C - CSA Cold Bend and Impact Temperature
- -25°C - Min. Installation Temperature
- 90°C - Max. Continuous Operating Temperature
Specifications:
Sample Print Legend:
{SQMTR_DUAL} SOUTHWIRE MASTER-DESIGN {CSA} LL90458 TECK 90 XLPE X/X XX AWG CU LSZH JACKET -40{D}C FT4-ST1 SUN RES AG14 90{D}C 1000V HL -- USA
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Ground | Ground Size | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | inch | inch | mil | No. x AWG | AWG | mil | inch | inch | mil | inch | lb/1000ft | lb/1000ft | |
| 138929 | 8 | 7 | 0.142 | 0.232 | 45 | 1x10 | 10 | 65 | 0.6 | 0.81 | 45 | 0.9 | 135 | 424 |
| TBA | 8 | 7 | 0.142 | 0.232 | 45 | 1x10 | 10 | 65 | 0.637 | 0.847 | 45 | 0.937 | 186 | 502 |
| TBA | 8 | 7 | 0.142 | 0.232 | 45 | 1x10 | 10 | 65 | 0.697 | 0.907 | 45 | 0.997 | 238 | 590 |
| TBA | 6 | 7 | 0.178 | 0.298 | 60 | 1x8 | 8 | 65 | 0.732 | 0.942 | 45 | 1.032 | 214 | 569 |
| TBA | 6 | 7 | 0.178 | 0.298 | 60 | 1x8 | 8 | 65 | 0.78 | 0.99 | 45 | 1.08 | 296 | 692 |
| TBA | 6 | 7 | 0.178 | 0.298 | 60 | 1x8 | 8 | 85 | 0.897 | 1.107 | 45 | 1.197 | 378 | 800 |
| TBA | 4 | 7 | 0.225 | 0.345 | 60 | 1x8 | 8 | 65 | 0.826 | 1.036 | 45 | 1.126 | 311 | 708 |
| TBA | 4 | 7 | 0.225 | 0.345 | 60 | 1x8 | 8 | 85 | 0.921 | 1.131 | 45 | 1.221 | 441 | 860 |
| TBA | 4 | 7 | 0.225 | 0.345 | 60 | 1x8 | 8 | 85 | 1.011 | 1.221 | 45 | 1.311 | 572 | 1048 |
| 138930 | 3 | 7 | 0.252 | 0.372 | 60 | 1x6 | 6 | 85 | 0.92 | 1.13 | 45 | 1.22 | 410 | 803 |
| TBA | 2 | 7 | 0.283 | 0.403 | 60 | 1x6 | 6 | 85 | 0.982 | 1.192 | 45 | 1.282 | 495 | 914 |
| TBA | 2 | 7 | 0.283 | 0.403 | 60 | 1x6 | 6 | 85 | 1.046 | 1.256 | 45 | 1.346 | 702 | 1177 |
| TBA | 2 | 7 | 0.283 | 0.403 | 60 | 1x6 | 6 | 85 | 1.151 | 1.361 | 45 | 1.451 | 909 | 1453 |
| 138931 | 1 | 19 | 0.322 | 0.482 | 80 | 1x6 | 6 | 85 | 1.14 | 1.35 | 45 | 1.44 | 602 | 1110 |
| TBA | 1 | 19 | 0.322 | 0.482 | 80 | 1x6 | 6 | 85 | 1.217 | 1.427 | 45 | 1.517 | 862 | 1450 |
| TBA | 1 | 19 | 0.322 | 0.482 | 80 | 1x6 | 6 | 85 | 1.342 | 1.652 | 45 | 1.742 | 1123 | 2112 |
| TBA | 1/0 | 19 | 0.362 | 0.522 | 80 | 1x6 | 6 | 85 | 1.304 | 1.614 | 45 | 1.704 | 1068 | 1996 |
| TBA | 1/0 | 19 | 0.362 | 0.522 | 80 | 1x6 | 6 | 85 | 1.439 | 1.749 | 45 | 1.839 | 1398 | 2456 |
| 138932 | 2/0 | 19 | 0.405 | 0.565 | 80 | 1x6 | 6 | 85 | 1.306 | 1.616 | 45 | 1.706 | 911 | 1791 |
| 668221 | 2/0 | 19 | 0.405 | 0.572 | 80 | 1x6 | 6 | 85 | 1.412 | 1.728 | 55 | 1.838 | 1327 | 2205 |
| TBA | 2/0 | 19 | 0.405 | 0.565 | 80 | 1x6 | 6 | 85 | 1.543 | 1.853 | 55 | 1.963 | 1741 | 2909 |
| TBA | 3/0 | 19 | 0.456 | 0.616 | 80 | 1x4 | 4 | 85 | 1.408 | 1.718 | 45 | 1.808 | 1175 | 2118 |
| TBA | 3/0 | 19 | 0.456 | 0.616 | 80 | 1x4 | 4 | 85 | 1.507 | 1.817 | 55 | 1.927 | 1698 | 2800 |
| TBA | 3/0 | 19 | 0.456 | 0.616 | 80 | 1x4 | 4 | 85 | 1.667 | 1.977 | 55 | 2.087 | 2221 | 3479 |
| TBA | 4/0 | 19 | 0.512 | 0.672 | 80 | 1x4 | 4 | 85 | 1.628 | 1.938 | 55 | 2.048 | 2107 | 3294 |
| TBA | 4/0 | 19 | 0.512 | 0.672 | 80 | 1x4 | 4 | 115 | 1.862 | 2.172 | 55 | 2.282 | 2767 | 4039 |
| TBA | 250 | 37 | 0.558 | 0.738 | 90 | 1x4 | 4 | 115 | 1.83 | 2.14 | 55 | 2.25 | 2468 | 3699 |
| TBA | 250 | 37 | 0.558 | 0.738 | 90 | 1x4 | 4 | 115 | 2.022 | 2.332 | 55 | 2.442 | 3247 | 4667 |
| TBA | 300 | 37 | 0.611 | 0.791 | 90 | 1x4 | 4 | 115 | 1.945 | 2.255 | 55 | 2.365 | 2934 | 4241 |
| TBA | 300 | 37 | 0.611 | 0.791 | 90 | 1x4 | 4 | 115 | 2.15 | 2.46 | 55 | 2.57 | 3870 | 5382 |
| TBA | 350 | 37 | 0.661 | 0.841 | 90 | 1x3 | 3 | 115 | 2.053 | 2.363 | 55 | 2.473 | 3438 | 4817 |
| TBA | 350 | 37 | 0.661 | 0.841 | 90 | 1x3 | 3 | 115 | 2.271 | 2.581 | 65 | 2.711 | 4530 | 6177 |
| TBA | 500 | 37 | 0.789 | 0.969 | 90 | 1x3 | 3 | 115 | 2.329 | 2.639 | 65 | 2.769 | 4841 | 6455 |
| TBA | 500 | 37 | 0.789 | 0.969 | 90 | 1x3 | 3 | 115 | 2.581 | 2.891 | 65 | 3.021 | 6400 | 8272 |
| TBA | 600 | 61 | 0.866 | 1.046 | 90 | 1x2 | 2 | 115 | 2.495 | 2.805 | 65 | 2.935 | 5819 | 7549 |
| TBA | 750 | 61 | 0.968 | 1.148 | 90 | 1x2 | 2 | 115 | 2.716 | 3.026 | 65 | 3.156 | 7222 | 9102 |
| TBA | 750 | 61 | 0.968 | 1.148 | 90 | 1x2 | 2 | 145 | 3.074 | 3.384 | 75 | 3.534 | 9561 | 11648 |
| TBA | 1000 | 61 | 1.117 | 1.297 | 90 | 1x1 | 1 | 145 | 3.098 | 3.408 | 75 | 3.558 | 9614 | 11611 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
^ Colour Code: 2/C black, Red
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp |
| 8 | 6.3 | 264 | 0.653 | 0.81 | 0.052 | 55 |
| 8 | 6.6 | 396 | 0.653 | 0.81 | 0.052 | 55 |
| 8 | 7 | 528 | 0.653 | 0.81 | 0.052 | 44 |
| 6 | 7.2 | 419 | 0.411 | 0.51 | 0.051 | 75 |
| 6 | 7.6 | 629 | 0.411 | 0.51 | 0.051 | 75 |
| 6 | 8.4 | 839 | 0.411 | 0.51 | 0.051 | 60 |
| 4 | 7.9 | 667 | 0.258 | 0.32 | 0.048 | 95 |
| 4 | 8.5 | 1001 | 0.258 | 0.32 | 0.048 | 95 |
| 4 | 9.2 | 1335 | 0.258 | 0.32 | 0.048 | 76 |
| 3 | 8.5 | 841 | 0.205 | 0.254 | 0.047 | 115 |
| 2 | 9 | 1061 | 0.162 | 0.201 | 0.045 | 130 |
| 2 | 9.4 | 1592 | 0.162 | 0.201 | 0.045 | 130 |
| 2 | 10.2 | 2123 | 0.162 | 0.201 | 0.045 | 104 |
| 1 | 10.1 | 1339 | 0.128 | 0.159 | 0.046 | 145 |
| 1 | 10.6 | 2008 | 0.128 | 0.159 | 0.046 | 145 |
| 1 | 12.2 | 2678 | 0.128 | 0.159 | 0.046 | 116 |
| 1/0 | 11.9 | 2534 | 0.102 | 0.127 | 0.044 | 170 |
| 1/0 | 12.9 | 3379 | 0.102 | 0.127 | 0.044 | 136 |
| 2/0 | 11.9 | 2129 | 0.082 | 0.102 | 0.043 | 195 |
| 2/0 | 12.9 | 3194 | 0.082 | 0.102 | 0.043 | 195 |
| 2/0 | 13.7 | 4259 | 0.082 | 0.102 | 0.043 | 156 |
| 3/0 | 12.7 | 2684 | 0.064 | 0.079 | 0.042 | 225 |
| 3/0 | 13.5 | 4027 | 0.064 | 0.079 | 0.042 | 225 |
| 3/0 | 14.6 | 5369 | 0.064 | 0.079 | 0.042 | 180 |
| 4/0 | 14.3 | 5078 | 0.051 | 0.063 | 0.041 | 260 |
| 4/0 | 16 | 6771 | 0.051 | 0.063 | 0.041 | 208 |
| 250 | 15.8 | 6000 | 0.043 | 0.053 | 0.041 | 290 |
| 250 | 17.1 | 8000 | 0.043 | 0.053 | 0.041 | 232 |
| 300 | 16.6 | 7200 | 0.036 | 0.045 | 0.041 | 320 |
| 300 | 18 | 9600 | 0.036 | 0.045 | 0.041 | 256 |
| 350 | 17.3 | 8400 | 0.031 | 0.039 | 0.04 | 350 |
| 350 | 19 | 11200 | 0.031 | 0.039 | 0.04 | 280 |
| 500 | 19.4 | 12000 | 0.021 | 0.027 | 0.039 | 430 |
| 500 | 21.1 | 16000 | 0.021 | 0.027 | 0.039 | 344 |
| 600 | 20.5 | 14400 | 0.018 | 0.024 | 0.039 | 475 |
| 750 | 22.1 | 18000 | 0.014 | 0.019 | 0.038 | 535 |
| 750 | 24.7 | 24000 | 0.014 | 0.019 | 0.038 | 428 |
| 1000 | 24.9 | 24000 | 0.011 | 0.016 | 0.037 | 615 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
Table 3 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Ground | Ground Size | Inner Jacket Thickness | Dia. Over Inner Jacket | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | mm | No. x AWG | AWG | mm | mm | mm | mm | mm | kg/km | kg/km | |
| 138929 | 8 | 7 | 3.61 | 5.89 | 1.14 | 1x10 | 10 | 1.65 | 15.24 | 20.57 | 1.14 | 22.86 | 201 | 631 |
| TBA | 8 | 7 | 3.61 | 5.89 | 1.14 | 1x10 | 10 | 1.65 | 16.18 | 21.51 | 1.14 | 23.80 | 277 | 747 |
| TBA | 8 | 7 | 3.61 | 5.89 | 1.14 | 1x10 | 10 | 1.65 | 17.70 | 23.04 | 1.14 | 25.32 | 354 | 878 |
| TBA | 6 | 7 | 4.52 | 7.57 | 1.52 | 1x8 | 8 | 1.65 | 18.59 | 23.93 | 1.14 | 26.21 | 318 | 847 |
| TBA | 6 | 7 | 4.52 | 7.57 | 1.52 | 1x8 | 8 | 1.65 | 19.81 | 25.15 | 1.14 | 27.43 | 440 | 1030 |
| TBA | 6 | 7 | 4.52 | 7.57 | 1.52 | 1x8 | 8 | 2.16 | 22.78 | 28.12 | 1.14 | 30.40 | 563 | 1191 |
| TBA | 4 | 7 | 5.72 | 8.76 | 1.52 | 1x8 | 8 | 1.65 | 20.98 | 26.31 | 1.14 | 28.60 | 463 | 1054 |
| TBA | 4 | 7 | 5.72 | 8.76 | 1.52 | 1x8 | 8 | 2.16 | 23.39 | 28.73 | 1.14 | 31.01 | 656 | 1280 |
| TBA | 4 | 7 | 5.72 | 8.76 | 1.52 | 1x8 | 8 | 2.16 | 25.68 | 31.01 | 1.14 | 33.30 | 851 | 1560 |
| 138930 | 3 | 7 | 6.40 | 9.45 | 1.52 | 1x6 | 6 | 2.16 | 23.37 | 28.70 | 1.14 | 30.99 | 610 | 1195 |
| TBA | 2 | 7 | 7.19 | 10.24 | 1.52 | 1x6 | 6 | 2.16 | 24.94 | 30.28 | 1.14 | 32.56 | 737 | 1360 |
| TBA | 2 | 7 | 7.19 | 10.24 | 1.52 | 1x6 | 6 | 2.16 | 26.57 | 31.90 | 1.14 | 34.19 | 1045 | 1752 |
| TBA | 2 | 7 | 7.19 | 10.24 | 1.52 | 1x6 | 6 | 2.16 | 29.24 | 34.57 | 1.14 | 36.86 | 1353 | 2162 |
| 138931 | 1 | 19 | 8.18 | 12.24 | 2.03 | 1x6 | 6 | 2.16 | 28.96 | 34.29 | 1.14 | 36.58 | 896 | 1652 |
| TBA | 1 | 19 | 8.18 | 12.24 | 2.03 | 1x6 | 6 | 2.16 | 30.91 | 36.25 | 1.14 | 38.53 | 1283 | 2158 |
| TBA | 1 | 19 | 8.18 | 12.24 | 2.03 | 1x6 | 6 | 2.16 | 34.09 | 41.96 | 1.14 | 44.25 | 1671 | 3143 |
| TBA | 1/0 | 19 | 9.19 | 13.26 | 2.03 | 1x6 | 6 | 2.16 | 33.12 | 41.00 | 1.14 | 43.28 | 1589 | 2970 |
| TBA | 1/0 | 19 | 9.19 | 13.26 | 2.03 | 1x6 | 6 | 2.16 | 36.55 | 44.42 | 1.14 | 46.71 | 2080 | 3655 |
| 138932 | 2/0 | 19 | 10.29 | 14.35 | 2.03 | 1x6 | 6 | 2.16 | 33.17 | 41.05 | 1.14 | 43.33 | 1356 | 2665 |
| 668221 | 2/0 | 19 | 10.29 | 14.53 | 2.03 | 1x6 | 6 | 2.16 | 35.86 | 43.89 | 1.40 | 46.69 | 1975 | 3281 |
| TBA | 2/0 | 19 | 10.29 | 14.35 | 2.03 | 1x6 | 6 | 2.16 | 39.19 | 47.07 | 1.40 | 49.86 | 2591 | 4329 |
| TBA | 3/0 | 19 | 11.58 | 15.65 | 2.03 | 1x4 | 4 | 2.16 | 35.76 | 43.64 | 1.14 | 45.92 | 1749 | 3152 |
| TBA | 3/0 | 19 | 11.58 | 15.65 | 2.03 | 1x4 | 4 | 2.16 | 38.28 | 46.15 | 1.40 | 48.95 | 2527 | 4167 |
| TBA | 3/0 | 19 | 11.58 | 15.65 | 2.03 | 1x4 | 4 | 2.16 | 42.34 | 50.22 | 1.40 | 53.01 | 3305 | 5177 |
| TBA | 4/0 | 19 | 13.00 | 17.07 | 2.03 | 1x4 | 4 | 2.16 | 41.35 | 49.23 | 1.40 | 52.02 | 3136 | 4902 |
| TBA | 4/0 | 19 | 13.00 | 17.07 | 2.03 | 1x4 | 4 | 2.92 | 47.29 | 55.17 | 1.40 | 57.96 | 4118 | 6011 |
| TBA | 250 | 37 | 14.17 | 18.75 | 2.29 | 1x4 | 4 | 2.92 | 46.48 | 54.36 | 1.40 | 57.15 | 3673 | 5505 |
| TBA | 250 | 37 | 14.17 | 18.75 | 2.29 | 1x4 | 4 | 2.92 | 51.36 | 59.23 | 1.40 | 62.03 | 4832 | 6945 |
| TBA | 300 | 37 | 15.52 | 20.09 | 2.29 | 1x4 | 4 | 2.92 | 49.40 | 57.28 | 1.40 | 60.07 | 4366 | 6311 |
| TBA | 300 | 37 | 15.52 | 20.09 | 2.29 | 1x4 | 4 | 2.92 | 54.61 | 62.48 | 1.40 | 65.28 | 5759 | 8009 |
| TBA | 350 | 37 | 16.79 | 21.36 | 2.29 | 1x3 | 3 | 2.92 | 52.15 | 60.02 | 1.40 | 62.81 | 5116 | 7168 |
| TBA | 350 | 37 | 16.79 | 21.36 | 2.29 | 1x3 | 3 | 2.92 | 57.68 | 65.56 | 1.65 | 68.86 | 6741 | 9192 |
| TBA | 500 | 37 | 20.04 | 24.61 | 2.29 | 1x3 | 3 | 2.92 | 59.16 | 67.03 | 1.65 | 70.33 | 7204 | 9606 |
| TBA | 500 | 37 | 20.04 | 24.61 | 2.29 | 1x3 | 3 | 2.92 | 65.56 | 73.43 | 1.65 | 76.73 | 9524 | 12310 |
| TBA | 600 | 61 | 22.00 | 26.57 | 2.29 | 1x2 | 2 | 2.92 | 63.37 | 71.25 | 1.65 | 74.55 | 8660 | 11234 |
| TBA | 750 | 61 | 24.59 | 29.16 | 2.29 | 1x2 | 2 | 2.92 | 68.99 | 76.86 | 1.65 | 80.16 | 10748 | 13545 |
| TBA | 750 | 61 | 24.59 | 29.16 | 2.29 | 1x2 | 2 | 3.68 | 78.08 | 85.95 | 1.91 | 89.76 | 14228 | 17334 |
| TBA | 1000 | 61 | 28.37 | 32.94 | 2.29 | 1x1 | 1 | 3.68 | 78.69 | 86.56 | 1.91 | 90.37 | 14307 | 17279 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
^ Colour Code: 2/C black, Red
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 4 – Electrical and Engineering Data (Metric)
| Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
|---|---|---|---|---|---|---|
| AWG/Kcmil | mm | newton | Ω/km | Ω/km | Ω/km | Amp |
| 8 | 160.02 | 1175 | 2.1424 | 2.66 | 0.1706 | 55 |
| 8 | 167.64 | 1762 | 2.1424 | 2.66 | 0.1706 | 55 |
| 8 | 177.80 | 2350 | 2.1424 | 2.66 | 0.1706 | 44 |
| 6 | 182.88 | 1865 | 1.3484 | 1.67 | 0.1673 | 75 |
| 6 | 193.04 | 2799 | 1.3484 | 1.67 | 0.1673 | 75 |
| 6 | 213.36 | 3734 | 1.3484 | 1.67 | 0.1673 | 60 |
| 4 | 200.66 | 2968 | 0.8465 | 1.05 | 0.1575 | 95 |
| 4 | 215.90 | 4454 | 0.8465 | 1.05 | 0.1575 | 95 |
| 4 | 233.68 | 5941 | 0.8465 | 1.05 | 0.1575 | 76 |
| 3 | 215.90 | 3742 | 0.6726 | 0.83 | 0.1542 | 115 |
| 2 | 228.60 | 4721 | 0.5315 | 0.66 | 0.1476 | 130 |
| 2 | 238.76 | 7084 | 0.5315 | 0.66 | 0.1476 | 130 |
| 2 | 259.08 | 9447 | 0.5315 | 0.66 | 0.1476 | 104 |
| 1 | 256.54 | 5959 | 0.4199 | 0.52 | 0.1509 | 145 |
| 1 | 269.24 | 8936 | 0.4199 | 0.52 | 0.1509 | 145 |
| 1 | 309.88 | 11917 | 0.4199 | 0.52 | 0.1509 | 116 |
| 1/0 | 302.26 | 11276 | 0.3346 | 0.42 | 0.1444 | 170 |
| 1/0 | 327.66 | 15037 | 0.3346 | 0.42 | 0.1444 | 136 |
| 2/0 | 302.26 | 9474 | 0.2690 | 0.33 | 0.1411 | 195 |
| 2/0 | 327.66 | 14213 | 0.2690 | 0.33 | 0.1411 | 195 |
| 2/0 | 347.98 | 18953 | 0.2690 | 0.33 | 0.1411 | 156 |
| 3/0 | 322.58 | 11944 | 0.2100 | 0.26 | 0.1378 | 225 |
| 3/0 | 342.90 | 17920 | 0.2100 | 0.26 | 0.1378 | 225 |
| 3/0 | 370.84 | 23892 | 0.2100 | 0.26 | 0.1378 | 180 |
| 4/0 | 363.22 | 22597 | 0.1673 | 0.21 | 0.1345 | 260 |
| 4/0 | 406.40 | 30131 | 0.1673 | 0.21 | 0.1345 | 208 |
| 250 | 401.32 | 26700 | 0.1411 | 0.17 | 0.1345 | 290 |
| 250 | 434.34 | 35600 | 0.1411 | 0.17 | 0.1345 | 232 |
| 300 | 421.64 | 32040 | 0.1181 | 0.15 | 0.1345 | 320 |
| 300 | 457.20 | 42720 | 0.1181 | 0.15 | 0.1345 | 256 |
| 350 | 439.42 | 37380 | 0.1017 | 0.13 | 0.1312 | 350 |
| 350 | 482.60 | 49840 | 0.1017 | 0.13 | 0.1312 | 280 |
| 500 | 492.76 | 53400 | 0.0689 | 0.09 | 0.1280 | 430 |
| 500 | 535.94 | 71200 | 0.0689 | 0.09 | 0.1280 | 344 |
| 600 | 520.70 | 64080 | 0.0591 | 0.08 | 0.1280 | 475 |
| 750 | 561.34 | 80100 | 0.0459 | 0.06 | 0.1247 | 535 |
| 750 | 627.38 | 106800 | 0.0459 | 0.06 | 0.1247 | 428 |
| 1000 | 632.46 | 106800 | 0.0361 | 0.05 | 0.1214 | 615 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.
Revision: 1.000.005
Updated On: Oct. 23, 2026, 11:19 a.m. UTC